NM-ECO-LV-3.6KW Plus NM-ECO-LV-3.6KW Plus

Hybrid Solar Inverter 3600W User Manual

Model: NM-ECO-LV-3.6KW Plus

1. Introducció

1.1 Finalitat

This manual describes the assembly, installation, operation, and troubleshooting of the Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Àmbit

This manual provides safety and installation guidelines as well as information on tools and wiring for the Hybrid Solar Inverter. This is a multi-function inverter/charger, combining functions of an inverter, solar charger, and battery charger to offer uninterruptible power support with a portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage basat en diferents aplicacions.

1.3 Característiques

Davant view of the 3600W Hybrid Solar Inverter, highlighting key specifications like 120A Max MPPT Solar Charging, 80A Max AC Charging, 500V Max PV Input Voltage, and 24V to 110/120V output.
Davant view of the 3600W Hybrid Solar Inverter, highlighting key specifications like 120A Max MPPT Solar Charging, 80A Max AC Charging, 500V Max PV Input Voltage, and 24V to 110/120V output.
Image highlighting key features of the inverter, including pure sine wave output, WiFi, no battery operation, one-key factory reset, lithium battery activation, anti-dust kit, smart charging, and dual output.
Key features of the Hybrid Solar Inverter.
Image showing the pure sine wave output waveform on an oscilloscope, emphasizing high quality AC power.
Pure Sine Wave Output for high quality AC power.

2. Instruccions de seguretat

ADVERTÈNCIA: aquest capítol conté instruccions importants de seguretat i funcionament. Llegiu i guardeu aquest manual com a referència futura.

  1. Abans d'utilitzar la unitat, llegiu totes les instruccions i les marques d'advertència de la unitat, les bateries i totes les seccions adequades d'aquest manual.
  2. PRECAUCIÓ --Per reduir el risc de lesions, carregueu només bateries recarregables de plom-àcid de cicle profund. Altres tipus de bateries poden explotar i causar lesions personals i danys.
  3. No desmunteu la unitat. Porteu-lo a un centre de servei qualificat quan calgui reparació o reparació. El muntatge incorrecte pot provocar un risc de descàrrega elèctrica o incendi.
  4. Per reduir el risc de descàrrega elèctrica, desconnecteu tots els cables abans d'intentar qualsevol manteniment o neteja. Apagar la unitat no reduirà aquest risc.
  5. PRECAUCIÓ – Només personal qualificat pot instal·lar aquest dispositiu amb bateria.
  6. MAI carregueu una bateria congelada.
  7. Per a un funcionament òptim d'aquest inversor/carregador, seguiu les especificacions requerides per seleccionar la mida de cable adequada. És molt important fer funcionar correctament aquest inversor/carregador.
  8. Tingueu molta precaució quan treballeu amb eines metàl·liques sobre o al voltant de les bateries. Existeix un risc potencial de deixar caure una eina per provocar espurnes o curtcircuit a bateries o altres peces elèctriques i podria provocar una explosió.
  9. Si us plau, seguiu estrictament el procediment d'instal·lació quan vulgueu desconnectar els terminals de CA o CC. Consulteu la secció INSTAL·LACIÓ d'aquest manual per obtenir els detalls.
  10. Es proporciona una peça de fusible de 150 A com a protecció contra sobreintensitat per al subministrament de la bateria.
  11. INSTRUCCIONS DE TERRA -Aquest inversor/carregador s'ha de connectar a un sistema de cablejat permanent posat a terra. Assegureu-vos de complir els requisits i la normativa local per instal·lar aquest inversor.
  12. MAI provocar un curtcircuit a la sortida de CA i a l'entrada de CC. NO connecteu a la xarxa elèctrica quan l'entrada de CC es produeixi un curtcircuit.
  13. Avís!! Només les persones de servei qualificades poden donar servei a aquest dispositiu. Si els errors persisteixen després de seguir la taula de resolució de problemes, si us plau, envieu aquest inversor/carregador al distribuïdor local o al centre de servei per al manteniment.

