1. Introducció
This manual provides detailed instructions for the installation, operation, and maintenance of the MOLLOM 0.75KW 1HP G70 Variable Frequency Drive (VFD). This VFD is designed to control the speed of three-phase AC motors, offering precise control for applications such as CNC routers, milling machines, drilling machines, and various other industrial equipment. It supports both single-phase and three-phase 220V input and provides a three-phase 220V output with a frequency range of 0-3000 Hz.
Key features include a user-friendly keyboard design, digital display, RS485 communication port, and strong anti-jamming capability. Please read this manual thoroughly before installation and operation to ensure safe and efficient use of the device.
2. Instruccions de seguretat
Seguretat elèctrica:
- Ensure all power is disconnected before performing any wiring or maintenance.
- Només personal qualificat ha d'instal·lar i mantenir aquest equip.
- La connexió a terra adequada és essencial per evitar descàrregues elèctriques.
- The frequency converter must be directly connected to the motor. Control of motor start and stop must be managed by the frequency converter to prevent damage.
Condicions ambientals:
- Avoid installation in environments with excessive humidity, water mist, water droplets, or where metal objects could fall into the unit, as this may cause short circuits.
- Ensure adequate ventilation around the VFD for proper heat dissipation.
Nota important: This VFD does not support external resistors. For heavy load motors, consider a higher power level VFD or consult technical support for model selection.
3. Producte acabatview
3.1. Aparença física

3.2. Dimensions

3.3. Control Panel Layout

3.4. Removable Keyboard

4. Instal·lació
4.1. Muntatge
Mount the VFD in a vertical position on a flat, stable surface. Ensure sufficient clearance around the unit for proper airflow and heat dissipation. Avoid mounting in direct sunlight or near heat sources.
4.2. Instruccions de cablejat
Refer to the wiring diagram and the video for correct connections. Ensure all connections are secure and properly insulated.

