Datakom DPR-02

DPR-02 Voltage Protection Controller User Manual

Model: DPR-02

1. Introducció

The Datakom DPR-02 is a three-phase (line to neutral) voltage protection relay engineered to safeguard electrical systems from various voltage anomalies. It provides robust protection against over voltage, sota voltage, and incorrect phase rotation, making it suitable for critical applications in distribution substations, generators, motors, transformers, and compensation systems.

This device offers adjustable over and under voltage limits, along with configurable trip and reset delays, allowing for precise customization to specific system requirements. Both maximum and minimum voltage limits can be set or disabled using trimmers located on the front panel. Corresponding delay times are also adjusted via dedicated trimmers.

Datakom DPR-02 Voltage Protection Controller front view

Figura 1: Frontal view of the DPR-02 Voltage Protection Controller, showing adjustment knobs and terminals.

2. Característiques

  • DIN Rail mounted for easy installation.
  • Adjustable over voltage limit (L-N).
  • Adjustable under voltage limit (L-N).
  • Adjustable TRIP and RESET Delays for precise control.
  • Integrated phase sequence protection.
  • Detection and protection against phase failure.
  • Overvoltagprotecció.
  • Protection against insufficient supply.
  • 6A/277VAC relay output.
  • Suitable for 1-3 phase gasoline and diesel gensets.
  • Designed for front panel mounting.
  • Survives cranking dropouts.
  • Generator protection with built-in alarms and warnings.
Datakom DPR-02 features and operation overview

Figura 2: Mésview of DPR-02 features and operational principles.

3. Configuració i instal·lació

The DPR-02 is designed for DIN rail mounting. Proper installation is crucial for reliable operation. Ensure all power is disconnected before proceeding with wiring.

3.1 Connexions de terminals

The device features clearly labeled terminals for input and output connections:

  • Terminals d'entrada: N (Neutral), L1, L2, L3 (Phase voltage entrades).
  • Output Relay Terminals: 1 (NC - Normally Closed), 2 (COM - Common), 3 (NO - Normally Open).

3.2 Esquema de cablejat

Refer to the connection diagram below for typical wiring in a motor protection application. Ensure all connections are secure and comply with local electrical codes.

Datakom DPR-02 Installation Diagram

Figure 3: Typical installation diagram for the DPR-02, showing connections for a 3-phase motor.

Datakom DPR-02 Connection Diagram and Specifications

Figure 4: Detailed connection diagram, LED indicators, and technical specifications.

4. Principis de funcionament

The DPR-02 continuously monitors the line-to-neutral voltages (L-N) and phase sequence to provide comprehensive protection.

4.1 voltage Protection (Under/Over Voltage)

If any phase voltage exceeds the set MAX limit, the "U>" LED illuminates, and the adjusted Delay timer begins to count. If the fault persists beyond the delay, the relay deactivates, the "OUT" LED turns off, and the "U>" LED turns off. Similarly, if any measured voltage drops below the set MIN limit, the "U<" LED illuminates, and the Delay timer starts. If the condition persists, the relay deactivates, and the "OUT" LED turns off, and the "U<" LED turns off.

When the MAX or MIN Voltage trimmer is adjusted to the "OFF" position, the related voltage protection will be disabled.

Tot voltages within adjusted MIN-MAX limits will cause the "U<" and "U>" LEDs to turn off. If the adjusted Reset Delay timer counts to its expiration, the relay output is activated, and the "OUT" LED illuminates.

4.2 Phase Failure Protection

Si el voltage of any phase falls below 50% of the nominal value, the "U<" LED illuminates, and the relay output immediately deactivates, turning off the "OUT" LED.

4.3 Sobrecàrregatage Protecció

Si el voltage of any phase goes 50% above the nominal value, the "U>" LED illuminates, and the relay output immediately deactivates, turning off the "OUT" LED.

4.4 Phase Sequence Protection

If the phase sequence is reversed, both "U<" and "U>" LEDs flash, the relay output deactivates, and the "OUT" LED turns off.

4.5 Indicadors LED

The DPR-02 features several LED indicators to provide status feedback:

U<U>ONFORADescripció
ONONONVoltages OK
ONONSota el voltage advertència
ONSota el voltage viatge
ONONMés de voltage advertència
ONMés de voltage viatge
FLASHONDisparo de seqüència de fase
  • ACTIVITAT: LED d'alimentació (verd)
  • SORTIDA: Relay output LED (yellow)
  • U<: Sota el voltage Warning LED (red)
  • U>: Més del voltage Warning LED (red)

5. Manteniment

The DPR-02 is designed for long-term, reliable operation with minimal maintenance. However, periodic checks can help ensure optimal performance:

  • Inspecció visual: Inspeccioneu periòdicament la unitat per detectar qualsevol signe de danys físics, connexions soltes o acumulació excessiva de pols.
  • Neteja: Si cal, netegeu suaument l'exterior de la unitat amb un drap sec i suau. No utilitzeu netejadors líquids ni dissolvents.
  • Integritat de la connexió: Ensure all terminal connections remain tight and secure. Loose connections can lead to intermittent operation or damage.

