RWRAPS REX-C100
RWRAPS REX-C100 Digital PID Temperature Controller User Manual
Model: REX-C100
Introducció
This manual provides comprehensive instructions for the installation, operation, and maintenance of your RWRAPS REX-C100 Digital PID Temperature Controller. This device is designed for precise temperature control in various industrial and laboratory applications, featuring universal input and a 0-20mA current output.
Característiques clau
- Pantalla dual: Simultaneous display of set temperature (SV) and process temperature (PV) in Celsius or Fahrenheit.
- Entrada universal: Supports 10 types of thermocouples (K, E, S, R, J, T, B, WRe3-WRe25) and RTD inputs (Pt100, Cu50).
- Control PID: Advanced PID control mode with auto-tune function for optimal parameter setting.
- Sortida actual: 0-20mA current output for precise control.
- Disseny compacte: 1/16 DIN size (48mm x 48mm x 110mm) for space-efficient installation.
- Aplicació àmplia: Suitable for kilns, furnaces, ovens, incubators, and various industrial temperature control systems.
Especificacions tècniques
| Tipus d'entrada | TC: K, E, S, R, J, T, B, WRe3-WRe25; RTD: Pt100, Cu50 |
| Interval d'entrada | K (-200~+1300°C), S (-50~+1600°C), R (-50~+1600°C), T (-200~400°C), E (-200~900°C), J (-200~1200°C), B (350~1800°C), Pt100 (-99.9~600.0°C or -200~+600°C), Cu50 (-50~150°C) |
| Mostra | Dual line, Four digits, °C/°F selectable |
| Resolució de visualització | 1°C, 1°F, or 0.1°C, 0.1°F (with Pt100) |
| Precisió | ±0.5% or ±1 unit of full input range |
| Mode de control | PID, On-Off |
| Mode de sortida | Current: 0-20mA (Non-linear output: 0mA when PV is close to SV, 20mA when PV varies significantly) |
| Alarma | Upper-limit bias alarm |
| Font d'alimentació | 85~260VAC / 50~60Hz |
| Consum d'energia | <2 watts |
| Dimensions | 48mm x 48mm x 110mm (1/16 DIN) |
| Pes de l'article | 10.6 unces |
Configuració i instal·lació
1. S'ha acabat el panell frontalview

The front panel (Figure 1) provides the primary interface for monitoring and adjusting the controller's settings. The upper display (PV) shows the current measured temperature, while the lower display (SV) shows the target temperature. The buttons allow for navigation through menus and parameter adjustments.
2. Wiring Terminals

Figure 2 illustrates the rear wiring terminals. Ensure all connections are made securely to prevent operational issues. Refer to the wiring diagram for correct terminal assignments.
3. Esquema de cablejat

The wiring diagram (Figure 3) is crucial for proper installation. Follow these guidelines:
- Font d'alimentació (terminals 1 i 2): Connect your 100-240VAC, 50/60Hz power source here.
- Current Output (Terminals 3 & 4): Connect your control device requiring 0-20mA input. Terminal 3 is positive (+), Terminal 4 is negative (-).
- Sortida d'alarma (terminals 6 i 7): Connect your alarm indicator or relay here.
- Entrada de sensor (terminals 8, 9, 10):
- For RTD (e.g., Pt100): Connect to terminals 8, 9, and 10.
- For Thermocouple (TC): Connect to terminals 9 and 10. Ensure correct polarity.
Important: Always ensure power is disconnected before performing any wiring to prevent electric shock.
Instruccions de funcionament
1. Power On and Initial Display
Upon powering on, the controller will display the current process value (PV) on the upper red display and the set value (SV) on the lower green display. Ensure the sensor is correctly connected and functioning.
2. Setting the Target Temperature (SV)
- Premeu el botó SET el botó una vegada. La pantalla SV començarà a parpellejar.
- Utilitza el Up (▲) i Avall (▼) botons de fletxa per ajustar la temperatura objectiu.
- Utilitza el Esquerra/Dreta (◀ / ▶) arrow buttons to move the cursor for faster adjustment of individual digits.
- Premeu el botó SET de nou per confirmar el nou SV i sortir del mode de configuració.
3. Auto-Tune Function (AT)
The auto-tune function automatically calculates optimal PID parameters for your specific system, ensuring stable and accurate temperature control.
- Set your desired target temperature (SV) as described above.
- Manteniu premut el botó SET button for approximately 3-5 seconds until the 'AT' indicator light begins to flash.
- The controller will now cycle through heating and cooling to determine the system's characteristics. This process may take some time depending on your system's thermal mass.
- Once auto-tuning is complete, the 'AT' indicator light will stop flashing and remain off. The controller will then operate with the newly calculated PID parameters.
Nota: It is recommended to perform auto-tuning whenever the system's thermal characteristics change significantly (e.g., new heater, different load).
4. Advanced Parameter Settings
For advanced users, the controller offers individually programmable control parameters (P, I, D, control period, digital filter coefficient, etc.). Accessing and adjusting these parameters typically involves pressing and holding the SET button for an extended period (e.g., 5-10 seconds) to enter the parameter menu. Refer to the detailed parameter list in the full technical manual for specific codes and ranges. Incorrect settings can lead to unstable control.
Manteniment
- Neteja: Keep the controller's front panel clean using a soft, dry cloth. Avoid abrasive cleaners or solvents.
- Condicions ambientals: Ensure the operating environment is within the specified temperature and humidity ranges to prolong the life of the device.
- Inspecció del cablejat: Comproveu periòdicament totes les connexions del cablejat per comprovar si estan ben ajustades i si hi ha signes de desgast o corrosió.
Resolució de problemes
| Problema | Causa possible | Solució |
|---|---|---|
| Sense pantalla/Apagat | Sense subministrament d'alimentació; cablejat incorrecte | Check power connections (Terminals 1 & 2); Verify power source is active. |
| La pantalla PV mostra "HHHH" o "LLLL" | Sensor open circuit; Sensor short circuit; Incorrect sensor type selected; Sensor out of range | Check sensor wiring; Replace faulty sensor; Verify sensor type setting matches installed sensor; Ensure temperature is within sensor's measurable range. |
| Temperature unstable/Overshoot/Undershoot | PID parameters not optimized; Incorrect control mode | Perform Auto-Tune (AT function); Ensure PID control mode is selected for precise control. |
| La sortida no s'activa | Wiring error; Output device fault; SV not reached | Check output wiring (Terminals 3 & 4); Test external output device; Ensure PV is below SV (for heating) or above SV (for cooling) to trigger output. |
Suport i garantia
For technical assistance or warranty inquiries, please contact your vendor or the manufacturer, RWRAPS. Please have your model number (REX-C100) and purchase details available when contacting support.