ANENJI ANJ-HHS-11KW-48V-WIFI/ANJ-11KW-48V-WIFI-P

ANENJI 11KW 48V Hybrid Solar Inverter User Manual

Model: ANJ-HHS-11KW-48V-WIFI / ANJ-11KW-48V-WIFI-P

Marca: ANENJI

1. Introducció

1.1 Sobre aquest manual

This manual describes the assembly, installation, operation, and troubleshooting of the ANENJI 11KW 48V Hybrid Solar Inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Àmbit

This manual provides safety and installation guidelines as well as information on tools and wiring for the inverter/charger.

1.3 Característiques

  • Inversor d'ona sinusoïdal pura
  • Inversor funcionant sense bateria
  • Built-in MPPT solar controller
  • Vol d'entrada configurabletagGamma per a electrodomèstics i ordinadors personals mitjançant la configuració LCD
  • Corrent de càrrega de la bateria configurable basat en aplicacions mitjançant configuració LCD
  • Prioritat del carregador AC / Solar configurable mitjançant configuració LCD
  • Compatible amb xarxa voltage o potència del generador
  • Es reinicia automàticament mentre AC es recupera
  • Protecció contra sobrecàrrega / sobre temperatura / curtcircuit
  • Disseny intel·ligent del carregador de bateries per obtenir un rendiment de bateria optimitzat
  • Funció d’arrencada en fred
  • Built-in 2 MPPT for optimal solar panel performance
  • Li-Ion Battery Activation via PV or utility power
  • LiFePO4 Battery Compatible via RS485 interface
  • Power Factor 1.0 for efficient power delivery
  • Photovoltaic input up to 500Vdc
  • Built-in 160A MPPT controller
  • Removable Dust Cover for harsh environments
  • WiFi Remote Monitoring with real-time system status updates
  • Supports multiple output priorities: UTL, SOL, SBU, SUB modes
  • Battery Optimization EQ Function to extend battery life
  • Off-grid and on-grid functionality
  • Dual Load Output (V2.0)
  • Two PV Inputs (ensure same number of solar panels in series for each side if parallel)

1.4 Arquitectura bàsica del sistema

The following illustration shows the basic application for this inverter/charger, including a generator or utility and optional PV modules. Consult your system integrator for other possible system architectures depending on your requirements. This inverter can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

System architecture diagram showing solar panels, inverter, battery, power grid, generator, and household appliances.
Figure 1: Hybrid Power System Architecture. This diagram illustrates the connections between solar panels, the inverter, battery, power grid, generator, and various household appliances.

2. Instruccions de seguretat

ADVERTÈNCIA: aquest capítol conté instruccions importants de seguretat i funcionament. Llegiu i guardeu aquest manual com a referència futura.

  1. Abans d'utilitzar la unitat, llegiu totes les instruccions i les marques d'advertència de la unitat, les bateries i totes les seccions adequades d'aquest manual.
  2. PRECAUCIÓ – To reduce the risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. No desmunteu la unitat. Porteu-lo a un centre de servei qualificat quan calgui reparació o reparació. El muntatge incorrecte pot provocar un risc de descàrrega elèctrica o incendi.
  4. Per reduir el risc de descàrrega elèctrica, desconnecteu tots els cables abans d'intentar qualsevol manteniment o neteja. Apagar la unitat no reduirà aquest risc.
  5. PRECAUCIÓ – Només personal qualificat pot instal·lar aquest dispositiu amb una bateria.
  6. MAI carregueu una bateria congelada.
  7. For optimum operation of this inverter/charger, please follow the required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Tingueu molta precaució quan treballeu amb eines metàl·liques sobre o al voltant de les bateries. Existeix un risc potencial de deixar caure una eina per provocar espurnes o curtcircuit a bateries o altres peces elèctriques i podria provocar una explosió.
  9. Please strictly follow the installation procedure when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  10. Es proporciona un fusible com a protecció contra sobrecorrent per a l'alimentació de la bateria.
  11. INSTRUCCIONS DE TERRA - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  12. MAI cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  13. Avís!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Producte acabatview

The ANENJI Hybrid Solar Inverter is designed for efficient power management in solar energy systems. Below are the key components and their functions.

Davant view of the inverter with LCD display and buttons.
Figura 2: Frontal View of the Inverter. Shows the LCD display and function buttons.
Enrere view of the inverter with labeled ports.
Figura 3: posterior View of the Inverter with Labeled Ports.

3.1 Identificació de components

  1. Pantalla LCD
  2. Indicador d'estat
  3. Indicador de càrrega
  4. Indicador d’error
  5. Botons de funció
  6. Interruptor d'encesa/apagada
  7. Battery negative/positive outlet hole
  8. RS485 communication port (RJ45)
  9. Port d'antena WiFi
  10. PV1 input
  11. PV2 input
  12. Entrada de CA
  13. Sortida principal
  14. Posada a terra
  15. Second out
  16. Port de contacte sec

4. Instal·lació

4.1 Desembalatge i inspecció

Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:

  • La unitat x 1
  • Manual d'usuari x 1
  • PV connector x 4
  • Battery fuse x 1 (Only 11K model)
  • Antena WIFI

4.2 Preparació

Before connecting all wirings, take off the bottom cover by removing four screws.

4.3 Muntatge de la unitat

Consider the following points when selecting where to install the inverter:

  • No munteu l'inversor sobre materials de construcció inflamables.
  • Muntar sobre una superfície sòlida.
  • Instal·leu aquest inversor a l'alçada dels ulls per permetre que la pantalla LCD es pugui llegir en tot moment.
  • La temperatura ambient ha d'estar entre 0 °C i 55 °C per garantir un funcionament òptim.
  • La posició d'instal·lació recomanada és adherir-se a la paret verticalment.
  • Ensure enough space around the unit for sufficient heat dissipation and for removing wires.

