Zurn 1-950XLT2

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer User Manual

Model: 1-950XLT2 | Brand: Zurn

Introducció

This manual provides essential information for the proper installation, operation, and maintenance of the Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer. This device is designed to protect potable water supplies from contamination or pollution due to back-siphonage or backpressure from non-potable sources. Adherence to these instructions is crucial for optimal performance and compliance with local regulations.

The Zurn 1-950XLT2 is suitable for a wide range of applications, including residential, commercial, industrial, irrigation, marine, and fire protection systems. It features a bronze body construction, Noryl replaceable seats, and silicone rubber check discs, ensuring durability and reliable operation.

Informació de seguretat

  • Always depressurize the system before attempting any installation, maintenance, or repair.
  • Utilitzeu l'equip de protecció individual (EPI) adequat, incloent-hi ulleres i guants de seguretat.
  • Ensure all local plumbing codes and regulations are followed during installation and testing.
  • Only qualified personnel should install and service this backflow preventer.
  • Do not use this device for applications exceeding its specified temperature and pressure ratings.

Producte acabatview

The Zurn 1-950XLT2 is a double check valve assembly designed to prevent backflow. It consists of two independently operating, spring-loaded check valves, two full port shut-off valves, and four ball valve test cocks for field testing.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, front view

Imatge 1: Davant view of the Zurn 1-950XLT2 Double Check Valve Backflow Preventer. This image shows the bronze body, the two main check valve sections, and the green-handled shut-off valves on either end. The model number and pressure rating are visible on the body.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, angled view

Imatge 2: En angle view of the Zurn 1-950XLT2, highlighting the full port connections and the overall compact design. The green handles of the shut-off valves are clearly visible.

Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer, top view with test cocks

Imatge 3: A dalt view of the Zurn 1-950XLT2, showing the four black-capped ball valve test cocks positioned along the body, essential for testing the check valves.

Instal·lació

Comprovacions prèvies a la instal·lació

  • Verify that the model number and size match the system requirements.
  • Inspect the unit for any signs of damage from shipping.
  • Ensure all necessary tools and materials are available.
  • Confirm compliance with local plumbing codes for backflow prevention devices.

Muntatge i orientació

The Zurn 1-950XLT2 must be installed in a horizontal position with the test cocks facing upwards to allow for proper testing and drainage. Ensure adequate clearance around the unit for maintenance and testing.

Connexions de canonades

  1. Flush the supply line thoroughly to remove any debris before connecting the backflow preventer.
  2. Install the unit with the flow arrow on the body pointing in the direction of water flow.
  3. Use appropriate pipe thread sealant on all threaded connections. Avoid overtightening.
  4. Ensure the shut-off valves are in the closed position during installation.
  5. Gradually open the upstream shut-off valve to slowly fill the device and system, allowing air to escape through the test cocks.
  6. Once filled, slowly open the downstream shut-off valve.

Funcionament

The Zurn 1-950XLT2 operates automatically to prevent backflow. Under normal flow conditions, both check valves are open. If a backpressure or back-siphonage condition occurs, the check valves close to prevent reverse flow.

Vàlvules de tancament

The unit is equipped with two full port shut-off valves, one upstream and one downstream. These valves allow for isolation of the backflow preventer for maintenance or testing without shutting down the entire water supply.

  • To close: Turn the green handle 90 degrees until it is perpendicular to the pipe.
  • To open: Turn the green handle 90 degrees until it is parallel to the pipe.

Manteniment

Regular maintenance and testing are essential to ensure the continued proper functioning of the backflow preventer and compliance with local regulations.

Annual Testing

The Zurn 1-950XLT2 must be tested annually by a certified backflow prevention device tester. The four ball valve test cocks are provided for this purpose. Refer to local codes for specific testing requirements and frequencies.

Manteniment

The entire unit is designed to be serviceable in-line. This includes the Noryl replaceable seats and silicone rubber check discs. If repairs are needed, use only genuine Zurn replacement parts.

  1. Isolate the unit by closing both upstream and downstream shut-off valves.
  2. Despressuritzeu la unitat obrint les aixetes de prova.
  3. Follow the specific service instructions provided in the detailed service manual (available from Zurn) for disassembling and reassembling the check valve modules.
  4. After servicing, close test cocks, slowly open shut-off valves, and re-test the unit.