3. Configuració i instal·lació

3.1 Desembalatge i inspecció

Abans de la instal·lació, inspeccioneu la unitat. Assegureu-vos que no hi hagi cap dany dins del paquet. Hauríeu d'haver rebut els articles següents dins del paquet:

Davant view of the inverter unit, labeled 'Only Inverter'.
The inverter unit.

3.2 Preparació

Before connecting all wirings, please take off the bottom cover by removing two screws.

3.3 Muntatge de la unitat

Tingueu en compte els punts següents abans de seleccionar on instal·lar-lo:

ADVERTÈNCIA: APTE NOMÉS PER A MUNTATGE SOBRE FORMIGÓ O ALTRA SUPERFÍCIE NO COMBUSTIBLE.

Install the unit by screwing two screws. It's recommended to use M6 screws.

3.4 Arquitectura bàsica del sistema

The following illustration shows a basic application for this inverter/charger. It includes connections to a generator or utility, PV modules, and external battery packs to power home appliances.

Diagram illustrating a Hybrid Power System setup, showing connections between solar power, generator, utility, external battery packs, the solar inverter, and various home appliances.
Hybrid Power System Diagram.
Detailed system architecture diagram showing solar modules, generator, utility grid, battery packs, and home appliances connected to the inverter.
Detailed Hybrid Power System Architecture.
Illustrative diagram of a house with solar panels and the inverter integrated into a hybrid power system, showing connections to battery, AC output, and home appliances.
Inverter integrated into a home solar system.

3.5 Connexió de la bateria

PRECAUCIÓ: Per a la seguretat del funcionament i el compliment de la normativa, es requereix instal·lar un protector de sobrecorrent de CC o un dispositiu de desconnexió separat entre la bateria i l'inversor. Pot ser que no es requereixi tenir un dispositiu de desconnexió en algunes aplicacions, però, tot i així, es requereix tenir instal·lada una protecció contra sobrecorrent. Consulteu les instruccions típiques. ampRegistreu-vos a la taula següent segons la mida del fusible o interruptor necessari.

ADVERTIMENT! Tot el cablejat ha de ser realitzat per personal qualificat.

ADVERTIMENT! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Mida recomanada del cable de la bateria:

ModelMida del cableCable (mm²)Valor de parell (màx.)
3.6 kW/6.2 kW1 x 2 AWG252 Nm

Si us plau, seguiu els passos següents per implementar la connexió de la bateria:

  1. Traieu la funda d'aïllament de 18 mm per als conductors positius i negatius.
  2. Suggeriu que col·loqueu virolles de cordó a l'extrem dels cables positius i negatius amb una eina de crimpada adequada.
  3. Connect all battery packs as shown in the diagram (refer to PDF page 7 for detailed diagram).
  4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with a torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

ADVERTÈNCIA: Perill de descàrrega elèctrica. La instal·lació s'ha de dur a terme amb cura a causa de l'alt volum de la bateria.tage en sèrie.

PRECAUCIÓ!! Abans de fer la connexió de CC final o tancar l'interruptor/desconnectador de CC, assegureu-vos que el positiu (+) estigui connectat al positiu (+) i el negatiu (-) estigui connectat al negatiu (-).

3.6 Connexió d'entrada/sortida de CA

ATENCIÓ!! Abans de connectar-vos a la font d'alimentació d'entrada de CA, instal·leu un interruptor de CA separat entre l'inversor i la font d'alimentació d'entrada de CA. D'aquesta manera, s'assegurarà que l'inversor es pugui desconnectar de manera segura durant el manteniment i totalment protegit de l'excés de corrent d'entrada de CA. L'especificació recomanada del interruptor de CA és de 32 A per a 3.6 kW i 50 A per a 6.2 kW.

ATENCIÓ!! Hi ha dos blocs de terminals amb les marques "IN" i "OUT". Si us plau, NO connecteu malament els connectors d'entrada i sortida.

ADVERTIMENT! Tot el cablejat ha de ser realitzat per personal qualificat.