APTE NOMÉS PER A LA MUNTATGE SOBRE FORMIGÓ O ALTRES SUPERFÍCIES NO COMBUSTIBLES.

4.4 Connexió de la bateria

PRECAUCIÓ:

For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be required to have a disconnect device in some applications, however, it's still required to have over-current protection installed. Refer to the typical amperage in the table below for required fuse or breaker size.

ADVERTIMENT!

All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce the risk of injury, use the proper recommended cable.

Follow these steps to implement battery connection:

  1. Make positive and negative cables based on the recommended terminal size.
  2. Connect all battery packs as units require. It's suggested to use the recommended battery capacity.
  3. Insert the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 10-12Nm. Ensure polarity at both the battery and the inverter/charger is correctly connected and battery cables are tightly screwed to the battery connector.

Recommended Battery Cable & Terminal Size

ModelMàxim AmpedatCapacitat de la bateriaMida del cableCable mm2Terminal Size (mm) LTerminal Size (mm) WTerminal Size (mm) DValor del parell
8.5 KVA180A400 AH4 AWG * 22537228.410~12 Nm
11.0 KVA220A600 AH2 AWG * 23837228.410~12 Nm

ADVERTÈNCIA: Perill de xoc

La instal·lació s'ha de fer amb cura a causa de l'elevat volum de la bateriatage en sèrie.

ATENCIÓ!!

Do not place anything between the flat part of the inverter terminal. Otherwise, overheating may occur. Do not apply anti-oxidant substance on the terminals before terminals are connected tightly. Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 Connexió d'entrada/sortida de CA

ATENCIÓ!!

Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended specification for the AC breaker is 63A. There are two terminal blocks with “IN” and “OUT” markings. Do not mis-connect input and output connectors.

ADVERTIMENT!

All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce the risk of injury, use the proper recommended cable size.

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.
  4. Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect the PE protective conductor (yellow-green) first.

Suggested Cable Requirement for AC Wires

ModelCalibreValor del parell
Tots els models6 AWG1.2 ~ 1.4 Nm

ATENCIÓ: Important

Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in dual output operation. Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

4.6 Connexió fotovoltaica

PRECAUCIÓ:

Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

ADVERTIMENT!

All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce the risk of injury, use the proper recommended cable size.

Follow these steps to implement PV module connection:

  1. Traieu la funda d'aïllament de 10 mm per als conductors positius i negatius.
  2. Comproveu la polaritat correcta del cable de connexió dels mòduls fotovoltaics i dels connectors d'entrada fotovoltaics. A continuació, connecteu el pol positiu (+) del cable de connexió al pol positiu (+) del connector d'entrada PV. Connecteu el pol negatiu (-) del cable de connexió al pol negatiu (-) del connector d'entrada PV.
  3. Assegureu-vos que els cables estiguin ben connectats.

Selecció de mòduls fotovoltaics

A l'hora de seleccionar els mòduls fotovoltaics adequats, cal tenir en compte els paràmetres següents:

  1. El circuit obert Voltage (Voc) dels mòduls fotovoltaics no ha de superar el volum màxim de circuit obert del panell fotovoltaictage de l'inversor.
  2. El circuit obert Voltagl'e (Voc) dels mòduls fotovoltaics ha de ser superior al volum mínim de la bateriatage.

Mode de càrrega solar

MODEL INVERSOR8.5 KVA11.0 KVA
Màx. Circuit obert de matriu fotovoltaica Voltage500VDC
PV Array MPPT Voltage Rang60VDC ~ 500VDC
Màx. CORRENT D'ENTRADA PV27A * 2

Per example, taking 450Wp and 550Wp PV modules, the recommended module configurations are listed in the table below. These configurations are suitable for PV1 or PV2. For instance, if PV1 has 8 pieces in series, PV2 could also have 8 pieces in series, totaling 16 panels.

Solar Input Configurations (450Wp Panel)

Especificacions del panell solar. (referència)ENTRADA SOLARQ'ty of panelsPotència total d'entradaModel inversor
450 Wp
Vmp: 34.67 Vdc
Imp: 13.82A
Voc: 41.25 Vdc
Isc: 12.98A
3 unitats en sèrie3 unitats1,350 WTots els models
4 unitats en sèrie4 unitats1,800 W
5 unitats en sèrie5 unitats2,250 W
6 unitats en sèrie6 unitats2,700 W
7 unitats en sèrie7 unitats3,150 W
8 unitats en sèrie8 unitats3,600 W
9 unitats en sèrie9 unitats4,050 W
10 unitats en sèrie10 unitats4,500 W
11 unitats en sèrie11 unitats4,950 W
12 unitats en sèrie12 unitats5,400 W

Solar Input Configurations (550Wp Panel)

Especificacions del panell solar. (referència)ENTRADA SOLARQ'ty of panelsPotència total d'entradaModel inversor
550 Wp
Vmp: 42.48 Vdc
Imp: 12.95A
Voc: 50.32 Vdc
Isc: 13.70A
3 unitats en sèrie3 unitats1,650 WTots els models
4 unitats en sèrie4 unitats2,200 W
5 unitats en sèrie5 unitats2,750 W
6 unitats en sèrie6 unitats3,300 W
7 unitats en sèrie7 unitats3,850 W
8 unitats en sèrie8 unitats4,400 W
9 unitats en sèrie9 unitats4,950 W

4.7 Assemblea final

After connecting all wirings, put the bottom cover back by screwing the four screws.

