GEYA GRL8 Liquid Level Control Relay Instruction Manual

Models: GRL8-01, GRL8-02

1. Introducció

The GEYA GRL8 series liquid level control relays are designed for precise monitoring and control of liquid levels in various applications. These devices are ideal for managing water levels in wells, basins, reservoirs, and tanks, ensuring efficient operation of pumps for filling or emptying. The GRL8 series offers robust performance with flexible configuration options to suit diverse industrial and domestic needs.

2. Característiques clau

  • Model GRL8-01: Provides 2-level control mode.
  • Model GRL8-02: Offers 2 or 1 level control mode, providing greater flexibility.
  • Selecció de la funció: User-selectable PUMP UP (filling) or PUMP DOWN (emptying) functions.
  • Retard de temps ajustable: Output time delay adjustable from 0.1 to 10 seconds.
  • Sensibilitat ajustable: Sensitivity (input resistance) can be adjusted via a potentiometer from 5 kΩ to 100 kΩ.
  • Wide Supply Voltage: Galvanically separated supply voltage AC/DC 24-240V.
  • Contacte de sortida: 1 SPDT (Single Pole Double Throw) output with a rating of 10A/AC1.
  • Indicació d'estat: Relay status is clearly indicated by an LED.
  • Muntatge: Compact 1-MODULE design for DIN rail mounting.

3. Especificacions tècniques

Refer to the table below for detailed technical parameters of the GRL8 series relays:

Technical Parameters Table for GEYA GRL8-01 and GRL8-02 Liquid Level Control Relays

Image: Technical Parameters for GRL8-01 and GRL8-02 models.

Paràmetre GRL8-01 (2 level control mode) GRL8-02 (2 or 1 level control mode)
Funció2 level control mode2 or 1 level control mode
Terminals de subministramentA1-A2A1-A2
Voltage gammaAC/DC 24-240V (50-60Hz)AC/DC 24-240V (50-60Hz)
Entradamàx. 2VAmàx. 2VA
Subministrament voltage tolerància-15%; +10%-15%; +10%
Sensitivity (input resistance)adjustable in range 5 kΩ - 100 kΩadjustable in range 5 kΩ - 100 kΩ
Voltage in electrodesmax. AC 5Vmax. AC 5V
Current in probeAC < 0.1 mAAC < 0.1 mA
Temps de respostamàx. 400 msmàx. 400 ms
Max. capacity length800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)800 m (sensitivity 25kΩ), 200 m (sensitivity 100 kΩ)
Max. capacity of probe cable400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)400 nF (sensitivity 25kΩ), 100 nF (sensitivity 100 kΩ)
Time delay (t)adjustable, 0.1 - 10 sadjustable, 0.1 - 10 s
Accuracy in setting (mechanical)± 10%± 10%
Coeficient de temperatura0.05%/°C, at +20°C (0.05°F, at =68°F)0.05%/°C, at +20°C (0.05°F, at =68°F)
Indicació de sortidaLED vermellLED vermell
Vida mecànica1×10⁷1×10⁷
Electrical life (AC1)1×10⁵1×10⁵
Restableix el tempsmax. 200msmax. 200ms
Temperatura de funcionament-20 °C a +55 °C (-4 °F a 131 °F)-20 °C a +55 °C (-4 °F a 131 °F)
Temperatura d'emmagatzematge-35 °C a +75 °C (-22 °F a 158 °F)-35 °C a +75 °C (-22 °F a 158 °F)
Muntatge/rail DINCarril DIN EN/IEC 60715Carril DIN EN/IEC 60715
Grau de proteccióIP40 per panell frontal/terminals IP20IP40 per panell frontal/terminals IP20
Posició operativaqualsevolqualsevol
Overvoltage categoriaIII.III.
Grau de contaminació22
Max. cable size(mm²)solid wire max. 1×2.5 or 2×1.5/ with sleeve max. 1×2.5 (AWG 12)solid wire max. 1×2.5 or 2×1.5/ with sleeve max. 1×2.5 (AWG 12)
Dimensions90×18×64 mm90×18×64 mm

Nota: les especificacions estan subjectes a canvis sense previ avís.

Dimensions

GEYA GRL8 Relay Dimensions Diagram

Image: Physical dimensions of the GRL8 series relay in millimeters.

4. Producte acabatview

The GRL8 series relays are designed for easy integration into control panels. Below are diagrams illustrating the main components and their functions.

GRL8-01 Function Diagram

GRL8-01 Function Diagram with labeled components

Image: Labeled components for GRL8-01, including Supply Voltage Terminals (A1, A2), Max/Min Level Sensor connections, Supply Indication (GREEN), Relay Status Indication (RED), Sensitivity Setting, Model No., Level Monitoring Circuit Terminal (C, 11, 12, 14), and Output Contact.

GRL8-02 Function Diagram

GRL8-02 Function Diagram with labeled components

Image: Labeled components for GRL8-02, similar to GRL8-01 but also showing the PUMP UP or DOWN function selector.

5. Instal·lació i cablejat

The GRL8 relays are designed for DIN rail mounting. Ensure all power is disconnected before installation and wiring. Follow local electrical codes and safety regulations.

Esquema de cablejat

Comprehensive Wiring Diagram, Panel Diagram, and Functions Diagram for GRL8 relays

Image: Detailed wiring diagram showing connections for power supply (Un), level sensors (Max, Min, C), and output contacts (11, 12, 14). Also includes panel layout and function diagrams.

Connexions del sensor:

  • Connecteu el Common Probe (C) to the lowest point of liquid detection.
  • Connecteu el Min Level Probe (Min) for the minimum liquid level.
  • Connecteu el Max Level Probe (Max) for the maximum liquid level.
  • Ensure probes are securely installed and insulated from each other, except through the liquid.

