ANENG MH14

Manual d'usuari del megòhmetre digital ANENG MH14 i del mesurador de resistència d'aïllament

Model: MH14 | Brand: ANENG

1. Acabatview

The ANENG MH14 Digital Megohmmeter is a professional instrument designed for testing the grounding resistance of electrical equipment. It features improved circuit, structure, and process compared to traditional grounding resistance testers, offering a beautiful and practical design, comprehensive functions, higher accuracy, and convenient, reliable operation. Its dust-proof and moisture-proof structure makes it suitable for field use. This device can be used to measure grounding resistance values for various power systems, power equipment, lightning protection equipment, and other grounding systems, as well as AC voltage.

ANENG MH14 Digital Megohmmeter, highlighting its high precision range of 0.01Ω to 2000Ω.
ANENG MH14 Digital Megohmmeter, highlighting its high precision range of 0.01Ω to 2000Ω.

2. Precaucions de seguretat

This instrument is designed in accordance with IEC1010 Safety Standards. Please read the following precautions carefully before use:

  1. Do not use the grounding resistance meter or measuring line if its appearance is damaged.
  2. Avoid touching live conductors (DC60V, AC36V RMS or higher) to prevent electric shock.
  3. Before measuring resistance, ensure the circuit is completely isolated from the power supply for accurate readings and personal safety.
  4. Do not store the meter in high temperatures or direct sunlight to protect the liquid crystal display.
  5. Si el símbol de la bateria ([BATTERY ICON]) is displayed, replace the batteries immediately. Remove batteries during long-term storage to prevent damage from battery fluid leakage.
  6. Exercise extreme caution when measuring bare wires.
  7. When powered by an external adapter, the internal battery is disconnected and cannot be charged. Ensure the power supply mode is selected correctly.

Grounding Resistance Test Requirements:

  • AC working grounding: Resistance should not exceed 4Ω.
  • Safe working grounding: Resistance should not be greater than 4Ω.
  • DC working grounding: Resistance should be determined by specific computer system requirements.
  • Lightning protection ground: Resistance should not exceed 10Ω.
  • Jointed grounding of shielded systems: Resistance should not exceed 1Ω.

3. Unpacking Inspection & Package Contents

Carefully unpack the product and verify that all items listed below are present and in good condition. If any items are missing or damaged, please contact your dealer.

Contingut del paquet:

  1. 1 x Ground Resistance Meter (ANENG MH14)
  2. 1 x Canvas Bag
  3. 2 x Grounded Steel Brazing (Ground Studs)
  4. 1 Set of Auxiliary Test Lines (Red 15m, Yellow 10m, Green 5m)
  5. 1 Set of Simple Test Lines (Red 1.6m, Green 1.6m)
  6. 1 x manual d'instruccions
  7. 1 x Product Certificate
ANENG MH14 Digital Megohmmeter shown with included accessories: test leads (red, green, yellow), ground studs, and a storage bag.
ANENG MH14 Digital Megohmmeter shown with included accessories: test leads (red, green, yellow), ground studs, and a storage bag.
Image showing the ANENG MH14 with all accessories: Meter (MH14), Simple Red line (1.6m), Simple Green line (1.6m), Red line (15m), Green line (10m), Yellow line (5m), Manual, Ground drill * 2, Storage bag, Packing box.
Image showing the ANENG MH14 with all accessories: Meter (MH14), Simple Red line (1.6m), Simple Green line (1.6m), Red line (15m), Green line (10m), Yellow line (5m), Manual, Ground drill * 2, Storage bag, Packing box.

4. Especificacions

Característiques generals:

  • Visualització: 90mm × 48mm LCD display, maximum display "1999".
  • Indicació d'excés de rang: Only the highest digit displays "1" when the upper limit is exceeded.
  • Font d'alimentació: 8 x AA alkaline batteries (LR6 1.5V) (optional external power adapter option). Under-voltage indication when insufficient voltage.
  • Consum d'energia: <=800mW when testing no load.
  • Temperatura de funcionament: 0°C - 40°C, Relative Humidity: 30%-85% RH.
  • Dimensions: 175 (L) × 110 (W) × 70 (D) mm.
  • Pes: Approximately 750g (including battery).
  • Disseny: Streamline design with anti-earthquake requirements.