4.8 Senyal de contacte sec

A dry contact (3A/250VAC) is available on the rear panel. When program 16 of the F0 group is set as "Model1", it can deliver a signal to an external device when the battery voltage reaches a warning level. When program 16 of F0 is set as "Model2" and the unit is working in battery mode, it can trigger the grounding box to connect neutral and grounding of AC output together.

Dry Contact Port Behavior (Program 16 F0 = Model1)

Estat de la unitatCondicióDry contact port: NC & CDry contact port: NO & C
ApagueuLa unitat està apagada i no s'alimenta cap sortida.TancarObert
EncèsLa sortida s'alimenta des de la utilitat.Obert
Bateria voltage or Soc < Low DC warning voltage or Soc (Program 1 of F1 set as SUB)ObertTancar
Bateria voltage or Soc > setting value program 5 of F2 or battery charging reaches floating stage (Program 1 of F1 set as SBU)TancarObert
Bateria voltage < Setting value program 5 of F2 or battery charging reaches floating stage (Program 1 of F1 set as SBU)ObertTancar

Dry Contact Port Behavior (Program 16 F0 = Model2)

Estat de la unitatCondicióDry contact port: NC & CDry contact port: NO & C
ApagueuLa unitat està apagada i no s'alimenta cap sortida.TancarObert
EncèsUnit works in standby mode, line mode or fault mode.TancarObert
Unit works in battery mode or power saving mode.ObertTancar

5. Funcionament

5.1 Encès/apagat

Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Funcionament i panell de visualització

The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, providing operating status and input/output power information.

Missatges indicadors LED

Indicador LEDColorEstatMissatges
AC/INVVerdEncès sòlidLa sortida és alimentada per la utilitat en mode de línia.
ParpellejantLa sortida s'alimenta amb bateria o fotovoltaica en mode bateria.
CHGVerdEncès sòlidLa bateria està completament carregada.
ParpellejantLa bateria s'està carregant.
FALTAVermellEncès sòlidS'ha produït un error a l'inversor.
ParpellejantEs produeix una condició d'advertència a l'inversor.

Tecles de funció

Tecla de funcióDescripció
ESCPer sortir del mode de configuració
UPPer anar a la selecció anterior
ABAIXPer anar a la següent selecció
ENTRARPer confirmar la selecció en el mode de configuració o entrar en el mode de configuració

5.3 Pantalla LCD

The LCD display provides real-time information about the inverter's operation. Information can be switched by pressing the "UP" or "DOWN" keys.

LCD Display Information Examples

Item1 Area Data3 Area DataPer Example
1Vol d’entradatageVolum de sortidatageEntrada Voltage=220V, sortida voltage=220V (Default Display Screen)
2Freqüència d'entradaFreqüència de sortidaInput frequency=50Hz, Output frequency=50Hz
3Total output active powerTotal output apparent powerActive power=3.02KW, Apparent power=4.0KVA
4output L1 apparent poweroutput L1 active power
5output L2 apparent poweroutput L2 active power
6Potència activa d'entradaPV feedback poweractive power=800w, feedback power=0w
7Bateria voltagePercentatge de càrregatageBateria voltage=50V, Load percentage=80%
8Potència de càrregaCorrent de càrregaTotal charging power=1.8KW, Charging current=36A. Icon AC and PV is light show that AC grid and PV charging battery at the same time
9Potència fotovoltaica totalCorrent de descàrregaPV power=8.6KW, Battery discharge current is 0 A
10Potència PV1Potència PV2PV1 power =4.5kw, PV2 power =4.3kw
11PV1 voltagecorrent PV1PV voltage=360V, PV current=12A
12PV2 voltagecorrent PV2PV voltage=320V, PV current=13A
13DIAGeneration power/dayGeneration power/day=10KWh
14DlGeneration power/monthGeneration power/month=310KWh
15Generation power/yearGeneration power/year=3.6mWh
16TTLTotal generation powerTotal generation power=13.6mWh
17Anymonth, day2024/03/25
18Horasecond, minute16:25:03
19Volum màxim de càrrega de la bateria de lititageCorrent màxim de càrrega de la bateria de litiOnly communication between the inverter and battery is successful, communication successful icon Li will be flashing, there is some information showing on the LCD
20Lithium battery charging status000 001: Indicating that lithium battery charging is prohibited; x1x: Indicating that the lithium battery is prohibited; 1xx: Indicating that the lithium battery requires forced charging
21Lithium battery SOC (%)BATT 099: Lithium battery SOC is 99%
22Software Version part1Software Version Part2, Software Version Part3240 31 201
23Model code Version part1Model code Version Part2, Model code Version Part319 00 60
24Tipus de CPUVersió de maquinari000 Hd 000

5.4 Configuració LCD

To enter the setting groups mode, press and hold the ENTER button for 3 seconds. Use the "UP" or "DOWN" buttons to select setting groups (F0/F1/F2/F3/F4). Press "ENTER" to confirm a selection or "ESC" to exit.

  • F0: Establiment de paràmetres generals
  • F1: Setting AC output parameters
  • F2: Setting battery parameters
  • F3: Setting time parameters
  • F4: Setting systems parameters

Press "ENTER" to confirm the selection groups or "ESC" to return to selection groups or exit. Note: Max[A,B] takes the larger value of A and B, and Min[A,B] takes the smaller value of A and B.

