1. Acabatview
The Smartgen FPC2000 is a sophisticated diesel-driven fire pump controller designed for fire pump systems that are controlled by an engine. This manual provides detailed instructions for the installation, operation, and maintenance of the FPC2000 controller to ensure its reliable performance in critical fire protection applications.


2. Configuració i instal·lació
The FPC2000 is designed for panel-mounted installation. Proper installation is crucial for the controller's functionality and safety.
2.1 Overall and Cutout Dimensions

2.2 Instruccions de muntatge
The FPC2000 is designed to be panel-mounted and fixed by clamps during installation. Follow these steps:
- Screw off the screw of fixed metal clamp counterclockwise to a proper position.
- Estireu el cl de metallamps backward one by one to make all four fixed metal clamps fixed in the specified slots.
- Tighten the screw of the metal clamp clockwise and make sure it is fixed on the controller panel.
- Don't tighten the screws of metal clamps too tightly.
- FPC2000 is installed on the DIN rail, with compact structure and convenient installation.

2.3 Connexió del cablejat
Refer to the terminal descriptions for proper wiring. Ensure all connections are secure and follow local electrical codes.

Table: Description of Display Module Connection Terminals
| No. | Item | Mida del cable | Observacions |
|---|---|---|---|
| 1 | PE | 1.0 mm² | Terminal de terra |
| 2 | Entrada d'alimentació CC B- | 1.0 mm² | Connect with the negative of DC power supply. |
| 3 | Entrada d'alimentació CC B+ | 1.0 mm² | Connect with the positive of DC power supply. |
| 4 | GND | 1.0 mm² | Common terminal of digital input. |
| 5 | Extension Digital Input 1 | 1.0 mm² | It is used as the digital input of master control module. |
| 6 | Extension Digital Input 2 | 1.0 mm² | It is used as the digital input of master control module. |
| 7 | GND | 1.0 mm² | Common terminal of analog input. |
| 8 | Extension Analog Input 1 | It is used as the analog input of master control module. | |
| 9 | Extension Analog Input 2 | It is used as the analog input of master control module. | |
| 10 | CAN H | 0.5 mm² | Reserved ports. |
| 11 | CAN L | 0.5 mm² | 120Ω impedance shielded twisted pair cable is recommended, and one end of the cable must be grounded. 120Ω termination resistor will be connected if terminal 10 is connected with Terminal 12 directly. |
| 12 | Termination Resistor (120Ω) | 0.5 mm² |
3. Instruccions de funcionament
This section details the various methods for operating the FPC2000 controller, including manual and automatic start/stop procedures, and navigating the display.
3.1 Panel of Controller and Buttons

Table: Instruction of Indicators
| Tipus | Instrucció |
|---|---|
| Indicador d’execució | It lights up when it starts successfully by Battery I. |
| Running II Indicator | It lights up when it starts successfully by Battery II. |
| Stop Indicator | It lights up when the running of engine stops. |
| Indicador de prova | It lights up when the engine is under test. |
Table: Description of Buttons
| Icona | Botó | Descripció |
|---|---|---|
| Start I | Press the button to start the engine by Battery I. | |
| Inici II | Press the button to start the engine by Battery II. | |
| Atureu-vos | Press the button to manually stop the engine. | |
| Prova | Press the button to open the bypass valve, so the sensor will detect the pressure drop. |
Note: The button icons are illustrative and may not be perfectly rendered from the source image. Refer to the physical device for exact button appearance.
3.2 Start Methods
- Inici manual: In manual mode, the fire pump engine can be started by pressing the "Start I" or "Start II" button regardless of the system pressure.
- Remote Manual Start: In manual mode, the fire pump engine can be started by closing the "Remote Manual Start" input.
- Test Start: In auto mode, press the "Test" button to open the bypass valve, the sensor detects the pressure drop, then the fire pump engine will start.
- Inici automàtic: In auto mode, when the pressure drops below the start pressure, the controller will automatically start the fire pump engine when the pressure sensor detects the low pressure.
- Remote Auto Start: In auto mode, the fire pump engine can be started by opening the "Remote Auto Start" or "Deluge Valve Start" input.
- Inici del flux: In auto mode, the fire pump engine can be started by closing the "Flow/Zone Start" input.
- Weekly Start: In auto mode, according to the set value of scheduled start parameters, the fire pump engine can be automatically started at a pre-programmed time.
- Inici seqüencial: For the application of multiple pumps, it is necessary to set an automatic start delay for all fire pump engines to prevent them from starting simultaneously when pressure drops.
- Auto Start Sequence:
- When the conditions for auto start are satisfied, it will enter the "Start delay".
- After the start delay is over, the fuel relay will activate and the crank relay activates at the same time. If the pump unit does not start successfully within the "Crank Time", the fuel relay and the crank relay will deactivate; it will enter the "Crank Rest Time", and wait for the next start.
- At any start, if the pump unit starts successfully, the fuel relay continues to activate, while the crank relay deactivates, and the pump unit enters the normal running status.
- Within the set start times, if the pump unit does not start successfully, the controller will issue a start failure alarm; at the same time, the fuel relay and crank relay will deactivate, the ETS relay will activate, and it will deactivate after the stop detection time (10s) is over.
3.3 Stop Methods
- Parada manual: In manual mode, press the "Stop" button to remove the manual start signal.
- Parada automàtica: The fire pump engine can only be automatically stopped after it has been started automatically and the automatic stop function is enabled. Once the automatic stop function is activated, if there are no other operation reasons, the fire pump engine will be automatically stopped when the pressure has recovered for 10 minutes (above the stop pressure set value).
- Flow Stop: If the controller has been started by "Flow/Zone Start" input and the signal has returned to normal, the fire pump engine will be stopped if there are no other operation reasons.
- Mode de parada: Regardless of the present starting reason, once the controller is switched to stop mode, the fire pump engine will be stopped.
- Stop Sequence: When all the start signals are removed or the controller is switched to stop mode, the controller will execute the stop process, the fuel relay will deactivate, the ETS relay will activate, and it will deactivate after the stop detection time (10s) is over. In auto mode, if the engine running signal is detected, the stop failure fault will be issued.
3.4 Navegació i configuració de la pantalla
The FPC2000 features a user-friendly display for monitoring and configuration.
- Primera posada en marxa: When the controller is started for the first time, the "First Start Up" page appears. Click the "User Login", then enter the valid password. After logging in, the icon in front of the "User Login" is unlocked and the unlock level will be displayed.
- Power Information Confirm: After logging in, click the "Power" button. Verify the voltage of chargers and batteries matches the actual value. If everything is normal, click the "Confirm" button to confirm the power information and return to the First Start page. After returning to the First Start page, the icon "√" will be displayed in front of the "Power" button.