ADVERTIMENT! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Requisit de cable suggerit per als cables de CA:

ModelCalibreCable (mm²)Valor del parell
3.6KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Si us plau, seguiu els passos següents per implementar la connexió d'entrada/sortida de CA:

  1. Abans de fer la connexió d'entrada/sortida de CA, assegureu-vos d'obrir primer el protector o el seccionador de CC.
  2. Traieu la funda d'aïllament de 10 mm per a sis conductors. I escurçar la fase L i el conductor neutre N 3 mm.
  3. Inseriu els cables d'entrada de CA segons les polaritats indicades al bloc de terminals i estrenyeu els cargols dels terminals. L→LINE (marró o negre), N→Neutre (blau).

ADVERTÈNCIA: Assegureu-vos que la font d'alimentació CA estigui desconnectada abans d'intentar connectar-la a la unitat.

  1. A continuació, inseriu els cables de sortida de CA segons les polaritats indicades al bloc de terminals i estrenyeu els cargols dels terminals. L→LINE (marró o negre), N→Neutre (blau).
  2. Assegureu-vos que els cables estiguin ben connectats.

PRECAUCIÓ: Appliances such as air conditioner are required at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

3.7 Connexió fotovoltaica

PRECAUCIÓ: Abans de connectar-vos als mòduls fotovoltaics, instal·leu per separat un disjuntor DC entre l'inversor i els mòduls fotovoltaics.

ADVERTIMENT! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for PV wires:

ModelMida del cableCable (mm²)Valor de parell (màx.)
3.6 kW/6.2 kW1 x 12 AWG41.2 Nm

Selecció del mòdul fotovoltaic: Quan seleccioneu els mòduls fotovoltaics adequats, assegureu-vos de tenir en compte els paràmetres següents:

  1. Circuit obert Voltage (Voc) dels mòduls fotovoltaics no supera el màxim. Circuit obert de la matriu fotovoltaica voltage d'inversor.
  2. Circuit obert Voltage (Voc) dels mòduls fotovoltaics ha de ser superior al min. bateria voltage.

Connexió del cable del mòdul fotovoltaic:

  1. Traieu la funda d'aïllament de 10 mm per als conductors positius i negatius.
  2. Suggeriu que col·loqueu virolles de cordó a l'extrem dels cables positius i negatius amb una eina de crimpada adequada.
  3. Comproveu la polaritat correcta de la connexió del cable dels mòduls fotovoltaics i els connectors d'entrada fotovoltaica. A continuació, connecteu el pol positiu (+) del cable de connexió al pol positiu (+) del connector d'entrada fotovoltaica. Connecteu el pol negatiu (-) del cable de connexió al pol negatiu (-) del connector d'entrada fotovoltaica. Eina recomanada: tornavís de fulla plana de 4 mm.

3.8 Assemblea final

After connecting all wirings, please put the bottom cover back by screwing two screws.

3.9 Connexió de comunicació

1. Wi-Fi cloud communication (option): Please use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP and install it from the APP store, and refer to the “Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status would be shown by the mobile phone APP or webpàgina de l'ordinador.

Image demonstrating the optional WiFi module for monitoring and control via a mobile phone application (iOS and Android).
WiFi module for monitoring and control.

2. GPRS cloud communication (option): Please use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status would be shown by the mobile phone APP or webpàgina de l'ordinador.

3. Battery communication: The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information.

4. Funcionament

4.1 Encès/apagat

Un cop instal·lada correctament la unitat i connectades les piles, només cal prémer l'interruptor d'encesa/apagada (situat a la part inferior de la carcassa) per encendre la unitat.

4.2 Funcionament i panell de visualització

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Producte detallat a continuacióview showing the LCD display, status indicators, function buttons, power switch, and various input/output ports including AC, Battery, PV, and communication ports.
Producte acabatview: LCD Display, Indicators, and Buttons.

Indicador LED:

Indicador LEDMissatges
INV/AC (Green Solid On)La sortida és alimentada per la utilitat en mode de línia.
INV/AC (Green Flashing)La sortida s'alimenta amb bateria o fotovoltaica en mode bateria.
CHG (Green Solid On)La bateria està completament carregada.
CHG (Green Flashing)La bateria s'està carregant.
FAULT (Red Solid On)S'ha produït un error a l'inversor.
FAULT (Red Flashing)Es produeix una condició d'advertència a l'inversor.