F0 Programs: General Parameters

ProgramaDescripcióSelectable Option
01Entrada d'AC voltage gamma
  • Appliances (default): 90-280VAC
  • UPS: 170-280VAC
  • Generador: 170-280VAC (Note: Generator output may be unstable)
02Activar/desactivar el mode d'estalvi d'energia
  • Saving mode disable (default): Inverter output unaffected by low/high load.
  • Saving mode enable: Output off if connected load is low or not detected.
03Bypass de sobrecàrrega
  • Bypass disable: (per defecte)
  • Bypass enable: Unit transfers to line mode if overload occurs in battery mode.
04Reinici automàtic quan es produeix una sobrecàrrega
  • Reinicia desactivar
  • Habilita reiniciar (per defecte)
05Reinici automàtic quan es produeixi una temperatura excessiva
  • Reinicia desactivar
  • Habilita reiniciar (per defecte)
06Retorn automàtic a la pantalla predeterminada
  • manual (default): If mains power is normal, it will automatically bypass, even if the switch is off.
  • automàtic:
07Retorn automàtic a la pantalla predeterminada
  • Return to default display screen (default): Returns to default display (Input/Output voltage) after 1 min of inactivity.
  • Stay at latest screen: Display stays on the last screen selected by the user.
08Control de llum de fons
  • Il·luminació de fons activada (per defecte)
  • Il·luminació de fons apagada
09Mode de timbre
  • Mode 1: Buzzer mute.
  • Mode 2: Buzzer sounds when input source changes or specific warning/fault.
  • Mode 3: Buzzer sounds when specific warning/fault.
  • Mode4 (default): Buzzer sounds when fault.
10Configuració d'ID de ModbusRange: 001 (default) ~ 247
16Dry contact mode
  • Model1 (default): Delivers signal to external device when battery voltage arriba al nivell d'avís.
  • Model 2: Allows neutral and grounding of AC output to be connected together. This function is available when the inverter is working with an external grounding box. When the inverter is in battery mode, it triggers the grounding box to connect neutral and grounding of AC output.

F1 Programs: AC Output Parameters

ProgramaDescripcióSelectable Option
01Prioritat de la font de sortida
  • SUB priority (default): Solar -> Utility -> Battery. Solar energy charges first, then powers loads. If solar energy is insufficient, utility power supplies loads.
  • SBU priority: Solar -> Battery -> Utility. Solar energy powers loads first. If solar energy is insufficient, battery powers loads. Utility powers loads only when battery voltage drops below warning or setting point.
  • SUF priority: Solar -> Utility -> Battery. If solar energy is sufficient for loads and battery charging, excess feeds to grid. If solar energy is insufficient, utility supplies loads.
02Mode de sortida de CA
  • Solter: This inverter is used in single phase application.
03Volum de sortidatage
  • 230V (default): Available settings: 220V, 230V, 240V.
04Freqüència de sortida
  • 50Hz (default): Available settings: 50Hz, 60Hz.
06Slave output source priority
  • OFF (default): Turn off slave output source priority.
  • SUB priority: Same as Program 01 of F1.
  • SBU priority: Same as Program 01 of F1.
  • SUF priority: Same as Program 01 of F1.
07Start timer setting for slave output source priority - Hours setting00 (default). Range: 00 to 23 of every day.
08Start timer setting for slave output source priority - Minutes setting00 (default). Range: 00 to 59 of every hour.
09End timer setting for slave output source priority - Hours setting00 (default). Range: 00 to 23 of every day.
10End timer setting for slave output source priority - Minutes setting00 (default). Range: 00 to 59 of every hour.
11Second output (OP2) control
  • Enable (default): Second output (OP2) is allowed.
  • Desactivar: Second output (OP2) is forbidden.
12Setting the second output (OP2) overload warning pointSet the OP2 overload warning point. If the set value is exceeded, a 3D warning will be displayed. Setting range is from 10% to 100% and the default setting is 50%.
13Setting the timer to turn on second output (OP2) - Hours setting00 (default). Setting range is from 00 to 23. If set to 00-23, OP2 is always on.
14Setting the timer to turn off second output (OP2) - Hours setting23 (default). Setting range is from 00 to 23. If set to 07-13, OP2 is on from 7:00 to 13:00. During this period, OP2 will be turned off if battery voltage reaches the setting value in program 08 of F2.