Mesura de la resistència a la presa de terra:

IntervalPrecisió bàsicaResolució
20 Ω± (2% + 0.1Ω)0.01 Ω
200 Ω± (2% + 3 d)0.1 Ω
2000 Ω± (2% + 3 d)1 Ω

Terra Voltage Measurement (50Hz~200Hz):

IntervalPrecisió bàsicaResolucióImpedància d'entradaProtecció de sobrecàrrega
200 V CA± (2% + 6 d)0.1 V1 MΩ200Vrms
Table of technical specifications including grounding resistance ranges (20Ω, 200Ω, 2000Ω) with basic accuracy and resolution, AC voltage range (AC200V) with accuracy, input resistance, and overload protection. Also includes physical dimensions (170mm x 125mm x 62mm) and weight (550g).
Table of technical specifications including grounding resistance ranges and AC voltage, along with physical dimensions and weight.

5. Operation Panel Instructions

Familiarize yourself with the controls and display of the ANENG MH14:

Detailed diagram of the ANENG MH14 panel with numbered labels for each component.
Detailed diagram of the ANENG MH14 panel with numbered labels for each component.
  1. Power Adapter Jack: For connecting an optional external power adapter.
  2. Model Face Card: Mostra la informació del model.
  3. LCD Display Window: Mostra lectures de mesurament i indicadors.
  4. Test Work Instructions Light: Illuminates when wiring is correctly connected during a test.
  5. Test Button with Lock: Initiates a test. Can be locked for continuous measurement.
  6. Self-locking Power Switch (POWER): Encén/apaga el dispositiu.
  7. Digital Hold Switch (HOLD): Congela la lectura actual a la pantalla.
  8. Voltage Test Selection Switch: Selecciona el voltage mode de mesura.
  9. 2000Ω Range Resistance Selection Switch: Selects the 2000 Ohm range.
  10. 200Ω Range Resistance Selection Switch: Selects the 200 Ohm range.
  11. 20Ω Range Resistance Selection Switch: Selects the 20 Ohm range.
  12. ACV Port: Voltage pole input.
  13. E Port: Grounding pole input.
  14. Port C: Current pole input.
  15. P Port: Potential pole input.
  16. Input Jack Face Card Instructions: Provides guidance for input connections.

6. Configuració

Instal·lació de la bateria:

The ANENG MH14 requires eight AA batteries (LR6 1.5V) for operation. Follow these steps to install them:

  1. Localitzeu el compartiment de la bateria a la part posterior del dispositiu.
  2. Feu servir un tornavís per obrir la tapa del compartiment de la bateria.
  3. Insert eight AA batteries, ensuring correct polarity (+/-).
  4. Substituïu la tapa del compartiment de la bateria i fixeu-la amb el cargol.

If the battery symbol appears on the display, replace the batteries. For long-term storage, remove the batteries to prevent leakage.

Video: Demonstration of ANENG MH14 Digital Megohmmeter features, unboxing, battery installation, and measurement procedures for grounding resistance and ground voltage.

7. Instruccions de funcionament

7.1. Bateria Voltage Comproveu:

After powering on the device, if the battery symbol is not displayed, the current power is sufficient. If the display flashes or the logo appears, please replace the battery.

7.2. Test Line Connection:

Ensure all test lead plugs are fully inserted into the test ends before measuring. Loose connections can lead to inaccurate measurement results.

7.3. Conventional Grounding Resistance Measurement:

DANGER: When measuring grounding resistance, a maximum of 50V AC voltage may be generated between the E-C or E-P terminals. Do not touch the test leads to avoid electric shock.

