El AKO-D14918 programming key allows you to quickly and easily copy configured settings from one controller to another with the same functionality

Avisos

-Using the equipment without following the manufacturer’s instructions may affect the device’s safety requirements.
-The unit must be used in a location protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed that shown in the technical data.
-Connecting this key to unsupported devices (see table) can cause serious damage to both pieces of equipment.
-In equipment with active communication, log out of communications software or disconnect the cable before connecting the programming key. The communication controller’s address must be 1.

Descripció

AKO D14918 Programming Key - 1

  1. LED COM
  2. CLAU DE REGISTRE
  3. EXTERNAL POWER CONNECTOR
  4. READ KEY
  5. LED encès
  6. CONNECTOR CABLE
Compatibilitat

Refer to the instruction manual of your equipment on its compatibility with the AKO-D14918 programming key.

AKO - Avís Connecting incompatible devices can permanently damage the key.

Cablejat

AKO D14918 Programming Key - 2

  1. IMPORTANT: Pay attention to the orientation of the connector.
  2. AKO-80018 
    (Opcional)
  3. AKO-D14918
Font d'alimentació

-If the controller is in operation (on-site programming), the key does not require an external power supply (it is powered via the connecting cable).
-If the controller is NOT powered (workshop programming), the key requires a 12Vdc/500 mA external power supply (AKO-80018 or equivalent).

Funcionament

AKO - Avís IMPORTANT: After connecting the key to the equipment wait for 5 seconds before starting the reading or writing process.

RECORD key

Write the data contained in the key memory to the controller.
Keep the key pressed until the COM led starts flashing quickly.
When recording is complete the controller will reset.

READ key

It reads the data from the controller and stores them in the programming key.
Keep the key pressed until the COM led starts flashing quickly.
When recording is complete the controller will reset.

LED encès

Steady or flashing: Indicates that the key is connected to the controller.

LED COM

Estable: Indicates an error in the transmission/reception of data
Parpelleig ràpid: Indicates transmission/reception of data in progress. At the end of the transmission LED COM s'apagarà.
Parpelleig lent: Indicates compatibility error- the data contained in the memory of the key is not compatible with the model of controller connected. Data can only be read from the controller to the key.

AKO - Important NOTA: To restart after a transmission or compatibility error, turn off the power supply or disconnect the controller connector cable.

AKO - Avís IMPORTANT: Mai disconnect the programming key during data transmission.

Especificacions tècniques

Length of cable from programming key to controller . . . . . . . . . . . . . 300 mm
Subministrament voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Vdc nominal
Supply current . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-80018 / 500 mA máx.
Especificacions ambientals:
Ambient working temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . 0ºC to 50ºC
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC to 70ºC

AKO logo2

AKO ELECTROMECÁNICA, SA
Av. Roquetes, 30-38 | 08812 Sant Pere de Ribes | Barcelona | Espanya

35D149181 REV.07 2025

Ens reservem el dret de subministrar materials que puguin variar lleugerament als descrits a les nostres fitxes tècniques.
La informació actualitzada està disponible al nostre weblloc.

Documents/Recursos

AKO D14918 Programming Key [pdfManual d'instruccions
AKO-D14918, AKO-80018, D14918 Programming Key, Programming Key, Key

Referències

Deixa un comentari

La teva adreça de correu electrònic no es publicarà. Els camps obligatoris estan marcats *