Tecles de funció:

Tecla de funcióDescripció
ESCPer sortir del mode de configuració
UPPer anar a la selecció anterior
ABAIXPer anar a la següent selecció
ENTRARPer confirmar la selecció en el mode de configuració o entrar en el mode de configuració

4.3 Icones de la pantalla LCD

The LCD display provides various icons to indicate the inverter's status and information. These include input source information (AC input, PV input, input voltage/frequency, PV voltage, corrent del carregador, volum de bateriatage), configuration program and fault information (setting programs, warning/fault codes), output information (output voltage/frequency, load percent, load in VA/Watt, discharging current), battery information, load information (overload), mode operation information (unit connected to mains/PV panel, load supplied by utility, utility charger circuit working, DC/AC inverter circuit working), and mute operation (alarm disabled).

4.4 Configuració LCD

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit. Refer to PDF pages 14-20 for detailed LCD setting programs and options.

4.5 Configuració de la pantalla

The LCD display information will be switched in turns by pressing the "UP" or "DOWN" key. The selectable information includes input voltage, freqüència d'entrada, PV voltage, corrent de càrrega, potència de càrrega, volum de bateriatage, voltage, freqüència de sortida, percentatge de càrregatage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version. Refer to PDF pages 21-26 for detailed display settings and examples.

4.6 Descripció del mode de funcionament

The inverter supports various operating modes including Standby mode, Line mode, Grid-Tie Operation, and Battery mode. Each mode has specific conditions and display characteristics. Refer to PDF pages 25-26 for detailed descriptions of each operating mode.

Visual representation of the inverter's operating modes: Standby, Line, Grid-Tie Operation, and Battery mode, integrated into a home solar system.
Inverter Operating Modes.
Diagram illustrating four battery charging modes: PV Priority, Utility Priority, PV and Utility, and Only PV.
Four Battery Charging Modes.
Diagram illustrating three power output modes: PV Priority, Utility Priority, and Inverter Priority.
Three Power Output Modes.
Collage of common home appliances (TV, refrigerator, computer, wall breaking machine, microwave oven, dishwasher) that can be powered by the inverter.
Examples of home appliances powered by the inverter.

4.7 Descripció de l'equalització de la bateria

La funció d'equalització s'afegeix al controlador de càrrega. Inverteix l'acumulació d'efectes químics negatius com l'estratificació, una condició en què la concentració d'àcid és més gran a la part inferior de la bateria que a la part superior. L'equalització també ajuda a eliminar els cristalls de sulfat que s'hagin pogut acumular a les plaques. Si no es controla, aquesta condició, anomenada sulfatació, reduirà la capacitat total de la bateria. Per tant, es recomana equalitzar la bateria periòdicament.

Com aplicar la funció d'equalització: Primer heu d'habilitar la funció d'equalització de la bateria al programa de configuració 30 de la pantalla LCD de monitorització. A continuació, podeu aplicar aquesta funció al dispositiu mitjançant un dels mètodes següents:

  1. Configuració de l'interval d'equalització al programa 35.
  2. Igualació activa immediatament al programa 36.

Quan s'ha d'igualar: A la carrossa stage, quan arribi l'interval d'equalització de configuració (cicle d'equalització de la bateria) o l'equalització estigui activa immediatament, el controlador començarà a introduir l'Equalize stage.

Equalize charging time and timeout: A l'Equalize stage, el controlador subministrarà energia per carregar la bateria tant com sigui possible fins que la bateria voltage augmenta el volum d'equalització de la bateriatage. Aleshores, constant-voltagS'aplica la regulació per mantenir el volum de la bateriatage a l'equalització de la bateria voltage. La bateria romandrà a l'Equalize stage until the setting battery equalized time is arrived. However, if the battery equalized time is expired and the battery voltage no puja fins al volum d'equalització de la bateriatagpunt e, el controlador de càrrega allargarà el temps d'equalització de la bateria fins que el volum de la bateriatage aconsegueix el volum d'equalització de la bateriatage. Si la bateria voltage encara és inferior al vol d'equalització de la bateriatage quan s'hagi acabat el temps d'espera d'equalització de la bateria, el controlador de càrrega aturarà l'equalització i tornarà a la posició flotant.tage.