  1. Test Wire Connection:
    Connect the auxiliary grounding rods P and C to the ground at a distance of 5 to 10 meters from the grounding object to be measured. Connect the green wire to the instrument's E terminal, the yellow wire to the P terminal, and the red wire to the C terminal.
  2. Preparació del sòl:
    Insert the auxiliary grounding rods into land with high water content. In dry land, depressions, or gravel, add water to keep the grounding hole moist. If concrete is encountered, lay the grounding rod flat, add water, and cover it with a wet towel before measuring.
  3. Procediment de mesura:
    Start with the 2000 Ω range and press the "PRESS TEST" button. The backlight will illuminate. If the displayed value is too small, switch to the 200 Ω or 20 Ω range in order. The displayed value is the measured ground resistance. After testing, turn off the power switch to save power.
Diagram for conventional grounding resistance test setup with floor nails and wiring distances (10m and 15m) for C and P electrodes.
Diagram for conventional grounding resistance test setup with floor nails and wiring distances (10m and 15m) for C and P electrodes.
Diagram illustrating the working principle of the grounding resistance measurement using four electrodes (E1, P1, P2, E2) inserted into the ground.
Diagram illustrating the working principle of the grounding resistance measurement using four electrodes (E1, P1, P2, E2) inserted into the ground.
Video: Demonstration of ANENG MH14 Digital Megohmmeter features, unboxing, battery installation, and measurement procedures for grounding resistance and ground voltage.

7.4. Ground Voltage Mesura:

  1. Adjust the range selector switch to "EARTH VOLTAGE".
  2. If the display shows a voltage value, it indicates the presence of grounding voltage en el sistema.
  3. Confirmeu que el voltage value is below 10V. If it's above 10V, the grounding resistance measurement may be inaccurate. In such cases, power off the grounding device and lower the grounding voltage abans de la mesura.
Diagram illustrating ground voltage measurement setup, showing the meter connected to a grounding body and a ground nail at a distance of 5m and 10m respectively.
Diagram illustrating ground voltage measurement setup, showing the meter connected to a grounding body and a ground nail at a distance of 5m and 10m respectively.
Video: Demonstration of ANENG MH14 Digital Megohmmeter features, unboxing, battery installation, and measurement procedures for grounding resistance and ground voltage.

7.5. Simple Grounding Resistance Measurement:

This method is convenient when auxiliary ground rods cannot be used. It involves using a ground electrode with small impedance (e.g., metal water pipe, commercial power system grounding terminal, or building grounding terminal) instead of auxiliary grounding straps C and P.

  1. Test Wire Connection:
    Connect the green wire to the instrument's E terminal and clamp it to the grounding body (e.g., electrical box ground terminal). Connect the red wire to the instrument's C terminal and clamp it to a suitable low-impedance ground electrode (e.g., fire hose, ensuring paint is removed for good contact).
  2. Procediment de mesura:
    After connecting the lines, press the "PRESS TEST" button. The backlight will illuminate. If the displayed value is too small, switch to the 200 Ω or 20 Ω range. The displayed value is the measured ground resistance.
Diagram illustrating the simple ground resistance test method using the MH14, connecting to a metal pipe (re) and a grounding body (Rx).
Diagram illustrating the simple ground resistance test method using the MH14, connecting to a metal pipe (re) and a grounding body (Rx).
Video: Demonstration of ANENG MH14 Digital Megohmmeter features, unboxing, battery installation, and measurement procedures for grounding resistance and ground voltage.

8. Consells d'usuari

  • For accurate grounding resistance measurements, especially in dry conditions, moisten the soil around the ground rods.
  • Always ensure good contact between the alligator clips and the test points by removing any paint or corrosion.
  • When using the simple test method, ensure the chosen ground electrode has genuinely low impedance for reliable results.
  • The "HOLD" function is useful for recording stable readings in challenging environments.

9. Manteniment

  • Neteja: Wipe the instrument with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Emmagatzematge: Store the device in a cool, dry place, away from direct sunlight and extreme temperatures. Remove batteries if storing for extended periods.
  • Protecció: The device features a silicone sheath/ABS material for drop protection. While durable, avoid unnecessary impacts.
Image highlighting the drop guard insulation material of the ANENG MH14, designed to protect hardware from damage.
The ANENG MH14 features a drop guard insulation material to protect hardware from damage.
Close-up of an insulated alligator clip connected to a reinforced floor nail, emphasizing safety and durability.
Insulated alligator clips and reinforced floor nails ensure safer and more reliable connections.

