1. Introducció
This manual provides detailed instructions for the installation, operation, and maintenance of your Sinotimer Digital Analogue DIN Module Time Switch. This device is designed for industrial applications, offering precise 24-hour programmable timing with a large LCD display and backlight functionality.
2. Funcions del producte
- Clock display (24-hour format).
- Programmable Timer with up to 96 ON/OFF programs per day.
- Backlight feature: The backlight illuminates when the timer is off and automatically disappears after 5 seconds.
3. Especificacions
| Paràmetre | Valor |
|---|---|
| Números de model | TM929AKL (16A), TM929BKL (30A) |
| Font d'alimentació | 85~265VAC, 50/60Hz |
| Corrent màxim de càrrega de sortida | 16A / 30A (depending on model) |
| Programes | Fins a 96 encesos/apagats per dia |
| Interval de configuració | De 15 minuts a 24 hores |
| Minimum Setting Interval | 15 minuts |
| Mostra | LCD amb llum de fons |
| Dimensions | 86.5 mm x 36 mm x 68.5 mm |
| Instal·lació | Carril DIN de 35 mm |
| Bateria | TM929AKL (16A): Replaceable CR2032; TM929BKL (30A): Non-replaceable internal battery |
| Consum d'energia | <5 VA |
| Black-out (Power Reserve) | 90 dies |
| Certificació | CE |
Nota: The TM929AKL (16A) model features a replaceable CR2032 battery, while the TM929BKL (30A) model has a non-replaceable internal battery. Wiring diagrams differ between models.

4. Configuració
4.1 Instal·lació
The time switch is designed for mounting on a standard 35mm DIN rail. Ensure the mounting location is dry, well-ventilated, and free from excessive vibrations or extreme temperatures.

4.2 Cablejat
ADVERTIMENT: All wiring should be performed by a qualified electrician and in accordance with local electrical codes. Ensure power is disconnected before attempting any wiring.
The timer has terminals for Line (L), Neutral (N), and output contacts (NO, NC, Common). Refer to the diagrams below for typical wiring configurations.


4.3 Engegada inicial
Once wired correctly, apply power to the device. The LCD will illuminate and display the current time. If the display is blank, check the power supply and, for the 16A model, ensure the CR2032 battery is correctly installed.
5. Instruccions de funcionament
The timer features a MENU button, UP/DOWN arrow buttons, an OK button, and a Reset (Res) button.

5.1 Configuració de l'hora actual
- Press the 'MENU' button.
- Use the 'UP' and 'DOWN' arrow buttons to adjust the hour and minute.
- Press 'OK' to confirm each setting.
- Press 'MENU' again to return to the clock display.
5.2 Programació de cicles d'encesa/apagada
El temporitzador admet fins a 96 programes d'encesa/apagada. Cada programa es pot configurar per a dies específics de la setmana.
- Press the 'MENU' button to enter programming mode. The display will show '00:00' or a program number.
- Use 'UP' and 'DOWN' to set the desired ON time (hour and minute). Press 'OK' to confirm.
- Next, set the desired OFF time (hour and minute). Press 'OK' to confirm.
- Use 'UP' and 'DOWN' to select the days of the week for this program (e.g., Mon-Fri, Sat-Sun, or individual days). Press 'OK' to confirm.
- Repetiu els passos 2-4 per a programes addicionals.
- Press 'MENU' to exit programming mode and save settings.
5.3 Anulació manual
To manually switch the timer's output, press the 'OK' button. This will cycle through the modes: ON (always on), AUTO (follows programmed schedule), and OFF (always off).
6. Manteniment
6.1 Battery Replacement (TM929AKL 16A only)
The TM929AKL (16A) model uses a replaceable CR2032 battery. If the display becomes dim or the time settings are lost frequently during power outages, the battery may need replacement. Carefully open the battery compartment and replace the CR2032 battery, ensuring correct polarity. The TM929BKL (30A) model has a non-replaceable internal battery.
6.2 Atenció general
Keep the device clean and dry. Use a soft, dry cloth for cleaning. Avoid using abrasive cleaners or solvents. Ensure the protective cover is closed to prevent dust and moisture ingress.
7. Solució De Problemes
- La pantalla està en blanc: Check the main power supply. For the 16A model, check the CR2032 battery.
- El temporitzador no canvia: Verify wiring connections are secure and correct. Ensure the timer is in 'AUTO' mode. Check that programs are set correctly and not conflicting.
- Hora incorrecta: Reset the timer using the 'Res' button and reprogram the current time.
- Programs not executing: Ensure the timer is in 'AUTO' mode. Check that the ON/OFF times and days are correctly set.
7.1 Restablir el temporitzador
To perform a full reset, press the 'Res' button (usually a small recessed button requiring a pointed object like a pen tip). This will clear all settings and return the timer to its factory default state. You will need to reprogram the current time and all desired ON/OFF cycles.
8. Consells d'usuari
- For precise control, utilize the full capacity of 96 ON/OFF programs to manage complex schedules.
- When setting intervals, remember the minimum programmable interval is 15 minutes.
- Always double-check your wiring before applying power to prevent damage to the unit or connected appliances.
9. Garantia i Suport
For technical assistance, warranty claims, or further information, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.