F2 Programs: Battery Parameters

ProgramaDescripcióSelectable Option
01Tipus de bateria
  • AGM (per defecte)
  • Inundat
  • Usuari definit: Volum de càrrega de la bateriatage i baix volum de tall de CCtage can be set in program 03/04/08 of F2.
  • PYLON US2000 Protocol (3.5 Version)
  • Standard communication Protocol 2 from inverter supplier.
  • LIB: Battery default value fits lithium battery without communication. Charge voltage i baix volum de tall de CCtage can be set in program 03/04/08 of F2.
02Prioritat de la font del carregador
  • Solar first: Solar charges battery as priority. Utility charges only when solar is unavailable.
  • Solar and Utility (default): Solar and utility charge battery at the same time.
  • Només solar: Solar is the only charger source.
  • Solar residual: Solar supports all connected loads as priority, residual energy charges battery.
03Volum de càrrega a graneltage (CV voltage)If User-Defined or LIB is selected in program 01 of F2, this program can be set up. Default: 56.4V. Range: Program 04 of F2 to 62V (for non-LIB) or Program 04 of F2 to 58V (for LIB).
04Vol de càrrega flotanttageIf User-Defined or LIB is selected in program 01 of F2, this program can be set up. Default: 54.0V. Range: 48.0V to Program 03 of F2.
05Voltage or Soc point back to utility source when selecting "SBU priority"
  • Lithium battery without communication: Default: 46.0V. Range: Max[44V, 07 of F2 +0.1V]~Min[06 of F2-0.1V,57.2V].
  • Lithium battery with communication: Default: 52.0V. Range: Max[44V, 07 of F2 +0.1V]~Min[06 of F2-0.1V,57.2V].
  • Default: 50%: Range: Program 07 of F2 +1% to 50%.
06Voltage point back to battery mode when selecting "SBU priority" in program 01(F1)
  • Bateria completament carregada (per defecte)
  • Lithium battery with communication: Default: 95%. Range: 60% to 100%.
07Setting cut off voltage punt o SOC percenttage on the Main output (OP1)
  • Lithium battery without communication: Default: 44.0V. Range: Program 08 of F2 to Min[05 of F2-0.1V, 54V].
  • Lithium battery with communication: Default: 51.9V. Range: Program 08 of F2 to Min[05 of F2-0.1V, 54V].
  • Default: 22%: Range: Program 08 of F2 to Min[05 of F2 - 1%,30%].
08Setting cut off voltage punt o SOC percenttage on the second output (OP2)
  • Lithium battery without communication: Default: 42.0V. Range: 40V~Min[07 of F2,54V].
  • Lithium battery with communication: Default: 50.0V. Range: 40V~Min[07 of F2,54V].
  • Default: 20%: Range: 3% to Program 07 of F2.
09Corrent de càrrega màxima: per configurar el corrent de càrrega total per als carregadors solars i de serveis públics.
  • Model de 8.5 kW: 10-140A (not less than AC charging current).
  • Model de 11.0 kW: 10-160A (not less than AC charging current).
10Corrent màxima de càrrega del servei públicRange: 5-120A (max setting must be less than Program 09 of F2).
16Temps de càrrega massiva (CV s)tage)
  • Automàticament (per defecte): Inverter judges charging time automatically.
  • 5 min: Range: 5 min to 900 min (increment 5 min).
17Equalització de la bateriaIf User-Defined or LIB is selected in program 01 of F2, this program can be set up.
  • Battery equalization (default)
  • Equalització de la bateria desactivada
18Equalització de la bateria voltageIf Flooded or User-Defined is selected in program 01 of F2, this program can be set up. Default: 58.4V. Range: Floating voltage (Program 04 of F2) ~ 62V.
19Temps igualat de bateria60min (default). Range: 0min to 900min (increment 5min).
20Temps d'espera de la bateria igualada120min (default). Range: 0min to 900min (increment 5min).
21Interval d'equalització30days (default). Range: 1 to 90 days (increment 1 day).
22L'equiparació s'ha activat immediatament
  • Activa: Activates battery equalization immediately.
  • Disable (default): Cancels equalization function until next activated equalization time.
23Manual activate the lithium battery settingIf User-Defined, LIB, or LIx is selected as lithium battery in program 01 of F2, and the battery is not detected, selecting 'Active' will activate the lithium battery.
24Automatic activation for lithium batteryIf LIx is selected as lithium battery in program 01 of F2, and the battery is not detected, the unit or PV will activate the lithium battery automatically. Restart the unit to activate automatically.
25Max battery discharge current settingWhen battery discharge current exceeds setting, unit stops discharging and goes to bypass or standby mode. Range: 50 to 500.
26Temps d'activació de la bateria de litiIf lithium battery activation is available, activation time can be set. Range: 6s~300s (default 6s).

F3 Programs: Time Parameters

ProgramaDescripcióSelectable Option
01Time setting - YearInterval: 00 a 99.
02Time setting - MonthInterval: 1 a 12.
03Time setting - DayInterval: 1 a 31.
04Time setting - HourInterval: 0 a 23.
05Time setting - MinuteInterval: 0 a 59.
06Time setting - SecondInterval: 0 a 59.

F4 Programs: System Parameters

ProgramaDescripcióSelectable Option
01Reset all stored data of PV generated power and output load energy
  • Reserve data (default)
  • Reset generated energy data

5.5 Indicador d'avís

There are seven groups of warning codes. A warning code consists of a group code and a number (e.g., 0B). The group code is first, and the number is last.

  • A: Inverter group fault code
  • B: Battery group fault code
  • C: PV group fault code
  • D: Output group fault code
  • E: Parallel group fault code
  • F: Other group fault code
  • G: Grid group fault code

Taula de codis d'advertència

Codi d'avísEsdeveniment d'avísAlarma sonoraIcona parpellejant
0BBateria baixaBeep un cop cada segon
1BLa bateria no està connectadaCap
2BEqualització de la bateriaCap
3BBattery low and it isn't up to the setting value of program 06 of F2 groupPiteu dos cops cada 3 segons
4BLa comunicació de la bateria de liti és anormalBeep un cop cada 0.5 segons
5BBattery discharge overcurrentCap
1CPV energy is too weakPiteu dos cops cada 3 segons
0DSobrecàrregaBeep un cop cada 0.5 segons
1DReducció de la potència de sortidaPiteu dos cops cada 3 segons
3DThe load exceeds the set value of program 12 of F1Cap
0FLa temperatura és massa altaPica tres vegades cada segon

6. Battery Equalization

The equalization function is added to the charge controller to reverse the buildup of negative chemical effects like stratification, where acid concentration is greater at the bottom of the battery. Equalization also helps remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.

6.1 How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 17 of F2 first. Then, you can apply this function by either of the following methods:

  1. Setting the equalization interval in program 21 of F2.
  2. Active equalization immediately in program 22 of F2.

6.2 Quan igualar

A la carrossa stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is activated immediately, the controller will start to enter the Equalize stage.

6.3 Equalize Charging Time and Timeout

A l'Equalize stage, el controlador subministrarà energia per carregar la bateria tant com sigui possible fins que la bateria voltage puja fins al volum d'equalització de la bateriatage. Aleshores, constant-voltagS'aplica la regulació per mantenir el volum de la bateriatage a l'equalització de la bateria voltage. La bateria romandrà a l'Equalize stage until the setting battery equalized time is reached.