Figure 7: Power Information Page. This screen displays battery voltage and charger status, allowing confirmation of power settings. - Pressure Information Confirm: Click the "Pressure" button, verify if the pressure reading on the screen matches the reading on the calibrated pressure meter installed beside the sensor.
- Pressure unit follows the configuration of the pressure sensor.
- If necessary, you can adjust the maximum value of the pressure sensor measuring range.
- If necessary, you can adjust the "Start Pressure" and "Stop Pressure" values of the fire pump.
- Once adjustments are completed and you confirm that the current pressure is consistent with the pressure meter reading, click the "Confirm" button to confirm the pressure information and return to the First Start page.
- Engine Start Confirm: Click the "Engine Start Up" button to enter the Engine Start Test page. Click the "Start I" or "Start II" button to start the fire pump engine by Battery I or Battery II, and verify if the engine starts normally or not. Press the "Stop" button to stop the fire pump engine. Press the "Confirm" button to confirm the current information and return to the First Start page.

Figure 8: Engine Start Test Page. This screen allows for testing engine startup and confirming its status. - Configuració de data i hora: If you want to adjust the date and time, click the "Date & Time" button to enter the date and time setting interface. After setting the date and time correctly, click the "Modify" button to save the setting. Then, click on the "Back" button to return to the First Start page.

Figure 9: Date & Time Setting Page. This interface allows users to adjust the controller's internal clock. - Pàgina de configuració: Click the "Parameters Setting" to enter the parameters setting page, all parameters of master control module can be set in this page. Password is required when entering the parameters setting page. The password can be set to dynamic password with the form of "yyyyMMdd", you can modify all parameters (the default password is 666221). After the password is entered successfully, it remains valid for five minutes. During this period, when entering the parameters setting page again, the password is not required. The icon in the right side of the "Parameters Setting" button displays the current password status. If it is the unlock status, click the icon to re-lock.

