Tyenaza ETCR2100A+

Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual

Model: ETCR2100A+

1. Introducció

This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.

Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Tyenaza ETCR2100A+ Digital Clamp Comprovador de resistència

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.

2. Informació de seguretat

Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:

  • Do not use the instrument if it appears damaged or is operating abnormally.
  • Assegureu-vos que el compartiment de la bateria estigui ben tancat abans de fer-lo funcionar.
  • Do not attempt to measure live circuits beyond the specified voltage limits (CAT III 150V).
  • Avoid using the instrument in wet environments or during thunderstorms.
  • Refer to qualified personnel for any repairs or servicing.
  • Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.

3. Contingut del paquet

Verifiqueu que tots els elements siguin presents al paquet:

  • 1 x ETCR2100A+ Digital Clamp Comprovador de resistència
  • 1 x Accessory (likely a test ring or similar calibration aid)
  • 1 x Manual d'usuari (aquest document)
  • 1 x Caixa d'emmagatzematge

Note: 1.5V AA batteries (x4) are required and are not included in the package.

ETCR2100A+ Digital Clamp Resistance Tester with included accessory

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.

4. Característiques del producte

The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:

  • Pantalla multifuncional: Resistance and current values are displayed simultaneously on a new black luxury screen.
  • Alta precisió: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
  • Gestió de dades: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
  • Alarma audible i visual: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
  • Funcions automàtiques: Automatic shutdown and fully automatic gear shifting for ease of use.
  • Disseny robust: Shockproof and dustproof structure, suitable for demanding industrial environments.
  • Aplicació àmplia: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.
Primer pla view del clamp jaws of the ETCR2100A+ tester

Imatge 4.1: Un primer pla view of the robust clamp jaws, highlighting the double insulation and structural features designed for durability and safety.

5. Configuració

5.1 Instal·lació de la bateria

The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).

  1. Locate the battery compartment cover on the back of the instrument.
  2. Use a suitable tool (if necessary) to open the battery compartment.
  3. Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
  4. Tanqueu bé la tapa del compartiment de la bateria.

5.2 Encès inicial

Després de la instal·lació de la bateria, premeu el botó ON/OFF button to power on the device. The LCD display will illuminate, indicating the device is ready for use.

6. Instruccions de funcionament

6.1 Mesura bàsica

To perform a grounding resistance test:

  1. Assegureu-vos que l'instrument està encès.
  2. Obriu el clamp mandíbules prement el gallet.
  3. Col·loqueu el clamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
  4. The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
  5. The single measurement time is approximately 0.5 seconds.
ETCR2100A+ tester clamping an insulated ground wire

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.

6.2 Single Point Grounding System, Auxiliary Measurement

For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Diagram illustrating the two-point auxiliary measurement method for single point grounding systems

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.

Per utilitzar aquest mètode:

  • Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
  • Connect a wire from the point to be measured to this auxiliary grounding point.
  • Clamp the ETCR2100A+ around the connecting wire to perform the measurement.
ETCR2100A+ Digital Clamp Resistance Tester in an industrial substation environment

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.

6.3 Emmagatzematge i recuperació de dades

The instrument can store up to 99 sets of measurement data.

  • To store data: After a measurement, press the MEM button to save the current reading.
  • To retrieve data: Press the MEM button repeatedly to cycle through stored data.

6.4 Funció d'alarma

The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.

  • To activate/deactivate the alarm: Press the AL botó.
  • To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.
Hand holding the ETCR2100A+ Digital Clamp Comprovador de resistència

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.

7. Manteniment

7.1 Neteja

Wipe the instrument's exterior with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.

7.2 Emmagatzematge

When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.

7.3 Calibració

Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.

8. Solució De Problemes

ProblemaCausa possibleSolució
El dispositiu no s'encén.Piles gastades o instal·lades incorrectament.Canvieu les piles per piles AA noves d'1.5 V, assegurant-vos de la polaritat correcta.
Lectures inexactes.Jaws not fully closed; interference from external fields; dirty jaws; need for calibration.Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration.
L'alarma sona contínuament.Measurement exceeds set alarm threshold.Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm.
La pantalla està en blanc o parpelleja.Low battery power; environmental conditions (extreme temperature/humidity).Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH).

9. Especificacions

ModelETCR2100A+
FuncióGrounding resistance test, circuit resistance test, leakage current test
Interval de resistència0.01 Ω a 200 Ω
Resistència Resolució0.001 Ω
Interval actualNone (for leakage current test, the range is 1-499mA for alarm setting)
Emmagatzematge de dades99 conjunts
Alarm Threshold Setting Range (Resistance)1-199 Ω
Alarm Threshold Setting Range (Current)1-499 mA
Temperatura de treball i humitat-20 ℃ to 55 ℃; 10% RH to 90% RH
Pantalla LCD4 digit LCD digital display
Mida de la pantallaApprox. 47 x 28.5mm / 1.85 x 1.12in (L x W)
Jaw Size (Round)Approx. 32mm / 1.26in diameter
Jaw Opening Size (Long)Aprox. 32 mm / 1.26 polzades
Clamp Size (Long Jaw)Aprox. 260 x 90 x 56 mm / 10.24 x 3.54 x 2.2 polzades
Nivell de proteccióDoble aïllament
Característiques estructuralsClamp shaped CT
Canvi de marxaFully automatic shifting
Camp magnètic extern<40A / m
Camp elèctric extern<1 V / m
Single Measurement Time0.5 segons
Resistance Measurement FrequencyGreater than 1KHz
Tested Current Frequency50/60Hz automatic
Font d'alimentació4 piles AA de 1.5 V (no incloses)
MaterialABS
Pes de l'article2.13 quilos / 4.69 lliures

10. Garantia i Suport

Per obtenir informació sobre la garantia, assistència tècnica o consultes sobre el servei, poseu-vos en contacte amb el vostre distribuïdor o directament amb el fabricant. Conserveu el rebut de compra com a comprovant de compra.

Manufacturer: Tyenaza

© 2023 Tyenaza. All rights reserved.