However, if in the Equalize stage, the battery equalized time expires and the battery voltage no puja fins al volum d'equalització de la bateriatagpunt e, el controlador de càrrega allargarà el temps d'equalització de la bateria fins que el volum de la bateriatage aconsegueix el volum d'equalització de la bateriatage. Si la bateria voltage encara és inferior al vol d'equalització de la bateriatage quan s'hagi acabat el temps d'espera d'equalització de la bateria, el controlador de càrrega aturarà l'equalització i tornarà a la posició flotant.tage.

7. Setting for Lithium Battery

7.1 Connexió de la bateria de liti

If you choose a lithium battery for the inverter, you are allowed to use only lithium batteries that have been configured. There are two connectors on the lithium battery: the RS485 port of the BMS and the power cable.

Follow these steps to implement lithium battery connection:

  1. Assemble the battery terminal based on the recommended battery cable and terminal size (same as Lead acid, see the Lead-acid Battery connection section for details).
  2. Connect the end of the RS485 port of the battery to the BMS (RS485) communication port of the inverter.

7.2 Lithium Battery Communication and Setting

If choosing a lithium battery, ensure the BMS communication cable is connected between the battery and the inverter. This cable delivers information and signals between the lithium battery and the inverter, including:

  • Re-configuring charging voltage, charging current, and battery discharge cut-off voltage segons els paràmetres de la bateria de liti.
  • Having the inverter start or stop charging according to the status of the lithium battery.

Connecteu l'extrem RS485 de la bateria al port de comunicació RS485 de l'inversor

Make sure the lithium battery RS485 port connects to the inverter is Pin to Pin. The communication cable is inside the package, and the inverter RS485 port pin assignment is shown below:

Número de pinPort RS485
PIN1RS485-B
PIN2RS485-A
PIN7RS485-A
PIN8RS485-B

7.3 Setting for PYLON US2000 Lithium Battery

1. PYLONTECH US2000 lithium battery setting:

Dip Switch: There are 4 Dip Switches that set different baud rate and battery group address. If the switch position is turned to the "OFF" position, it means "0". If the switch position is turned to the "ON" position, it means "1".

  • Dip 1 is "ON" to represent the baud rate 9600.
  • Els dip 2, 3 i 4 estan reservats per a l'adreça del grup de bateries.
  • Dip switch 2, 3 and 4 on the master battery (first battery) are used to set up or change the group address.

NOTE: "1" is the upper position and "0" is the bottom position.

2. Process of install:

  1. Use the RS485 cable to connect the inverter and Lithium battery.
  2. Switch on the Lithium battery.
  3. Press for more than three seconds to start the Lithium battery; power output is ready.
  4. Enceneu l'inversor.
  5. Be sure to select battery type as “Li2” in LCD program 5. If communication between the inverter and battery is successful, the battery icon will light up on the LCD display.

7.4 Setting for Lithium Battery Without Communication

This suggestion is used for lithium battery applications and to avoid lithium battery BMS protection without communication. Please finish the setting as follows:

A. Recommended method 1: Set battery type as "LIB" in program 01 of F2.

B. Recommended method 2: Setting as follows:

  1. Before starting setting, you must get the battery BMS specification: Max charging voltage, Max charging current, Discharging protection voltage.
  2. Set battery type as "LIB" in program 01 of F2.
  3. Set CV voltage com Volum de càrrega màximatage of BMS-0.5V in program 03 of F2.
  4. Estableix el volum de càrrega flotanttage com CV voltage in program 03 of F2.
  5. Estableix el volum de tall de CC baixtage ≥ discharging protection voltage de BMS+3V.
  6. Set Max charging current in program 09 of F2 which must be less than the Max charging current of BMS.
  7. Set voltage point back to utility source when selecting "SBU priority" in program 05 of F2.

The setting value must be ≥ Low DC cut-off voltage + 2V, or else the inverter will have a warning as battery voltage baix.

Observació:

  1. You'd better to finish setting without turning on the inverter (just let the LCD show, no output).
  2. When you finish setting, please restart the inverter.

8. Especificacions

The ANENJI 11KW 48V Hybrid Solar Inverter offers robust performance and features. Detailed specifications are provided in the tables below.

Detailed product parameters table for the ANENJI 11KW 48V Hybrid Solar Inverter.
Figure 4: Detailed Product Parameters Table.

8.1 Taula 1 Especificacions del mode de línia

MODEL INVERSOR8.5 KVA11.0 KVA
Entrada Voltage Forma d'onaSinusoïdal (utilitat o generador)
Volum d’entrada nominaltage230Vac
Baixa pèrdua voltage170Vac±7V (UPS); 90Vac±7V (electrodomèstics)
Retorn de pèrdua baixa Voltage180Vac±7V (UPS); 100Vac±7V (electrodomèstics)
High Loss Voltage280Vac±7V
Retorn de pèrdua alta voltage270Vac±7V
Volum màxim d'entrada de CAtage300Vac
Freqüència nominal d'entrada50 Hz / 60 Hz (detecció automàtica)
Baixa freqüència de pèrdua40 ± 1 Hz
Freqüència de retorn de baixa pèrdua42 ± 1 Hz
Alta freqüència de pèrdua65 ± 1 Hz
Freqüència de retorn d'alta pèrdua63 ± 1 Hz
Protecció contra curtcircuits de sortidaMode de bateria: Circuits electrònics
Eficiència (mode de línia)>95% (càrrega nominal R, bateria completament carregada)
Temps de transferència10 ms típic (UPS); 20 ms típic (electrodomèstics)