- Potència d'entrada (R, S, T): For single-phase 220V input, connect to any two of the R, S, T terminals. For three-phase 220V input, connect to R, S, T terminals.
- Sortida del motor (U, V, W): Connect the three-phase motor wires to the U, V, W terminals.
- Posada a terra: Connect the ground wire to the designated grounding terminal.
- Terminals de control: The VFD supports various control terminals for external switches, potentiometers, and RS485 communication. Refer to the detailed terminal block for specific connections.
4.3. Comunicació RS485
For RS485 communication, connect RS485+ and RS485- to the corresponding terminals. If the control device requires a power supply, connect GND and 24V terminals.
Video 1: MOLLOM VFD G75 and G70 Introduction and Setup Process. This video demonstrates the physical installation, wiring connections for input power and motor, and initial parameter settings for the VFD. It provides a visual guide for connecting the VFD to a motor and configuring basic operational parameters.
5. Funcionament
5.1. Controls bàsics
- PRG (Programming/Return): Entra o surt del mode de programació.
- ENTRAR: Confirma la configuració dels paràmetres.
- Fletxes AMUNT/AVALL: Navigates through parameters and adjusts values.
- MAJÚS: Moves the cursor during parameter editing.
- CORRER: Engega el motor.
- STOP/RST: Stops the motor or resets errors.
- MF.K (Function/Jog): Multi-function key, often used for jogging or specific functions.
- Potenciòmetre: Adjusts output frequency/speed in real-time.
5.2. Configuració de paràmetres
The VFD requires specific parameter settings to match your motor's characteristics. The following are examples for a 380V motor. Always set parameters according to your motor's nameplate data.
General Steps for Parameter Setting:
- Premeu el botó PRG button to enter programming mode (Display F0.00).
- Ús Amunt/Avall arrows to navigate to the desired parameter group (e.g., F1-xx).
- Premeu ENTRAR to select the parameter group.
- Ús Amunt/Avall arrows to select the specific parameter (e.g., F1-01).
- Premeu ENTRAR a view el valor actual.
- Ús Amunt/Avall fletxes i MAJÚS per ajustar el valor.
- Premeu ENTRAR per guardar el nou valor.
- Premeu PRG per sortir del mode de programació.
Example Parameter Settings (Refer to Video 1 for demonstration):
- F1-01 (Motor Power): Set according to your motor's power (e.g., 2.2 for 2.2KW).
- F1-02 (Motor Voltage): Set according to your motor's rated voltage (e.g., 380 for 380V).
- F1-03 (Motor Current): Set according to your motor's rated current (e.g., 7 for 7A).
- F1-04 (Motor Frequency): Set according to your motor's rated frequency (e.g., 60 for 60Hz).
- F1-05 (Motor RPM): Set according to your motor's rated RPM (e.g., 3450 for 3450 RPM).
6. Especificacions
| Especificació | Valor |
|---|---|
| Poder | 0.75 kW (1 CV) |
| Entrada Voltage | 220 V CA (± 15%) |
| Vol. De sortidatage | 220 V CA |
| Freqüència d'entrada | 50/60 Hz |
| Freqüència de sortida | 0-3000 Hz |
| Fase d’entrada | Single or Three Phase |
| Fase de sortida | Trifàsica |
| Corrent nominal | 3.8A |
| Dimensions (L x A x A) | 3.5 x 4.5 x 6.5 polzades (90 mm x 115 mm x 165 mm) |
| Pes de l'article | 2.49 lliures |
| Material | Acrilonitril butadiè estirè (ABS) |
| Tipus de visualització | Digital |
| Port de comunicació | RS485 (MODBUS) |
7. Manteniment
Un manteniment regular garanteix la longevitat i el rendiment òptim del vostre variador de freqüència.
- Neteja: Keep the VFD clean and free from dust and debris. Use a soft, dry cloth for cleaning. Do not use liquid cleaners.
- Ventilació: Ensure that the cooling fan and ventilation openings are not obstructed. Periodically check for dust buildup in the fan and heatsink.
- Connexions: Periodically check all wiring connections for tightness and signs of wear or corrosion. Loose connections can lead to overheating or malfunction.
- Medi ambient: Maintain the operating environment within specified temperature and humidity ranges. Avoid exposure to corrosive gases or liquids.
8. Solució De Problemes
This section provides solutions to common issues. For complex problems, contact technical support.
- El motor no arrenca:
- Comproveu la font d'alimentació d'entrada.
- Verify motor wiring (U, V, W) is correct and secure.
- Ensure VFD parameters (F1-01 to F1-05) match motor nameplate data.
- Check if the RUN command is active (e.g., pressing the RUN button or external control signal).
- Motor Running at Incorrect Speed:
- Check the frequency setting (potentiometer or digital input).
- Verify F1-04 (Motor Frequency) is set correctly.
- Ensure the control mode (e.g., V/F control, vector control) is appropriate for the application.
- VFD Displays Error Code:
- Refer to the VFD's specific error code list (not provided in this manual, but typically found in the full product manual).
- Common errors include overcurrent, overvoltage, minvartage, and overload. Address the underlying cause (e.g., motor overload, unstable power supply).
- VFD Overheating:
- Check for proper ventilation and clear any obstructions around the VFD.
- Assegureu-vos que la temperatura ambient estigui dins dels límits de funcionament.
- Verify the motor load is not exceeding the VFD's capacity.
- Problemes de comunicació (RS485):
- Check RS485+ and RS485- wiring for correct polarity and secure connections.
- Verify communication parameters (baud rate, parity, data bits) are correctly set on both the VFD and the control device.
- Ensure proper termination resistors are used if necessary.
9. Suport tècnic
If you encounter difficulties with parameter settings or require assistance with your motor, please contact MOLLOM technical support. Provide specific motor parameters or a photo of your motor's nameplate for accurate guidance.