GEYA W2R ATS Dual Power Automatic Transfer Switch User Manual

Model: W2R-100 | Brand: GEYA

1. Producte acabatview

The GEYA W2R Automatic Transfer Switch (ATS) is designed to automatically switch between a main power source and a backup power source, ensuring an uninterrupted power supply for various applications. It supports both automatic and manual operation modes and includes real-time voltage monitoring and protection features.

Les característiques clau inclouen:

  • Quick switching time: Less than 50 milliseconds.
  • Voltage compatibility: Supports 110V or 220V systems.
  • PC Level performance.
  • Integrated Overvoltage Protecció.
  • Integrated Undervoltage Protecció.
  • High current capacity: Up to 100A.
GEYA W2R ATS Dual Power Automatic Transfer Switch with key features listed
Figure 1: GEYA W2R ATS Dual Power Automatic Transfer Switch highlighting its main features.

2. Precaucions de seguretat

WARNING: Electrical installation should only be performed by qualified personnel. Always disconnect power before installation or maintenance.

  • Assegureu-vos que el volum nominaltage of both the main and backup power supplies is within 85%-110% of the rated value.
  • The operating current must not be less than 5A. Failure to meet these requirements may cause the coil to overheat or spontaneously combust.
  • If your local grid voltage is unstable, it is strongly recommended to install additional voltage protectors in the system.
  • For stable and reliable switching when connecting a PV inverter, ensure it is a Pure Sine Wave type with a rated power greater than 3000W.

3. Instal·lació i cablejat

3.1 Components anteriorsview

Primer pla view of GEYA W2R ATS components including copper terminals, guide rail installation, and silver contacts.
Figura 2: Detallada view of the ATS components: Copper Terminals, Guide Rail Installation, and Silver Contacts.

The GEYA W2R ATS features robust copper terminals for secure connections, silver contacts for reliable switching, and is designed for easy guide rail installation.

3.2 Esquema de cablejat

The following diagrams illustrate typical wiring configurations for the GEYA W2R ATS. Ensure all connections are secure and comply with local electrical codes.

Wiring diagrams for 2-pole and 4-pole GEYA W2R ATS, showing connections for common power supply, standby power supply, backup control line, load output, and alternate control line.
Figure 3: Product Wiring Diagram for 2-pole and 4-pole configurations.

For 2-Pole Configuration (Top Left Diagram):

  • Connect the Common Power Supply (L, N) to the designated terminals.
  • Connect the Standby Power Supply to its respective terminals.
  • Connect the Backup Control Line.
  • Connect the Load Output to your electrical loads.

For 4-Pole Configuration (Top Right Diagram):

  • Connect the Common Power Supply (L1, L2, L3, N) to the designated terminals.
  • Connect the Backup Power to its respective terminals.
  • Connect the Alternate Control Line.
  • Connect the Load Output to your electrical loads.

Notes generals de cablejat:

  • Ensure proper phase sequence for multi-phase systems.
  • All connections must be tight to prevent loose contacts and overheating.

3.3 Connecting External Indicators

The ATS provides passive terminals (NO, C, NC) for connecting external indicators, allowing you to monitor the product's operation from outside the cabinet.

Wiring diagram for connecting external indicators to the GEYA W2R ATS, showing common closing/opening and backup closing/opening indicators.
Figure 4: Wiring for External Indicators.

Connect your common closing/opening indicators and backup closing/opening indicators to the NO, C, NC terminals as shown in Figure 4. These are passive terminals and do not supply voltage.

4. Funcionament

4.1 Automatic and Manual Modes

The GEYA W2R ATS supports both automatic and manual operation. Use the selection switch on the unit to choose your desired mode.

GEYA W2R ATS showing the manual/automatic selection switch and LED indicators for normal and abnormal voltage.
Figure 5: Manual/Automatic Selection Switch and LED Indicators.
  • Mode automàtic: The switch will automatically transfer power sources based on voltage condicions.
  • Mode manual: Allows for manual switching using the handle. This mode is typically used for testing or specific maintenance scenarios.

4.2 Power Transfer Function

The ATS is designed to seamlessly switch between power sources in case of a mains failure or restoration.

Diagram illustrating the function of the Automatic Transfer Switch: switching from City Power/PV AC Power to Standby Power Generator upon mains failure, and back when mains are normal, with a 50ms switch time.
Figure 6: Automatic Transfer Switch Function Diagram.

The transfer time is less than 50 milliseconds, ensuring minimal disruption to connected loads.

4.3 voltage Monitoring and LED Indicators

The device continuously monitors the voltage of the connected power sources and provides visual feedback through LED indicators.

CondicióLED estatAcció
Normal VoltageTwo LEDs stay on constantly.No cal cap acció.
Anormal Voltage (General)Lights are flickering. LED displays a breathing effect (dims gradually during undervoltage, brightens gradually during overvoltagi).Switches to standby power after a 10-second delay (default setting).
Overvoltage EstatLED flashes twice every 2 seconds.Automatic transfer to standby power if configured.
Undervoltage EstatLED flashes once every 2 seconds.Automatic transfer to standby power if configured.

Voltage Protection Parameters (for 220V W2R):

  • Undervoltage Trip Value: 175V
  • Undervoltage Recovery Value: 190V
  • Overvoltage Trip Value: 270V
  • Overvoltage Recovery Value: 250V
  • Delay for Trip: 10 seconds
  • Delay for Reset: 30 seconds

5. Manteniment

The GEYA W2R ATS is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.

