1. Introducció
This manual provides detailed instructions for the installation, operation, and maintenance of the GEYA Mini ATS Automatic/Manual Transfer Switch, Model 3P-63A-110VAC. This device is designed to automatically or manually switch between two power sources, such as grid power, a generator, or a photovoltaic system, ensuring continuous power supply to your load.

Figure 1: GEYA Mini ATS Automatic/Manual Transfer Switch (Model 3P-63A-110VAC)
2. Informació de seguretat
Please read and understand all safety warnings and instructions before installing or operating this device. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- La instal·lació i el manteniment només els ha de dur a terme personal qualificat.
- Always disconnect all power sources before working on the switch or connected circuits.
- Assegureu-vos de posar a terra adequadament per evitar descàrregues elèctriques.
- Verifiqueu el voltage and current ratings of the switch match your application requirements.
- No feu funcionar l'interruptor en llocs humits o secs.amp condicions.
- El voltage of the common and backup power supply must be 85-110% of the rated voltage.
- The current cannot be less than 5A, otherwise the coil may overheat or combust.
- The backup power of the product must be a stable city power, otherwise the product will not switch automatically.
3. Característiques del producte
- Compatibilitat amb fonts d'alimentació dual: Designed for automatic or manual conversion between two power supplies (e.g., mains, generator, photovoltaic).
- Més de voltage i Under-Voltage Protection (110V/50Hz):
- Undervoltage value: 85V, Recovery value: 95V (± 5V)
- Overvoltage value: 145V, Recovery value: 130V (± 5V)
- Més de voltage i Under-Voltage Protection (220V/50Hz):
- Undervoltage value: 175V, Recovery value: 195V (± 5V)
- Overvoltage value: 260V, Recovery value: 240V (± 5V)
- Canvi automàtic: When the normal power supply is abnormal, the device automatically switches to the backup power supply. It switches back to normal power when restored.
- Llums indicadores: Equipped with indicator lights for both power sources (A and B) to show operational status.
- Fast Switching: Power switch completed within 100 milliseconds, minimizing power interruptions.
- Control intel·ligent: Features self-restoring, over-voltage, i sota-voltagprotecció.
- Construcció duradora: Utilizes silver contacts and copper terminals for reliability and longevity.
- Muntatge en carril DIN: Compatible with universal DIN rail mounting for easy installation.

Figure 2: Explanation of Automatic Transfer Switch Function

Figure 3: Fast Switching and Intelligent Control Capabilities

Figure 4: Internal Components and Installation Method
4. How to Choose Your Model
Refer to the table below to select the appropriate ATS model based on your live line voltage and connection requirements.

Figure 5: Model Selection Guide
| Live Line Voltage | Suitable for US Voltage Sistema | Must Connect with Neutral Line | Producte recomanat |
|---|---|---|---|
| One Live Line Voltage 110V | 110/230V | 1 Live line + 1 Neutral line | ATS-2P-63A-110V |
| 2 Live line + 1 Neutral line | ATS-3P-63A-110V | ||
| 3 Live line + 1 Neutral line | ATS-4P-63A-110V | ||
| One Live Line Voltage 230V | 220/400V | 1 Live line + 1 Neutral line | ATS-2P-63A-220V |
| 2 Live line + 1 Neutral line | ATS-3P-63A-220V | ||
| 3 Live line + 1 Neutral line | ATS-4P-63A-220V |
Nota: El voltage of the common and backup power supply must be 85-110% of the rated voltage, and the current cannot be less than 5A, otherwise the coil will heat up or even spontaneously combust. The backup power of the product must be a stable city power, otherwise the product will not switch automatically.
5. Dimensions del producte
The GEYA Mini ATS is designed for compact installation with universal DIN rail mounting. Refer to the diagram below for detailed dimensions.

Figure 6: Product Dimensions (in mm)
- Longitud total: 125 mm
- Amplada total: 78.5 mm
- Alçada total: 103 mm
- DIN Rail Mounting Height: 35 mm
- Safety Distance S1: ≥ 30 mm
- Safety Distance S2: ≥ 203 mm

Figure 7: Detailed Dimensions and Safety Clearances
6. Especificacions tècniques
Below are the technical specifications for the GEYA Mini ATS Automatic/Manual Transfer Switch.

Figure 8: Technical Parameter Table
| Paràmetre | Especificació (63A) | Especificació (100A) |
|---|---|---|
| Rated current Ie A | 63A | 100A |
| Aïllament voltagi Ui | 690 V CA | |
| Vol d’entradatagi Ue | AC 110V / AC 220V | |
| Grau | PC grade: able to make and withstand not to break short-circuit current | |
| Utilitza la categoria | AC-33iB | |
| Pol | 2P/3P/4P | |
| Pes (kg) | 0.81 | - |
| La vida | Electrical: 2000 times; Mechanical: 5000 times | |
| Rated conditional short circuit current | 50 kA | |
| SCPD (fuse) | RT16-00-63A | RT16-00-100A |
| Resistència d'impuls nominal | 8kV | |
| Control circuit (Input voltage: AC 110V) | Control nominal voltage Us: AC110V, 50Hz; Correct working condition 85%-110% Us | |
| Control circuit (Input voltage: AC 230V) | Control nominal voltage Us: AC230V, 50Hz; Correct working condition 85%-110% Us | |
| Freqüència de corrent | 50/60Hz | |
| Contact transfer time | <50 ms | |
| Temps de transferència operativa | <50 ms | |
| Return transfer time | <50 ms | |
| Fora de temps | -55 °C ~ +40 °C | |
| Interval de temperatura | Average temperature not more than 35°C in 24 hours | |

Figure 9: Main Technical Parameters for W2R-100 Series
7. Configuració i instal·lació
7.1 Identificació de components
Familiarize yourself with the different parts of the transfer switch before proceeding with installation.