10. Solució De Problemes

If your meter is not working properly, the following methods can help resolve common problems. If the issue persists, contact your service center or dealer.

Fenomen de fracàsInspection Site and Method
Display not shownBattery not connected / Replace the battery
Battery symbol appearsSubstituïu la bateria
Error de pantalla granSubstituïu la bateria

Nota: The measuring current is about 2mA. Even if an earth leakage circuit breaker is connected, the circuit breaker will not be operated.

The true grounding resistance value RX shall be calculated by the following formula:

RX = RE - re

  • RE: Grounding resistance of common ground terminal (e.g., commercial power system)
  • re: Instrument grounding resistance reading

11. Garantia i assistència

This manual is subject to change without notice. The contents are considered correct at the time of publication. If you find any errors or omissions, please contact the manufacturer.

The company is not responsible for accidents or hazards caused by incorrect user operation. The functions described in this manual are not intended for special purposes beyond their stated use.

ANENG's professional after-sales team is available to assist you with any questions or issues during the use of the product. For specific product damage or operational problems, please contact ANENG customer service for timely solutions and assistance.

Information on ANENG's professional after-sales team, covering contact for questions, quality issues, replacement/refund requests, product not operating properly, questions about product use, artificially damaged products, and coupons for positive reviews.
ANENG's professional after-sales team provides support for product inquiries and issues.

ANENG MH14 Digital Earth Tester: Grounding Resistance & Voltage Measurement Guide

ANENG MH14 Digital Earth Tester: Grounding Resistance & Voltage Measurement Guide

2:36 • 1280×720 • instruccions
ANENG MH14 Digital Earth Tester: Grounding Resistance & Voltage Measurement Guide

ANENG MH14 Digital Earth Tester: Grounding Resistance & Voltage Measurement Guide

2:36 • 1280×720 • instruccions
ANENG MH14 Digital Earth Tester: Grounding Resistance and Voltage Measurement Guide

ANENG MH14 Digital Earth Tester: Grounding Resistance and Voltage Measurement Guide

2:36 • 1280×720 • instruccions

Documents relacionats - MH14

Preview ANENG MH14 Digital Grounding Multimeter: Instruction Manual & Technical Guide
This manual provides comprehensive instructions for the ANENG MH14 Digital Grounding Multimeter, covering its features, operation, safety precautions, technical specifications, and troubleshooting for accurate grounding resistance testing.
Preview Manual d'usuari del provador de resistència d'aïllament ANENG MH12
Manual d'usuari complet per al provador de resistència d'aïllament ANENG MH12, que detalla les especificacions, les precaucions de seguretat, les instruccions d'ús i els procediments de mesura per a les proves de resistència d'aïllament.
Preview ANENG MH15 高精度绝缘电阻测试仪使用说明书
ANENG MH15是一款高精度绝缘电阻测试仪,提供多种测量功能,包括直流/交流电压、电阻、通断、二极管和绝缘电阻。本手册详细介绍了仪器的操作、安全信息和技术规格。
Preview ANENG 1000V/2500V/5000V Series Insulation Resistance Tester User Manual
Comprehensive user manual for the ANENG 1000V, 2500V, and 5000V series Insulation Resistance Testers, covering safety, operation, technical specifications, and measurement procedures for electrical equipment.
Preview ANENG ST180 Cl digitalamp Manual d'usuari del comptador
Manual d'usuari que proporciona informació detallada, especificacions i instruccions de funcionament per a l'ANENG ST180 Digital Cl.amp Metre.
Preview ANENG MH10 Digital Insulation Resistance Tester - Operating Instructions and Safety Guide
Comprehensive operating instructions, safety specifications, technical parameters, and troubleshooting for the ANENG MH10 Digital Insulation Resistance Tester. Learn how to safely and effectively use this high-voltage electrical equipment test instrument.