Figure 10: Configuration Page. This page allows advanced users to modify various operational parameters of the controller.
4. Manteniment
To ensure the longevity and reliable operation of your FPC2000 controller, regular maintenance is recommended. Keep the unit clean and free from dust and moisture. Periodically check all wiring connections for tightness and signs of wear. Refer to the full user manual for detailed maintenance schedules and procedures, if available from the manufacturer.
5. Solució De Problemes
If you encounter issues with your FPC2000 controller, consider the following general troubleshooting steps:
- Sense energia: Check the DC power input connections and ensure the power supply is active.
- El motor no arrenca: Verify battery connections, fuel supply, and check for any alarm indicators on the display. Review the start sequence in the operating instructions.
- Lectures incorrectes: Ensure sensors are correctly wired and calibrated. Check the "Power Information Confirm" and "Pressure Information Confirm" sections in the operating instructions.
- Errors de comunicació: Check CAN and Ethernet cable connections.
For persistent issues or complex problems, it is recommended to consult the full user manual or contact qualified technical support.
6. Especificacions
The Smartgen FPC2000 Diesel Fire Pump Controller boasts the following technical specifications and performance features:
6.1 Característiques de rendiment
- 7-inch large color LCD screen, resistive touch screen, which supports one-click switching between Chinese and English.
- It can collect and display AC voltage, and frequency, and support overvoltage, minvartage, overfrequency, underfrequency detection.
- Real-time display of charging battery over voltage and current, two-way starter battery voltage.
- Real-time display of alarm information from the master control module.
- It supports multiple types of sensors, including resistance type, 4-20mA current type, 0-5V voltage type sensors. And it supplies the sensors with voltage of 5V or 24V. Sensor parameters are adjustable.
- In manual mode, it can control the start/stop of engine by buttons.
- Input lock function, the start/stop of engine can only be controlled by start and stop buttons on the panel when this function is active.
- All parameters can be programmed on site, with two-level password verification to prevent misoperation by non-professionals.
- 8-35VDC power supply range of (8-35VDC) which can be supplied by the engine's starting battery.
- RS485 communication port, and USB Type-C port for parameter configuration of upper computer and reading of histories.
- Real-time alarm event recording function, which can record up to 500 pieces of data cyclically.
- Timed recording function, which can record system pressure, voltage, and current for up to 500 pieces of data cyclically by the preset interval automatically.
- Display the number of start times, total accumulated running time, previous accumulated running time, current accumulated running time of the pump engine.
- Visualització del rellotge en temps real.
- Adjustable screen brightness for display module based on the different requirements of environment.
- All parameters of the master control module can be adjusted, and the display module communicates with the master control module via the CANBUS port.
- USB Type-C port for convenient parameter debugging and program upgrade on site.
- USB host port for exporting alarm event records and data record data.
- Rubber sealing gasket design between the enclosure and screen for IP65 waterproof performance.
- With modular structure design, pluggable terminals, embedded mounting, and compact structure, it is easy to install.
6.2 Paràmetres tècnics
Table: FPC2000 Technical Parameters
| Item | Contingut |
|---|---|
| Vol. Operatiutage | 8VDC~35VDC, protection for DC reverse connection. Resolution: 0.1V. Precision: 1%. |
| Consum d'energia | ≤7W (Standby mode: ≤5W). |
| Resistance Input | Range: 0Ω ~ 6000Ω. Resolution: 1Ω. Precision: 1Ω (Below 300Ω). |
| Sensor analògic | Voltage input: Range: 0V ~ 5V. Resolution: 0.01V. Precision: 1%. Current input: Range: 4mA ~ 20mA. Resolution: 0.1mA. Precision: 1%. |
| Extension Digital Output 1-3 | Capacity 10A @ 250VAC, passive output. |
| Extension Aux. Input 1-2 | Active when it is grounded (GND). Low threshold voltage is less than or equal to 1.4VDC, and maximum voltagL'entrada és de 60 VCC. |
| Port RS485 | Isolated, half-duplex, baud rate at 9600, maximum communication distance at 1000m. |
| MS/CAN Port | Isolated, maximum communication distance at 250m. Boston 9841 cable or other equal rating cable is required. |
| CE-EMC Certification | EN 55024, EN 55022. |
| Dimensions de la caixa | 209 mm x 189 mm x 99 mm. |
| Retall del panell | 188.5 mm x 165.5 mm. |
| Temperatura de treball | (-25~+70)°C (The module mounting part can't withstand high temperature). |
| Humitat de treball | (20~90)%RH. |
| Temperatura d'emmagatzematge | (-30~+80)°C (The module mounting part can't withstand high temperature). |
| Classificació IP | Front enclosure: IP65 when waterproof rubber gasket is installed between controller panel and enclosure. |
| Força dielèctrica | Aplicar voltage of 2.2KV AC between AC high voltage terminal i baix voltage terminal, and the leakage current is below 3mA in one minute. |
| Pes | 0.90 kg. |
Note: Some parameters are derived from FPC200M and FPC2000D tables, assumed to be relevant to the FPC2000 model.
7. Consells d'usuari
Based on common inquiries, here are some tips for using your FPC2000 controller:
- Always ensure the correct password is used for accessing configuration settings to prevent unauthorized changes.
- Regularly check the display for any alarm messages and address them promptly to maintain system integrity.
- For optimal performance, ensure all sensors are properly connected and calibrated according to the specifications.
8. Preguntes freqüents (FAQ)
- Q: What does this controller include?
- A: The Smartgen FPC2000 controller typically includes the main control unit with its display and buttons, designed for panel mounting. It is intended to be integrated into a larger fire pump system. Specific accessories like wiring, sensors, or external power supplies are usually sourced separately or as part of the complete fire pump system installation.
9. Garantia i Suport
For warranty information, technical support, or service inquiries, please contact your supplier or the manufacturer directly. Keep your purchase records and product model number (FPC2000) handy when seeking assistance.