APC BX1400UI

APC Back-UPS BX1400UI User Manual

Model: BX1400UI | Brand: APC

1. Introducció

The APC Back-UPS BX1400UI is an Uninterruptible Power Supply (UPS) designed to protect your electronic equipment from power outages, surges, and spikes. Featuring Line Interactive Technology and Automatic Voltage Regulation (AVR), this unit provides reliable battery backup and surge protection for connected devices. It includes six IEC 320 C13 outlets, a USB interface for communication, and data line protection.

Davant view of the APC Back-UPS BX1400UI Uninterruptible Power Supply, showing the power button and LED indicators.

Figura 1: Frontal view of the APC Back-UPS BX1400UI.

2. Informació important de seguretat

  • Risc elèctric: Aquesta unitat conté un alt volumtage components. Do not attempt to open the UPS casing, especially when connected to power. Refer all servicing to qualified personnel.
  • Connexió directa: Always connect the UPS directly to a wall outlet. Do not use surge protectors, extension cords, or power strips with the UPS input.
  • Ventilació: Ensure adequate ventilation around the UPS. Do not block ventilation openings.
  • Olor inicial: A new unit may emit a distinct odor, often described as similar to burnt plastic. This is normal and typically dissipates after a few weeks of continuous operation in a well-ventilated area. It is not indicative of a malfunction.
  • Substitució de la bateria: User-performed battery replacement during the warranty period will void the product warranty. Refer to the Maintenance section for details.

3. Contingut del paquet

Comproveu que el vostre paquet contingui els elements següents:

  • APC Back-UPS BX1400UI Unit
  • Two (2) IEC-C13 to IEC-C14 power cables (for connecting devices to the UPS)
  • Manual d'usuari (aquest document)

Nota: The input power cable (for connecting the UPS to the wall outlet) and the USB communication cable are typically no inclòs and must be purchased separately if needed.

4. Configuració

4.1. Unpacking and Battery Connection

  1. Carefully remove the UPS from its packaging.
  2. Locate the yellow battery connector on the rear panel of the UPS. This connector is typically disconnected for safe transport.
  3. Push the yellow battery connector firmly into its socket until it clicks into place. This activates the UPS battery circuits.

4.2. Connexió a l'alimentació

  1. Connect the UPS to a grounded 230V AC wall outlet using an appropriate IEC-320 C14 input power cable (not included).
  2. Ensure the connection is direct to the wall outlet. Do not use surge protectors or extension cords.
  3. Allow the UPS to charge for at least 10 hours before connecting critical equipment to ensure full battery runtime.

4.3. Connexió d'equips

The BX1400UI features six IEC 320 C13 outlets for connecting your devices.

  • Battery Backup & Surge Protection Outlets: All six IEC-C13 outlets provide both battery backup and surge protection. Connect your computer, monitor, and other critical electronics to these outlets.
  • Data Line Protection: The rear panel includes RJ-11 ports labeled "DSL/Modem/Fax/Phone" for protecting your telephone or DSL line from surges. These ports are not suitable for Ethernet network connections.
  • Interfície USB: Connect a USB Type B cable (not included) from the UPS to your computer for communication and to enable shutdown software functionality.
Rear panel of the APC Back-UPS BX1400UI, showing IEC-C13 outlets, USB port, battery connector, circuit breaker, and data line protection ports.

Figure 2: Rear panel connections of the APC Back-UPS BX1400UI.

5. Instruccions de funcionament

5.1. Encès / apagat

  • Per encendre: Press and hold the power button on the front panel until you hear a short beep. The UPS will perform a self-test, and the 'On Line' LED will illuminate green.
  • Per apagar: Premeu i manteniu premut el botó d'engegada fins que el SAI s'apagui.

5.2. Indicadors LED

The front panel features LED indicators to show the UPS status:

  • En línia (LED verd): Indicates the UPS is operating on utility power and providing power to connected equipment.
  • On Battery (Yellow LED): Indicates the UPS is operating on battery power during a power outage or brownout. A humming noise is normal during battery operation.
  • Canviar la bateria (LED vermell): Indicates the battery needs to be replaced.
  • Sobrecàrrega (LED vermell): Indicates that the connected equipment exceeds the UPS's capacity. Disconnect non-essential equipment immediately.

5.3. Volum automàtictagReglament (AVR)

El SAI corregeix automàticament els volums menorstage fluctuations (sags and surges) without switching to battery power, thus preserving battery life. If voltage fluctuations exceed the AVR's correction range, the UPS will switch to battery power.

6. Característiques clau

  • Line Interactive Technology: Provides stable power by regulating voltage without constantly switching to battery.
  • Volum automàtictage Regulació (AVR): Corrects minor voltage fluctuacions sense utilitzar energia de la bateria.
  • Còpia de seguretat de la bateria: Supplies power to connected equipment during outages.
  • Protecció contra sobretensions: Protects connected devices from damaging power surges and spikes.
  • 6 IEC 320 C13 Outlets: Standard outlets for computer equipment.
  • Interfície USB: Enables communication with a computer for monitoring and controlled shutdown.
  • Data Line Protection: Safeguards telephone/DSL lines from surges.