All maintenance should be performed by qualified personnel with power disconnected.

6. Solució De Problemes

If the DPR-02 is not functioning as expected, consider the following common issues:

  • Sense alimentació/LED apagats: Comproveu el volum de subministramenttage to the N, L1, L2, L3 terminals. Ensure the power source is active and within the specified voltage gamma.
  • Unexpected Relay Trip: Verifiqueu que el volum mesurattages are within the set MIN/MAX limits. Check for correct phase sequence. Review the delay settings (Trip Delay, Reset Delay) to ensure they are appropriate for the application.
  • Relé no activat: Confirmeu que l'entrada voltages are stable and within the acceptable operating range. Check the status of the U< and U> LEDs to identify any active voltage falles.
  • Incorrect Phase Sequence Indication: Double-check the L1, L2, L3 phase connections for correct order.

If issues persist after checking these points, consult a qualified electrician or contact Datakom technical support.

7. Especificacions

Detailed technical specifications for the Datakom DPR-02:

ParàmetreValor
Oferta nominal Voltage230V-AC (L-N)
Subministrament Voltage Rang150-300 V-AC (L-N)
Tipus de subministramentCapacitive, 1-phase
Interval de freqüència47-63 Hz
Consum d'energia30VA / 2W (max)
Mètode de mesuraTrue RMS, line to neutral
Voltage Adjustment Accuracy3 %
Precisió de repetició0.5 %
Més de voltage Viatge240-300V-AC (L-N) adjustable
Sota Voltage Viatge150-210V-AC (L-N) adjustable
Trip Delay Setup0.5 - 20 sec. adjustable
Reset Delay Setup0.5 - 20 sec. adjustable
Sortida de relé6A @ 277V-AC, 1800VA, 300W
Gamma de cables de terminals2.5 mm² (12 AWG)
Screwing Force2.4 Nm (3.6 Lb)
Temperatura de funcionament-30 °C (-22 °F) a 70 °C (158 °F)
Temperatura d'emmagatzematge-40 °C (-40 °F) a 80 °C (176 °F)
Humitat màxima95% sense condensació
Dimensions (AxAxP)36.0 x 90.6 x 58.4 mm (1.42 x 3.57 x 2.30 polzades)
Pes~90 g (3.17 oz)
Instal·lacióDIN Rail mounted
Material de la caixaHigh temp. ABS/PC (UL94-V0)
Protecció IPIP30
Conformity (EU Directives)2006/95/CE (volum baixtage), 2004/108/CE (EMC)
Norms of ReferenceEN 61010 (safety requirements), EN 60255-6, EN 61326 (EMC requirements)
País d'origenTurquia

8. Garantia i Suport

For information regarding product warranty, technical support, or service, please contact your authorized Datakom distributor or visit the official Datakom website. Ensure you have your product model number (DPR-02) and purchase details available when seeking support.

© 2024 Datakom. All rights reserved.

Documents relacionats - DPR-02

Preview DPR-02 Voltage Protection Relay (Line to Neutral) - Datakom
The Datakom DPR-02 is a three-phase voltage protection relay for line-to-neutral applications. It protects against over-voltage, baix voltage, and phase rotation issues in distribution substations, generators, motors, transformers, and compensation systems. Features include adjustable voltage limits, trip and reset delays, and phase sequence protection.
Preview DKM-401 Digital Multimeter: Installation and Technical Specifications
Comprehensive guide for the DATAKOM DKM-401 Digital Multimeter, covering installation, electrical safety, technical specifications, and operational functions for 3-phase distribution panels.
Preview DATAKOM SC4875-R2 High Efficiency Solar Charger Technical Specifications
Especificacions tècniques i operativesview of the DATAKOM SC4875-R2 48VDC 4000W high-efficiency solar charger, featuring MPPT technology and hot plug-in capabilities.
Preview DATAKOM DKM-0216 Alarm Anons Ünitesi - Teknik Özellikler ve Fonksiyonlar
DATAKOM DKM-0216 Alarm Anons Ünitesi hakkında detaylı bilgiler, enerji ve otomasyon sistemleri için özellikler, teknik şartnameler, kurulum yönergeleri ve operasyonel fonksiyonlar.
Preview DATAKOM BC4860-R2 High Efficiency Telecom Rectifier - Technical Specifications
Detailed technical specifications, features, and performance characteristics of the DATAKOM BC4860-R2 high-efficiency telecom rectifier. This 3000W, 48VDC unit offers 97% peak efficiency, universal input voltage, and advanced protection features for telecommunications applications.
Preview Datakom BC9635-R2 High Efficiency Telecom Rectifier - 4000W
Tècnic acabatview and specifications for the Datakom BC9635-R2, a high-efficiency 4000W telecom rectifier featuring 96 VDC output, hot plug-in capability, and advanced power management.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.