Figure 10: Analysis of Each Part Name (3P Poles)
- Terminal de senyal: For control signals.
- Source A Power Inlet Terminal: Connection point for Main Power (Source A).
- Source A Power Indicator: Indicates status of Source A.
- Auto/Manual Mode Switch: Selector for operation mode.
- Source B Power Indicator: Indicates status of Source B.
- Transfer Handle: Manual override for switching power sources.
- Source B Power Inlet Terminal: Connection point for Standby Power (Source B).
- Power Output (Load Port): Connection point for the electrical load.
7.2 Esquema de cablejat
Follow the wiring diagrams carefully to ensure correct and safe installation. The device supports connection to mains, generator, or photovoltaic systems.

Figura 11: Example of Photovoltaic and Generator Combination Wiring

Figure 12: General Wiring Diagram (3P Poles)

Figure 13: Various Product Wiring Diagram Examples
Passos de cablejat:
- Mount the ATS on a DIN rail in a suitable enclosure.
- Connect the Main Power (Source A) to the "Source A Power Inlet Terminal" (AR, AS, AT, AN).
- Connect the Standby Power (Source B) to the "Source B Power Inlet Terminal" (BR, BS, BT, BN).
- Connect the load to the "Power Output (Load Port)".
- Ensure all connections are secure and tightened to prevent loose contacts and overheating.
- Connect the control lines (Common Neutral line, Common control line, Alternate control line) as per the diagram for automatic operation.
Video: Wiring Example and Operation Demonstration
Video 1: This video demonstrates the wiring process and basic operation of the GEYA ATS (W2R) unit. It shows how to connect power sources and loads, and how the switch responds to power changes.
8. Instruccions de funcionament
The GEYA Mini ATS can operate in both automatic and manual modes.
8.1 Mode automàtic
- Set the "Auto/Manual Mode Switch" to AUTO.
- When normal power supply A is working properly, the A (red light) indicator will be on.
- If normal power supply A becomes abnormal (e.g., power outage, under/over voltage), the A (green light) indicator will go off, and the switch will automatically transfer the load to backup power supply B.
- When normal power supply A recovers, the switch will automatically transfer the load back to power supply A.
8.2 Mode manual
- Set the "Auto/Manual Mode Switch" to MANUAL.
- To select power supply A, manually operate the red transfer handle towards power supply A. The red light for A will turn on.
- To select power supply B, manually operate the red transfer handle towards power supply B. The red light for B will turn on.
- In manual mode, the switch will not automatically transfer power.
Video: Automatic/Manual Transfer Switch Operation
Video 2: This video illustrates the functionality of the GEYA Automatic/Manual Transfer Switch (W2R), demonstrating how it switches between power sources.
Video: ATS Usage Demonstration
Video 3: A brief demonstration of the GEYA ATS (W2R) in action, showing the power transfer process.
9. Manteniment
The GEYA Mini ATS is designed for reliable operation with minimal maintenance. However, periodic checks are recommended to ensure optimal performance and safety.
- Inspecció visual: Regularly inspect the switch for any signs of physical damage, loose connections, or discoloration due to overheating.
- Estanquitat del terminal: Periodically check and tighten all terminal screws to ensure good electrical contact.
- Neteja: Keep the switch free from dust, dirt, and moisture. Use a dry, soft cloth for cleaning.
- Prova de funcionalitat: Occasionally test the automatic transfer function by temporarily disconnecting the main power source (if safe to do so) to ensure the switch transfers to the backup source as expected.
10. Solució De Problemes
If you encounter issues with your GEYA Mini ATS, consider the following troubleshooting steps:
- No Power Transfer:
- Check if both power sources (A and B) are active and within the specified voltage range (85-110% of rated voltagi).
- Ensure the "Auto/Manual Mode Switch" is set to AUTO for automatic operation.
- Verifiqueu que totes les connexions de cablejat siguin segures i correctes segons el diagrama de cablejat.
- Check if the current is below 5A, which can cause the coil to malfunction.
- Indicator Lights Not Functioning:
- Confirm that the corresponding power source is active.
- Inspect for loose internal connections (requires professional inspection).
- Sobreescalfament:
- Ensure the current is not below 5A.
- Comproveu si hi ha connexions de terminals soltes.
- Verify the load does not exceed the rated current of the switch.
For persistent issues or complex problems, contact qualified electrical personnel or GEYA customer support.
11. Garantia i Suport
GEYA products are manufactured to high-quality standards. For warranty information and technical support, please refer to the official GEYA weblloc web o poseu-vos en contacte amb el vostre distribuïdor local. Conserveu el rebut de compra per a reclamacions de garantia.
Per obtenir més ajuda, visiteu el GEYA Store on Amazon.