7. Ús de programari

The APC Back-UPS BX1400UI supports USB Human Interface Device (HID) class specifications, allowing it to be recognized by most operating systems without special drivers.

7.1. APC PowerChute Personal Edition (Windows)

For advanced monitoring and management on Windows systems, download the APC PowerChute Personal Edition software from the official APC weblloc. Aquest programari us permet:

  • Monitor UPS status, power consumption, and battery charge.
  • Configura l'apagada automàtica de l'ordinador durant un apagada prolongadatages.
  • Adjust UPS settings, such as alarm behavior (e.g., disable the beeper during battery operation).
  • Perform self-tests to ensure proper UPS functionality.

7.2. Linux Support (apcupsd / NUT)

For Linux environments, the UPS can be managed using `apcupsd` or Network UPS Tools (NUT). These tools provide similar monitoring and shutdown capabilities. Refer to the documentation for `apcupsd` or NUT for configuration details, typically involving specifying `UPSCABLE usb` and `UPSTYPE usb` for `apcupsd`, or using the `usbhid-ups` driver for NUT.

8. Manteniment

8.1. Substitució de la bateria

The APC Back-UPS BX1400UI uses two 12V 7.2Ah sealed lead-acid batteries. The recommended replacement battery pack is APC RBC113.

  • During Warranty: If the unit is still under its 2-year warranty, battery replacement must be performed by Schneider Electric IT (SEIT) customer service. User-performed battery replacement during the warranty period will automatically void the warranty.
  • After Warranty: After the warranty period, batteries can be replaced by the user. However, due to the presence of high voltage components even when disconnected, it is highly recommended that this operation be performed by specialized personnel. If you choose to replace the batteries yourself, exercise extreme caution.
  • S'ha acabat el procedimentview (for experienced users only): Disconnect the UPS from all power sources and connected equipment. Disconnect the yellow battery connector. Remove the rear panel screws, then the front panel (which is snap-fitted), and additional screws. Carefully access the battery compartment. Note the orientation and wiring of the existing batteries (taking photos is recommended) to ensure correct installation of the new batteries.

8.2. Reinicialització de l'interruptor

In case of an overload, the UPS may trip its circuit breaker. To reset, disconnect some equipment from the UPS, then press the circuit breaker button located on the rear panel (refer to Figure 2).

9. Solució De Problemes

ProblemaCausa possibleSolució
El SAI no s'encén.Battery connector disconnected; No input power.Ensure yellow battery connector is fully inserted. Verify UPS is plugged into a live wall outlet.
Initial strong odor.New unit manufacturing residue.This is normal. Ensure adequate ventilation. Odor will dissipate over time (typically a few weeks).
UPS emits a humming noise.Operating on battery power; Normal electrical noise.Humming is normal when on battery. If persistent and loud on utility power, ensure proper ventilation and check for loose connections.
'Overload' LED is lit.Massa equips connectats.Disconnect non-essential equipment. Press the circuit breaker reset button on the rear panel.
'Replace Battery' LED is lit.Bateria a punt d'arribar al final de la seva vida útil.Contact APC support or a qualified technician for battery replacement. Refer to Section 8.1.
Curt temps de funcionament de la bateria.Battery not fully charged; Battery nearing end of life; Excessive load.Ensure initial 10-hour charge. Reduce connected load. Consider battery replacement if old.

For more detailed troubleshooting, refer to the complete user manual available on the APC weblloc.

10. Especificacions

CaracterísticaEspecificació
ModelBX1400UI
Capacitat (VA/Watts)1400 VA / 700 W
Entrada Voltage230 V AC
Freqüència d'entrada50 Hz
Vol. De sortidatage230V AC (simulated sine wave on battery)
Sortides de sortida6 x IEC 320 C13 (Battery Backup & Surge Protection)
Classificació de protecció contra sobretensions273 Joules
Tipus de bateriaÀcid de plom segellat
Configuració de la bateria2 x 12 V 7.2 Ah
Temps de recàrrega típic8 hores (fins al 90% de la capacitat)
Runtime (at 700W load)Approximately 1 minute
Runtime (at 100W load)Uns 60 minuts
Dimensions (A x A x P)21.5 cm x 13 cm x 33.6 cm
Pes4.7 kg
Ports d’interfícieUSB Type B, RJ-11 (Data Line Protection)
Runtime graph for APC Back-UPS 1400VA, 230V, AVR, IEC Sockets (BX1400UI), showing battery runtime in minutes versus load in watts.

Figure 3: Typical runtime graph for APC Back-UPS 1400VA.

11. Garantia i Suport

11.1. Garantia del producte

The APC Back-UPS BX1400UI comes with a Garantia limitada d'2 any des de la data de compra. Aquesta garantia cobreix els defectes de materials i de fabricació en condicions d'ús normal. Conserveu el comprovant de compra per a reclamacions de garantia.

Important: Unauthorized opening of the unit or user-performed battery replacement during the warranty period will void the warranty.

11.2. Suport tècnic

For technical assistance, troubleshooting, or warranty service, please contact APC by Schneider Electric customer support. Visit the official APC website for contact information specific to your region, including phone numbers and online support resources.

Online resources often include FAQs, knowledge bases, and downloadable manuals that can provide further assistance.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.