Resolució de problemes

ProblemaCausa possibleSolució
Water leakage from test cocksTest cock not fully closed; debris in test cock; faulty test cock.Ensure test cock is fully closed. Flush test cock. Replace test cock if damaged.
Continuous discharge from relief valve (if applicable, though this is a DCVA)Not applicable for Double Check Valve Assembly (DCVA). This symptom is typical for a Reduced Pressure Zone (RPZ) assembly.N/A (DCVA does not have a relief valve).
Failure during annual testWorn check valve seats or discs; debris lodged in check valves; damaged springs.Isolate unit, disassemble, inspect, clean, and replace worn components (seats, discs, springs). Re-test after service.
Reduced flow or pressure dropPartially closed shut-off valves; debris accumulation within the unit or upstream piping.Ensure shut-off valves are fully open. Isolate and flush the system. Inspect check valves for debris.

For issues not listed here, or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Zurn technical support.

Especificacions

  • Model: Zurn 1-950XLT2 Wilkins Double Check Valve Backflow Preventer
  • Material: Bronze
  • Inlet/Outlet Connection Size: 1 polzades
  • Tipus de connexió: Port complet
  • Nombre de ports: 2 (for main flow)
  • Galls de prova: 4 Ball Valve Test Cocks
  • Interval de temperatura: De 33 °F a 180 °F (de 0.5 °C a 82 °C)
  • Acabat exterior: Rubber, Silicone (for seals and discs)
  • Dimensions (L x A x A): Aproximadament 10 x 7.5 x 4.5 polzades
  • Pes de l'article: Aproximadament 8.1 lliures
  • Certificacions: NSF/ANSI 372 (Lead Free), NSF/ANSI 61, ASTM B122, ASTM B153, ASSE 1013, ASSE 1014
  • Lead Free Compliance:
Diagram showing Retrofit, Lead Free, and Water Saving icons

Imatge 4: Informational graphic illustrating key features: "Retrofit" (suitable for retrofit applications), "Lead Free" (low lead compliant), and "Water Saving" (implied benefit of proper backflow prevention). This highlights the product's modern design and compliance.

Garantia i Suport

Informació de la garantia

Zurn products are manufactured to high-quality standards. For specific warranty details, please refer to the official Zurn warranty statement included with your product or visit the Zurn weblloc. Conserveu el rebut de compra per a reclamacions de garantia.

Atenció al client

For technical assistance, replacement parts, or further information, please contact Zurn customer support. You can find contact details on the official Zurn weblloc web o a través del vostre distribuïdor local.

Zurn Weblloc: www.zurn.com

Documents relacionats - 1-950XLT2

Preview Muntatge de la vàlvula reductora de pressió Zurn Wilkins ZW209FP: instal·lació, funcionament i manteniment
Guia completa del conjunt de vàlvules reductores de pressió de protecció contra incendis Zurn Wilkins ZW209FP, que cobreix la instal·lació, la posada en marxa, el funcionament, les característiques de flux i els procediments de manteniment. Inclou instruccions detallades per a la vàlvula principal i la vàlvula pilot PV-PRD.
Preview Conjunt de vàlvula de retenció doble ZURN Model 350AST: especificacions i aplicació
Detalls tècnics complets per al conjunt de vàlvula de retenció doble ZURN model 350AST, que cobreixen la seva aplicació en sistemes d'aigua potable, materials, estàndards de compliment, dimensions, pesos, característiques de flux i pautes d'instal·lació.
Preview Especificacions i instal·lació del conjunt de disjuntors de buit a pressió Zurn Wilkins Model 720A
Informació detallada sobre el conjunt de trencador de buit a pressió Zurn Wilkins Model 720A, incloent-hi la seva aplicació, compliment de les normes, materials, característiques, dimensions, pesos, característiques de flux i pautes d'instal·lació tant per a ús interior com exterior.
Preview Vàlvula reductora de pressió sense plom Zurn NR3XL: guia d'instal·lació, manteniment i reparació
Guia completa per a la vàlvula reductora de pressió sense plom Zurn NR3XL, que cobreix la instal·lació, la inspecció, el manteniment, els procediments de reparació i la resolució de problemes. Inclou les especificacions del producte i informació sobre la garantia.
Preview Zurn NR3XL Water Pressure Reducing Valve with Integral By-Pass Check Valve and Strainer
Detailed specifications and installation guide for the Zurn NR3XL, a water pressure reducing valve designed for potable water lines. Features include an integral strainer, by-pass check valve, and low lead cast bronze body. Suitable for residential and commercial applications.
Preview Adaptador d'espai d'aire ZURN Model AG
L'adaptador de gap d'aire ZURN model AG està dissenyat per al seu ús amb els preventors de reflux de principi de pressió reduïda ZURN WILKINS, garantint una instal·lació correcta de la línia de drenatge en sistemes horitzontals o verticals. Aquest document detalla les seves especificacions, materials i requisits d'instal·lació típics.