  • Inspecció visual: Periodically inspect the unit for any signs of physical damage, loose connections, or discoloration.
  • Estanquitat del terminal: Ensure all wiring terminals remain tight. Loose connections can lead to overheating and potential hazards.
  • Pols i deixalles: Keep the unit free from dust and debris. Use a soft, dry cloth for cleaning. Do not use liquid cleaners.
  • Prova de funcionalitat: Periodically test the automatic transfer function by simulating a main power failure (if safely possible and recommended by a qualified electrician).
  • Inspecció professional: It is advisable to have a qualified electrician inspect the unit and its connections annually.

6. Solució De Problemes

This section provides guidance on common issues you might encounter with your GEYA W2R ATS.

ProblemaCausa possibleSolució
ATS does not transfer power automatically.
  • Voltage of main or backup power is outside the 85%-110% rated range.
  • Operating current is less than 5A.
  • Unit is in Manual mode.
  • Cablejat o connexions defectuoses.
  • Comproveu el volum d'entradatages and ensure they are within the specified range.
  • Verify the load current meets the minimum requirement.
  • Switch the unit to Automatic mode.
  • Inspect all wiring connections for tightness and correctness. Consult a qualified electrician if unsure.
LED indicators are flickering or flashing.
  • Vol anormaltage detected (overvoltage o undervoltagi).
  • Refer to Section 4.3 "Voltage Monitoring and LED Indicators" to interpret the specific flashing pattern.
  • Consulteu el voltage of the power supply. Consider installing additional voltage protectors if the grid is unstable.
La unitat s'sobreescalfa.
  • Voltage or current requirements not met.
  • Connexions fluixes.
  • Assegureu-vos voltage is within 85%-110% of rated value and current is not less than 5A.
  • Reviseu i estrenyeu totes les connexions elèctriques.
Issues with PV Inverter connection.
  • Inverter is not a Pure Sine Wave type.
  • Inverter rated power is less than 3000W.
  • Ensure the PV inverter is a Pure Sine Wave type.
  • Verify the PV inverter has a rated power greater than 3000W for stable operation.

7. Especificacions

CaracterísticaEspecificació
Nom de marcaGEYA
Número de modelW2R-100
Tipus de canviInterruptor universal
Corrent nominal100A
Bobina Voltage220 V
Pols2P, 4P
Resistència d'impuls nominal Voltage (KV)8KV AC 110V or 220V
Vol. d'oferta nominaltage Nosaltres50 Hz
Condicions de treball85% Us - 110% Us
Hora de canvi<50 ms
Temps d'acció<50 ms
Vida elèctrica2000 vegades
Vida mecànica5000 vegades
MaterialPlàstic
És un dispositiu intel·ligentNo
CertificacióCE
OrigenXina continental
EU LVD VoltageVol baixtage: Below 50Vac or 75Vdc
Substància química molt preocupantCap

7.1 Dimensions (Approximate)

Diagram showing dimensions of the GEYA W2R-100 ATS unit in millimeters.
Figure 7: Product Dimensions (Unit: mm).
  • Amplada: 78.5 mm
  • Alçada: 103 mm
  • Depth (2P): 107.5 mm
  • Depth (3P): 125.5 mm
  • Depth (4P): 142.5 mm
  • Profunditat de muntatge: 35 mm

8. Garantia i Suport

8.1 Garantia del producte

The GEYA W2R ATS comes with a 2 any de garantia from the date of purchase, covering manufacturing defects and malfunctions under normal operating conditions.

8.2 Suport tècnic

For technical assistance, inquiries, or support, please contact GEYA customer service:

  • Weblloc: www.geya.net
  • Correu electrònic: cassie@cngeya.com
  • Telèfon: +86 13968799499
  • Address: Wenzhou Bridge Industrial Zone, Beibaixiang Town, Wenzhou City, Zhejiang Province

Documents relacionats - W2R-100

Preview GEYA W2R-W1 Smart ATS Quick Start Guide: Dual Power Automatic Transfer Switch
Get started quickly with the GEYA W2R-W1 Smart ATS Dual Power Automatic Transfer Switch. This guide covers setup, network configuration, and device management for this 2P/3P/4P Din Rail device, ensuring uninterrupted power supply.
Preview EARU EAATS-A Automatic Transfer Switch: User Manual & Safety Guide
This manual provides essential safety instructions, product description, and technical specifications for the EARU EAATS-A Automatic Transfer Switch, a miniature dual power switch for household and standby power management.
Preview Manual del commutador de transferència automàtica dual de commutació ininterrompuda de mil·lisegons de Zhejiang Geya Electrical
Aquest manual proporciona informació detallada sobre el commutador de transferència automàtica dual de commutació ininterrompuda de mil·lisegons de Zhejiang Geya Electrical Co., Ltd., incloent-hi informació general, paràmetres tècnics, instal·lació, cablejat, manteniment i precaucions de seguretat.
Preview Manual d'usuari del commutador de transferència automàtica
User manual for the Dual Power Smart Automatic Transfer Switch (ATS) by MOES, detailing installation, operation, specifications, and safety recommendations for off-grid solar and wind systems.
Preview Manual d'usuari de l'interruptor de transferència automàtica ATS-16A ONLINE
Manual d'usuari complet per al commutador de transferència automàtica ONLINE ATS-16A, que detalla les seves característiques, instal·lació, funcionament, especificacions i resolució de problemes per a una gestió fiable de doble font d'alimentació.
Preview Commutador de transferència automàtica (ATS) GEYA G2R-63/00 - Especificacions tècniques
Especificacions tècniques detallades i guia d'instal·lació per al commutador de transferència automàtica (ATS) GEYA G2R-63/00, que inclou commutació de classe PC per a fonts d'alimentació duals, condicions de funcionament i procediments de manteniment.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.