5. Manteniment

5.1 Acabatview of Anti-Dust Kit

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.

5.2 Clearance and Maintenance of Anti-Dust Kit

Pas 1: Please loosen the screw in the counterclockwise direction on the top of the inverter.

Pas 2: Then, the dustproof case can be removed, and the air filter foam can be taken out (refer to PDF page 30 for diagrams).

Pas 3: Netegeu l'escuma del filtre d'aire i la carcassa antipols. Després de netejar-lo, torneu a muntar el kit de pols a l'inversor.

AVÍS: el kit antipols s'ha de netejar de la pols cada mes.

6. Solució De Problemes

6.1 Codi de referència d'error

The inverter provides fault codes to help diagnose issues. Refer to the table below for common fault codes and their explanations.

Codi d'errorEsdeveniment de fallaExplicació / Possible causaQuè fer
01El ventilador està bloquejat quan l'inversor està apagat.Falla del ventiladorSubstituïu el ventilador.
02Excés de temperaturaLa temperatura interna del component inversor és superior a 100 °C.Comproveu si el flux d'aire de la unitat està bloquejat o si la temperatura ambient és massa alta.
03Bateria voltage és massa altaLa bateria està sobrecarregada.Comproveu si les especificacions i la quantitat de bateries compleixen els requisits.
04Bateria voltage és massa baixaLa bateria voltage és massa baixa. (<1.4 V/cel·la)Re-charge battery. Replace battery.
05Els components interns del convertidor detecten curtcircuits o sobretemperatura de sortida.Sortida curtcircuitat.Comproveu si el cablejat està ben connectat i elimineu la càrrega anormal.
06/58Volum de sortidatage is too high / Output abnormalSortida anormal (inversor voltage inferior a 190Vac o superior a 260Vac)Reduce the connected load. Return to repair center.
07Temps d'espera de sobrecàrregaError de sobrecàrrega. L'inversor està sobrecarregat un 110% i el temps s'ha acabat.Reduïu la càrrega connectada apagant alguns equips.
08/09/53/57Bus voltage is too high / Bus soft start failed / Inverter soft start failed / Current sensor failedEls components interns han fallat.Tornar al centre de reparació.
51Sobreintensitat o sobretensió.Sobreintensitat o sobretensió.Reinicieu la unitat, si l'error torna a passar, torneu al centre de reparació.
52Bus voltage és massa baixa.Bus voltage és massa baixa.Reinicieu la unitat, si l'error torna a passar, torneu al centre de reparació.
55Volum de sortidatage està desequilibrada.Volum de sortidatage està desequilibrada.Reinicieu la unitat, si l'error torna a passar, torneu al centre de reparació.

6.2 Indicador d'avís

The inverter provides warning indicators for various conditions. Refer to the table below for common warning codes and their audible alarms.

Codi d'avísEsdeveniment d'avísAlarma sonora
01El ventilador està bloquejat quan l'inversor està encès.Pica tres vegades cada segon
03La bateria està sobrecarregadaBeep un cop cada segon
04Bateria baixaBeep un cop cada segon
07SobrecàrregaBeep un cop cada 0.5 segons
10Reducció de la potència de sortidaPiteu dos cops cada 3 segons
15L'energia fotovoltaica és baixa.Piteu dos cops cada 3 segons
E9Equalització de la bateriaCap
bPLa bateria no està connectadaCap

