1. Producte acabatview
The GEYA GRD9L-R A-SI RCCB Auto Recloser is an advanced automatic reclosing leakage circuit breaker designed to enhance electrical system reliability and reduce maintenance costs. It automatically recloses after an electrical fault, specifically earth leakage current, eliminating the need for manual intervention. This device is suitable for a wide range of applications, including power grid terminal lines, meter boxes, new energy circuit management, PV solar control boxes, smart electricity systems, smart homes, and electric vehicle charging piles.
This manual provides essential information for the safe and effective installation, operation, and maintenance of your GRD9L-R A-SI RCCB Auto Recloser.
2. Característiques clau
- Compatible with Residual Current Circuit Breakers (RCCB) for remote switching and splitting.
- Equipped with a manual/automatic selector switch for flexible operation.
- Features mechanical and electronic double locking functions for enhanced safety.
- LED indicator provides clear status of operation.
- Automatically switches on the distribution board following an electrical trip.
- Adjustable auto reclosing interval times: 10 seconds, 60 seconds, and 300 seconds.
- Includes 3 built-in reclosing attempts; continuous closing failure within 15 minutes triggers an alarm via an auxiliary contact.
- Manual reclosing time can be cleared by switching from AUTO to MANU and back to AUTO.
- A-SI Type RCD (Electromagnetic Super Immunised) for improved immunity to nuisance tripping.
3. Aplicacions
The GRD9L-R A-SI RCCB Auto Recloser is ideal for:
- Power grid terminal lines
- Meter boxes
- New energy circuit management
- PV solar control boxes
- Smart electricity systems
- Smart home installations
- Electric vehicle charging piles
4. Configuració i instal·lació
Advertència de seguretat: Installation should only be performed by qualified personnel in accordance with local electrical codes and regulations. Ensure power is disconnected before installation.
4.1 Instal·lació física
The GRD9L-R is designed for DIN rail mounting (EN/IEC 60715). Ensure sufficient space for ventilation and access to controls.
4.2 Esquema de cablejat
Refer to the wiring diagram below for proper connection. The device can cooperate with both RCCB and MCB units. Ensure correct polarity and secure connections for all terminals.
Passos d'instal·lació:
- Mount the GRD9L-R unit onto a standard DIN rail.
- Connect the main power supply (L and N) to the designated terminals.
- Connect the RCCB/MCB unit to the GRD9L-R as shown in the 'Cooperate with RCCB' or 'Cooperate with MCB' sections of Figure 1.
- Connect the load to the output terminals of the RCCB/MCB.
- Assegureu-vos que totes les connexions estiguin estretes i segures.
- Verify the closing lock mechanism is correctly engaged when not performing maintenance.
5. Instruccions de funcionament
5.1 Selecció del mode
- Mode AUTOMÀTIC: The auto reclosing function is enabled. The device will automatically attempt to reclose the circuit after a trip.
- MANU Mode: The auto reclosing function is disabled. The MCB/RCCB can only be opened and closed manually.
5.2 Indicadors d'estat
The device features an LED indicator:
- LED verd: Indicates stable power supply.
- LED vermell: Indicates that the MCB/RCCB has tripped. After a delay, the device will attempt to reclose, and if successful, the green LED will illuminate.
5.3 Auto Reclosing Logic
In AUTO mode, the GRD9L-R follows a specific reclosing sequence after a trip:
- 1st Attempt: After 10 seconds, the device attempts to reclose. If successful, the cycle resets.
- 2nd Attempt: If the 1st attempt fails, after 60 seconds, it attempts to reclose again.
- 3rd Attempt: If the 2nd attempt fails, after 300 seconds, it attempts to reclose a third time.
- Bloqueig: If the 3rd attempt fails, the device enters a lockout state for 15 minutes. During this time, continuous closing failure will send an alarm via auxiliary contact.
The power delay before the first reclosing attempt is 2 seconds. The closing times can be manually cleared by switching the mode from AUTO to MANU and then back to AUTO.
6. Manteniment
Regular maintenance ensures optimal performance and safety of the GRD9L-R Auto Recloser.
- Prova mensual: Press the 'Test Monthly' button on the device to verify its tripping mechanism. The device should trip and then attempt to reclose according to its programmed logic.
- Inspecció visual: Periodically inspect the device for any signs of physical damage, loose connections, or overheating.
- Neteja: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
If any issues are observed during inspection or testing, refer to the Troubleshooting section or contact technical support.
7. Solució De Problemes
This section provides solutions for common issues encountered with the GRD9L-R Auto Recloser.
| Descripció de l'error | Resolvent |
|---|---|
| Unable to close or open |
|
| Trips immediately after closing |
|
If the problem persists after following these steps, please contact GEYA technical support.
8. Especificacions
| Paràmetre | Valor |
|---|---|
| Nom de marca | GEYA |
| Número de model | GYL9 RCCB Recloser (GRD9L-R) |
| Tipus | Earth Leakage, RCD |
| Voltage | 220 V CA |
| Corrent nominal | 40A (also available in 63A) |
| Rated Residual Operating Current (IΔn) | 30 mA |
| Rated Residual Non-Operating Current (IΔno) | 15 mA |
| Rated Conditional Short-Circuit Current (Inc=IΔc) | 6000A |
| Resistència d'impuls nominal Voltage (Uimp) | 4kV |
| Freqüència nominal | 50/60Hz |
| Nombre de pols | 2P (also available in 4P) |
| Mode de control | Retancament automàtic |
| Supply Terminals | DC12V, DC24-48V, AC220V |
| Entrada d'alimentació (DC) | Max. 1W (standby), Max. 20W (action) |
| Entrada d'alimentació (CA) | Max. 1VA (standby), Max. 20VA (action) |
| Subministrament Voltage Tolerància | -10% ~ +10% |
| Supply Indication | LED vermell |
| Temps d'acció | <1 s |
| Auto Reclosing Times | 3 |
| Auto Reclosing Interval Time | Anys 10, 60, 300 |
| Reset Reclosing Times | No trip or manual reset within 15 minutes after successful closing |
| Vida mecànica | 10000 cicles |
| Electrical Life (AC1) | 4000 cicles |
| Temperatura de funcionament | -20 °C a +55 °C (-4 °F a 131 °F) |
| Temperatura d'emmagatzematge | -35 °C a +75 °C (-22 °F a 158 °F) |
| Mounting / DIN Rail | DIN rail EN/IEC 60715 |
| Grau de Protecció | IP20 |
| Posició operativa | Qualsevol |
| Overvoltage Categoria | III |
| Grau de contaminació | 2 |
| Max. Cable Size (mm²) | Solid wire max. 1×2 or 2×1.5; with sleeve wire max. 1×2.5 (AWG 12) |
| Certificació | CE, RoHS |
8.1 Dimensions
For detailed dimensions of the 2P and 4P models, please refer to the diagrams below:
9. Consells d'usuari
- Always ensure the device is in MANU mode when performing any wiring or maintenance to prevent accidental reclosing.
- For critical applications, consider integrating the auxiliary contact alarm with a monitoring system to receive immediate notifications of persistent faults.
- Regularly check the LED indicator for operational status, especially after power fluctuations or trips.
10. Garantia i Suport
GEYA products are manufactured to high standards and come with a manufacturer's warranty. For specific warranty terms and conditions, please refer to the documentation provided with your purchase or contact GEYA customer service.
For technical support, troubleshooting assistance, or inquiries regarding your GRD9L-R A-SI RCCB Auto Recloser, please contact GEYA directly. You can find contact information on the official GEYA weblloc web o a través del vostre distribuïdor autoritzat.