8.2 Taula 2 Especificacions del mode inversor

MODEL INVERSOR8.5 KVA11.0 KVA
Potència de sortida nominal8.5KVA/8.5KW11.0KVA/11.0KW
Dual output function
Max.main output power8.5KVA/8.5KW11.0KVA/11.0KW
Max.second output power5.0KVA/5.0KW5.5KVA/5.5KW
Vol. De sortidatage Forma d'onaOnda senyal pura
Vol. De sortidatage Reglament230Vac ± 5%
Freqüència de sortida60 Hz o 50 Hz
Màxima eficiència94%
Protecció de sobrecàrrega5.5s @ ≥140% de càrrega; 10.5 s @ 100% ~ 140% de càrrega
Capacitat de sobretensióPotència nominal 2 * durant 5 segons
Volum d’entrada nominal CCtage48Vdc
Cold Start Voltage46.0Vdc
Vol. d'avís de CC baixtage (Just for AGM and Flooded)@càrrega < 20%44.0Vdc
@20% ≤ càrrega <50%42.8Vdc
@càrrega ≥ 50%40.4Vdc
Vol. de retorn d'avís de CC baixtage (Just for AGM and Flooded)@càrrega < 20%46.0Vdc
@20% ≤ càrrega <50%44.8Vdc
@càrrega ≥ 50%42.4Vdc
Vol de tall de CC baixtage (Just for AGM and Flooded)@càrrega < 20%42.0Vdc
@20% ≤ càrrega <50%40.8Vdc
@càrrega ≥ 50%38.4Vdc

8.3 Taula 3 Especificacions del mode de càrrega

Mode de càrrega d'utilitat
MODEL INVERSOR8.5 KVA11.0 KVA
Charging Current (Max) (AC+PV)140Amp160Amp
Corrent de càrrega de CA (màx.)120Amp (@VI/P=230Vac)
Vol. de càrrega a graneltageBateria inundada58.4Vdc
AGM / bateria de gel56.4Vdc
Càrrega flotant Voltage54Vdc
Protecció de sobrecàrrega63Vdc
Algoritme de càrrega3-Pas
Entrada solar
MODEL INVERSOR8.5 KVA11.0 KVA
Potència nominal5000 W * 25500 W * 2
Màx. Circuit obert de matriu fotovoltaica Voltage500Vdc
PV Array MPPT Voltage Rang60Vdc~500Vdc
Max. MPPT Charge Current140A160A
Màx. Corrent d'entrada27A * 227A * 2

8.4 Taula 4 Especificacions generals

MODEL INVERSOR8.5 KVA11.0 KVA
Certificació de seguretatCE
Interval de temperatura de funcionament-10 °C a 55 °C
Temperatura d'emmagatzematge-15°C~60°C
Humitat5% a 95% d'humitat relativa (sense condensació)
Dimensió (P*A*A), mm540x403x122
Pes net, kg14.414.8

9. Solució De Problemes

This section provides a guide to common issues and their solutions. If problems persist, contact customer support.

9.1 Codi de referència d'error

There are seven groups of fault codes, each consisting of a group code and a number (e.g., A0). The group code is first, and the number is last.

  • A: Inverter group fault code
  • B: Battery group fault code
  • C: PV group fault code
  • D: Output group fault code
  • E: Parallel group fault code
  • F: Other group fault code
  • G: Grid group fault code

Taula de codis d'error

Codi d'errorEsdeveniment de fallaIcona activada
A0Sortida curtcircuitat.ERROR
A1Volum de sortidatage és massa alta.ERROR
A2Sobreintensitat o sobretensióERROR
A3Sobre DC voltage en sortida de CAERROR
A4La compensació de corrent de l'inversor és massa altaERROR
A5Volum de sortidatage és massa baixaERROR
A6Potència negativa del inversorERROR
B0Bateria voltage és massa altaERROR
B1Sobreintensitat DCDCERROR
B2La compensació de corrent DC/DC és massa altaERROR
C0Sobreintensitat fotovoltaicaERROR
C1PV sobre voltageERROR
C2PV1 current offset is too highERROR
C3PV2 current offset is too highERROR
D0Temps d'espera de sobrecàrregaERROR
D1La compensació del corrent operatiu és massa altaERROR
D2Op2 current offset is too highERROR
F0Sobretemperatura del mòdul inversorERROR
F1Sobretemperatura del mòdul fotovoltaicERROR
F2Sobretemperatura del mòdul DCDCERROR
F3Bus voltage és massa altaERROR
F4L'arrencada suau de l'autobús ha fallatERROR
F5Bus voltage és massa baixaERROR
F6Hardware incompatibilityERROR