7. Especificacions

7.1 Especificacions del mode de línia

MODEL INVERSOR3.6KW6.2KW
Entrada Voltage Forma d'onaSinusoïdal (utilitat o generador)
Volum d’entrada nominaltage100Vac
Baixa pèrdua voltage90Vac±5V (UPS); 90Vac±5V (electrodomèstics)
Retorn de pèrdua baixa Voltage95Vac±5V (UPS); 95Vac±5V (electrodomèstics)
High Loss Voltage145Vac±5V
Retorn de pèrdua alta voltage140Vac±5V
Volum màxim d'entrada de CAtage150Vac
Freqüència nominal d'entrada50 Hz / 60 Hz (detecció automàtica)
Baixa freqüència de pèrdua40 ± 1 Hz
Freqüència de retorn de baixa pèrdua42 ± 1 Hz
Alta freqüència de pèrdua65 ± 1 Hz
Freqüència de retorn d'alta pèrdua63 ± 1 Hz
Protecció contra curtcircuits de sortidaInterruptor
Eficiència (mode de línia)>95% (càrrega nominal R, bateria completament carregada)
Temps de transferència10 ms típic (UPS); 20 ms típic (electrodomèstics)

7.2 Especificacions del mode inversor

MODEL INVERSOR3.6KW6.2KW
Potència de sortida nominal3.6KW6.2KW
Vol. De sortidatage Forma d'onaOnda senyal pura
Vol. De sortidatage Reglament100/105/110/115/120Vac±5%
Freqüència de sortida50Hz / 60Hz
Màxima eficiència93%
Protecció de sobrecàrrega3s@≥150%; 5s@101%~150% load
Capacitat de sobretensióPotència nominal 2 * durant 5 segons
Volum d’entrada nominal CCtage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Vol. d'avís de CC baixtage @càrrega < 50%22.0Vdc44.0Vdc
Vol. d'avís de CC baixtage a càrrega ≥ 50%21.0Vdc42.0Vdc
Vol. de retorn d'avís de CC baixtage @càrrega < 50%22.5Vdc45.0Vdc
Vol. de retorn d'avís de CC baixtage a càrrega ≥ 50%22.0Vdc44.0Vdc
Vol de tall de CC baixtage @càrrega < 50%20.5Vdc41.0Vdc
Vol de tall de CC baixtage a càrrega ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
Vol de tall DC alttage33Vdc63Vdc
Consum d'energia sense càrrega45W50W

7.3 Potència de sortida de dues càrregues

MODEL INVERSOR3.6KW6.2KW
Càrrega completa3600W6200W
Càrrega principal màxima3600W6200W
Càrrega màxima de segona càrrega (model amb bateria)1200W2066W
Vol. de tall de càrrega principaltage26VDC52VDC
Retorn de càrrega principal Voltage27VDC54VDC

7.4 Especificacions del mode de càrrega

MODEL INVERSOR3.6KW6.2KW
Algoritme de càrrega3-Pas
Corrent de càrrega de CA (màx.)80Amp (@VI/P=100 Vca)
Vol. de càrrega a graneltage (Bateria inundada)29.258.4
Vol. de càrrega a graneltage (bateria AGM / de gel)28.256.4
Càrrega flotant Voltage27Vdc54Vdc
Màx. Potència de matriu fotovoltaica4200W6500W
Vol. PV nominaltage240Vdc360Vdc
PV Array MPPT Voltage Rang60Vdc~500Vdc
Màx. Circuit obert de matriu fotovoltaica Voltage500Vdc
Corrent de càrrega màxim (carregador de CA més carregador solar)120Amp120Amp

7.5 Operació de connexió a la quadrícula

MODEL INVERSOR3.6KW6.2KW
Volum de sortida nominaltage100/105/110/115/120VAC
Feed-in Grid Voltage Rang90~150VAC
Interval de freqüència de la xarxa d'alimentació49~51±1Hz/59~61±1Hz
Corrent de sortida nominal30A51.7A
Interval del factor de potència>0.99
Màxima eficiència de conversió (DC/AC)97%

7.6 Especificacions generals

MODEL INVERSOR3.6KW6.2KW
Certificació de seguretatCE
Interval de temperatura de funcionament-10 °C a 50 °C
Temperatura d'emmagatzematge-15°C~60°C
Humitat5% a 95% d'humitat relativa (sense condensació)
Dimensió (D * W * H), mm110X334X423110X334X423
Pes net, kg910

7.7 Taula de temps aproximat de còpia de seguretat

The following tables provide approximate back-up times for different loads and battery configurations.