Connexions de sortida:

  • The relay has a 1SPDT output. Terminals 11, 12, and 14 are available.
  • Terminal 11 is the Common contact.
  • Terminal 12 is Normally Closed (NC).
  • Terminal 14 is Normally Open (NO).
  • Connect your pump or control device to the appropriate contacts (e.g., 11 and 14 for pump activation when liquid level changes).

6. Funcionament

The GRL8 series relays can be configured for two primary operation modes: PUMP UP (filling) and PUMP DOWN (emptying).

Operation Modes Explained

  • PUMP UP (Filling Mode): The pump activates when the liquid level drops below the 'Min' probe and deactivates when it reaches the 'Max' probe. This mode is used to fill a tank.
  • PUMP DOWN (Emptying Mode): The pump activates when the liquid level reaches the 'Max' probe and deactivates when it drops below the 'Min' probe. This mode is used to empty a tank.

Ajustaments:

  • Sensibilitat: Use the 'Sensitivity' potentiometer to adjust the input resistance (5-100K) based on the conductivity of the liquid and the length of the sensor cables.
  • Time Delay (Tt): Use the 'Tt' potentiometer to set a time delay (0.1-10s) for the output. This prevents rapid switching due to minor liquid fluctuations.

Demostració visual

Video: Demonstration of the GRL8 relay controlling liquid levels for both pump down and pump up scenarios.

7. Consells d'usuari

  • Sensor Cable Extension: Sensors can typically be extended. Users have reported successful extensions up to 10 meters using standard twisted pair cables. For longer distances or specific environments, consult the technical specifications for maximum capacity length and probe cable capacity.
  • Direct Pump Connection: For pumps up to 2kW (10A at 220V), direct connection to the relay's output contacts (11/12 or 11/14) is generally possible without an additional contactor. Always verify the pump's power requirements against the relay's maximum contact load.
  • Muntatge del sensor: Sensors can be simply suspended at the desired maximum, minimum, and common liquid levels within the tank or container. Ensure they are stable and do not move freely.
  • Normal Operation Sound: It is normal to hear a faint clicking sound from the relay when it switches on or off, indicating proper operation of the internal mechanism.
  • Filling vs. Draining: When setting up, ensure you correctly select the 'PUMP UP' (filling) or 'PUMP DOWN' (draining) mode based on your application to prevent unintended pump behavior.

8. Solució De Problemes

  • Relé no activat:
    • Check power supply to terminals A1 and A2.
    • Verify sensor connections to Max, Min, and C terminals.
    • Ensure liquid level is within the detection range of the probes.
    • Adjust 'Sensitivity' potentiometer, especially for liquids with low conductivity or long sensor cables.
    • Check the 'Time Delay (Tt)' setting; a long delay might cause perceived non-activation.
  • Pump Not Responding to Relay:
    • Confirm correct wiring of the pump to the output contacts (11, 12, 14).
    • Mesura voltage at the output contacts (e.g., between 11 and 14 when activated) to ensure the relay is providing power. If voltage is low (e.g., 0-0.3V), there might be an internal fault or incorrect wiring.
    • Ensure the pump's power rating does not exceed the relay's 10A/AC1 contact rating. For higher power pumps, an external contactor is required.
  • Operació erràtica:
    • Check for loose sensor connections or damaged sensor cables.
    • Ensure probes are clean and free from deposits that might affect conductivity.
    • Adjust sensitivity to match liquid properties.
    • Increase time delay if rapid liquid fluctuations are causing frequent switching.

9. Manteniment

  • Neteja del sensor: Periodically inspect and clean the liquid level sensors, especially in environments prone to mineral deposits, sludge, or other contaminants (e.g., septic tanks). Buildup on the probes can interfere with accurate level detection.
  • Comprovacions de connexió: Regularly check all electrical connections for tightness and signs of corrosion or damage.
  • Condicions ambientals: Ensure the relay is operating within its specified temperature and protection degree (IP40 for front panel/IP20 terminals) to prolong its lifespan.

10. Garantia i Suport

GEYA products are manufactured to high-quality standards. For any technical assistance, warranty claims, or support inquiries, please contact your authorized GEYA distributor or the GEYA Official Store. Please have your product model number and purchase details ready when contacting support.

© 2024 GEYA. All rights reserved.

Documents relacionats - GRL8

Preview Catàleg de productes de control industrial GEVA: relés i protectors
Exploreu la gamma completa de productes de control industrial GEVA, incloent-hi relés temporitzats, vol.tagRelés electrònics, relés de monitorització de corrent, protectors i accessoris essencials. Aquest catàleg proporciona especificacions, funcions i aplicacions detallades per millorar la seguretat elèctrica i l'automatització.
Preview GEYA GRL8 Level Control Relay Instruction Manual
Instruction manual for the GEYA GRL8 series level control relays (GRL8-01, GRL8-02). Provides technical specifications, application details, function configurations, wiring diagrams, and operational guidance for monitoring fluid levels in tanks, reservoirs, and wells.
Preview GEYA GRL8 Level Control Relay Instruction Manual
Detailed instruction manual for the GEYA GRL8 series level control relay, covering technical specifications, functions, wiring diagrams, and operational modes for GRL8-01 and GRL8-02 models.
Preview GEYA Industrial Control Products Catalog - Relays and Protectors
Comprehensive catalog of GEYA industrial control products, featuring a wide range of relays, voltage protectors, current monitors, and accessories. Detailed specifications, applications, and technical data for electrical safety and automation.
Preview GEYA Low Voltage Electrical Products Catalog | Industrial Control Integration
Comprehensive catalog of GEYA low voltage electrical appliances and automation control products, including circuit breakers, relays, contactors, timers, and more. Featuring industrial control integration solutions.