9.2 General Troubleshooting Table

ProblemaLCD/LED/BuzzerExplicació / Possible causaQuè fer
La unitat s'apaga automàticament durant el procés d'inici.Els LCD/LEDs i el timbre estaran actius durant 3 segons i després s'apagaran.La bateria voltage és massa baixa.1. Torneu a carregar la bateria.
2. Substituïu la bateria.
Sense resposta després de l'encesa.Cap indicació.1. La bateria voltage és massa baixa.
2. La polaritat de la bateria està connectada invertida.
1. Comproveu si les bateries i el cablejat estan ben connectats.
2. Torneu a carregar la bateria.
3. Substituïu la bateria.
Vol d’entradatage es mostra com a 0 a la pantalla LCD i el LED verd parpelleja.El protector d'entrada està activat.Comproveu si l'interruptor de CA s'ha activat i el cablejat de CA està ben connectat.
Hi ha xarxa elèctrica, però la unitat funciona en mode bateria.El LED verd parpelleja.Qualitat insuficient de l'alimentació CA. (Riba o generador)1. Comproveu si els cables de CA són massa prims i/o massa llargs.
2. Comproveu si el generador (si s'aplica) funciona bé o si el volum d'entradatagLa configuració del rang és correcta. (Dispositiu UPS)
El LED verd parpelleja.Set "SBU" or "SUB" as the priority of output source.Primer canvieu la prioritat de la font de sortida a Utilitat.
Quan la unitat està engegada, el relé intern s'encén i s'apaga repetidament.La pantalla LCD i els LED parpellegen.La bateria està desconnectada.Comproveu si els cables de la bateria estan ben connectats.
Fault code D0Error de sobrecàrrega. L'inversor està sobrecarregat un 100% i el temps s'ha acabat.Reduïu la càrrega connectada apagant alguns equips.
Fault code A2Sortida curtcircuitat.Comproveu si el cablejat està ben connectat i elimineu la càrrega anormal.
Codi d'error F2La temperatura interna del component inversor és superior a 100 °C.Comproveu si el flux d'aire de la unitat està bloquejat o si la temperatura ambient és massa alta.
El timbre sona contínuament i el LED vermell està encès.Fault code B0La bateria està sobrecarregada.Tornar al centre de reparació.
La bateria voltage és massa alta.Check if spec and quantity of batteries are met requirements.
Fault code A1/A5Sortida anormal (inversor voltage inferior a 190Vac o superior a 260Vac)1. Reduïu la càrrega connectada.
2. Retornar al centre de reparació.
Fault code F3/F4Els components interns han fallat.Tornar al centre de reparació.
Fault code A2Sobreintensitat o sobretensió.Reinicieu la unitat, si l'error torna a passar, torneu al centre de reparació.
Codi d'error F5Bus voltage és massa baixa.
Fault code A3Volum de sortidatage està desequilibrada.
Un altre codi d'errorIf the wires are connected well, please return to repair center.

10. Wi-Fi Plug Pro Quick Installation Guideline

10.1 Remove and Install the Wireless Antenna

Consulteu el producteview diagram for the location of the WiFi antenna port. Install the provided WiFi antenna into this port.

10.2 Descarrega l'APP

  1. Scan the QR code below to download the SmartESS APP (available on iPhone App Store and Android).
  2. Open the APP, click the "Registration" button, and select "Mobile phone Registration" or "Email Registration".
  3. Activeu el Bluetooth o el WiFi segons calgui.
QR code for SmartESS App download.
Figure 5: SmartESS App Download QR Code.

10.3 Bluetooth Connection to the Digital Collector

  1. Click the "Toolbox" in the app and select "BLE network" or "Wi-Fi network" as required.
  2. If you choose the Bluetooth distribution network, the app will automatically scan for nearby devices on the "Bluetooth Pairing" page. Find the PN corresponding to the digital collector and click "Connect".
SmartESS app screenshot showing device status.
Figure 6: SmartESS App Device Status.
SmartESS app screenshot showing WiFi pairing process.
Figure 7: SmartESS App WiFi Pairing Process.

10.4 Afegeix Datalogger

  1. Log in to your account and click the Datalogger button. Tap the "+" button on the top-right corner of the datalogger page.
  2. According to the prompts, type in the information to finish adding the datalogger. The PN number is located next to the machine appliance label. (Initial Password: 12345678)

10.5 Networking Settings

Select the corresponding 2.4G WiFi according to the prompts, fill in the password, and click "Start Connecting to the Network". Follow the prompts on the WiFi distribution network reference APP page.

11. Consells d'usuari

  • For optimal performance, ensure all cable connections are secure and meet the recommended gauge specifications. Loose connections can lead to efficiency loss or safety hazards.
  • When configuring battery settings, especially for lithium batteries, double-check the voltage and current parameters to match your battery's specifications to prevent damage and ensure longevity.
  • Regularly monitor the inverter's status via the LCD display or the SmartESS app to catch any warnings or faults early. This proactive approach can prevent minor issues from escalating.
  • If using the parallel function, ensure that the solar panel configuration (number of panels in series) is identical for each side to maintain balanced input.
  • In environments with high dust or humidity, utilize the removable dust cover to protect internal components and prolong the inverter's lifespan.

12. Garantia i Suport

This product comes with a 1-year warranty. For technical support, troubleshooting assistance beyond this manual, or warranty claims, please contact your local dealer or the ANENJI service center. Ensure you have your product model and serial number ready when contacting support.

For offline after-sales service, you may contact via WhatsApp: +86 18373137352.

Please refer to the official ANENJI website or your purchase documentation for the most up-to-date warranty terms and conditions.

Documents relacionats - ANJ-HHS-11KW-48V-WIFI/ANJ-11KW-48V-WIFI-P

Preview Catàleg de productes d'inversors solars, controladors de càrrega i bateries ANENJI
Exploreu la gamma ANENJI d'inversors solars d'alta eficiència, controladors de càrrega solar MPPT i bateries LiFePO4. Descobriu especificacions, característiques i aplicacions detallades per a ús residencial i automobilístic.
Preview Manual d'usuari de l'inversor/carregador solar híbrid ANENJI 11KVA 230Vac
Aquest manual d'usuari proporciona instruccions completes per a l'inversor/carregador solar híbrid ANENJI, model 11KVA 230Vac. Cobreix la instal·lació, el funcionament, les especificacions i la resolució de problemes per a una gestió eficient de l'energia solar.
Preview User Manual: Hybrid Solar Inverter/Charger
Comprehensive user manual for the Hybrid Solar Inverter/Charger, covering installation, operation, specifications, and troubleshooting.
Preview Especificacions tècniques de l'inversor híbrid fora de xarxa ANENJI ANJ-2000W-12V-WiFi
Especificacions tècniques detallades de l'inversor híbrid fora de xarxa ANENJI ANJ-2000W-12V-WiFi, incloent-hi característiques, paràmetres d'entrada/sortida, especificacions de la bateria i dades ambientals.