ModelCàrrega (W)Temps de còpia de seguretat @ 24 Vdc 100 Ah (min)Temps de còpia de seguretat @ 24 Vdc 200 Ah (min)
3.6KW3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
6.2KW5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

Nota:

  1. El temps de còpia de seguretat depèn de la qualitat de la bateria, l'edat de la bateria i el tipus de bateria. Les especificacions de les bateries poden variar segons els diferents fabricants.
  2. El dret d'interpretació final d'aquest producte pertany a l'empresa.
Table of Inverter Model specifications including PV input, Grid Output, Two Load Output Power, and Off-Grid Operation details.
Inverter Model Specifications (Part 1).
Continuation of inverter specifications, covering Battery & Charger details, Hybrid Operation, and General Specifications.
Inverter Model Specifications (Part 2).

8. Consells d'usuari

9. Garantia i Suport

For detailed warranty information, service, and technical support, please refer to the complete user manual PDF available at: Hybrid Inverter User Manual (PDF). If you encounter any issues not covered in this manual or require further assistance, please contact your local dealer or the manufacturer's customer service.

Documents relacionats - NM-ECO-LV-3.6KW Plus

Preview Y&H Hybrid Inverter User Manual (3.6KW/6.2KW)
This user manual from Y&H (Shenzhen Yonghui Co., Ltd) provides comprehensive guidance for the NM-ECO-LV-3.6K Hybrid Solar Inverter models (3.6KW and 6.2KW). It details installation, operation, safety, troubleshooting, and specifications for efficient solar power system management.
Preview Manual d'usuari de l'inversor solar híbrid DAXTROMN 6200W PRO / 3600W PRO
Manual d'usuari complet per als inversors solars híbrids DAXTROMN de les sèries 6200W PRO i 3600W PRO, que detalla les especificacions, les característiques, els modes de funcionament i les directrius de seguretat per a una gestió eficient de l'energia solar.
Preview Manual d'usuari de l'inversor solar híbrid Sumry ECO LV 3.6KW
Manual d'usuari de l'inversor solar híbrid Sumry ECO LV 3.6KW, amb 110/120V, doble sortida de 24V, MPPT, controlador de càrrega de 120A i rang d'entrada de 60-450V. Proporciona informació essencial per a sistemes d'energia solar domèstica.
Preview Manual d'usuari de l'inversor solar fora de xarxa ECO-WORTHY de 3.5 kW
Aquest manual d'usuari proporciona instruccions completes de seguretat, instal·lació i funcionament per a l'inversor solar fora de xarxa ECO-WORTHY de 3.5 kW (model ECO3500W(SR)). Apreneu sobre la configuració del sistema, el cablejat, els modes de funcionament i les especificacions tècniques per a una gestió eficient de l'energia solar.
Preview Manual d'usuari de l'inversor fora de xarxa d'ona sinusoidal pura ECO-WORTHY de 3000 W i 24 V
Manual d'usuari de l'inversor de xarxa sense fil ECO-WORTHY de 3000 W i 24 V. Proporciona instruccions detallades sobre seguretat, instal·lació, funcionament, configuració de paràmetres, resolució de problemes i especificacions per a sistemes d'alimentació CC-CA fiables sense fil. Les característiques inclouen sortida d'ona sinusoidal pura, proteccions completes i capacitats de monitorització remota.
Preview Manual d'usuari de l'inversor fora de xarxa d'ona sinusoidal pura ECO-WORTHY de 3000 W i 24 V
Manual d'usuari de l'inversor fora de xarxa d'ona sinusoidal pura ECO-WORTHY de 3000 W i 24 V. Aquesta guia proporciona informació essencial sobre seguretat, instal·lació, funcionament i resolució de problemes per a solucions d'alimentació fora de xarxa fiables en diverses aplicacions.