Leviton 2K480-2D

Leviton Series 2000 480V 3P4W 200A Demand Indoor Kit

Model: 2K480-2D (200-Amp)

1. Introducció

The Leviton Series 2000 480V 3P4W 200A Demand Indoor Kit (Model 2K480-2D) is a revenue-grade meter designed for accurate measurement of power consumption. This kit is suitable for various applications, including load management and achieving LEED ratings. It provides reliable performance for both new construction and retrofit installations, ensuring precise data capture of electrical usage.

Leviton Series 2000 480V 3P4W 200A Demand Indoor Kit with 3 Split Core CTs

Image 1.1: Leviton Series 2000 480V 3P4W 200A Demand Indoor Kit with 3 Split Core CTs. This image displays the main components of the metering kit, including the meter unit and the current transformers.

2. Informació de seguretat

ADVERTIMENT: Installation and servicing of this equipment should only be performed by qualified, licensed electrical personnel. Failure to follow these instructions may result in serious injury or death.

3. Contingut del paquet

Verifiqueu que tots els components siguin presents abans de començar la instal·lació:

4. Configuració i instal·lació

This section outlines the general steps for installing the Leviton Series 2000 meter. Refer to the detailed wiring diagrams provided with the product packaging for specific connection instructions.

  1. Desconnexió d'alimentació: Ensure all power to the installation area is completely disconnected at the source. Confirm with a voltage provador.
  2. Mounting the Meter: Mount the Leviton Series 2000 meter in a suitable indoor location, ensuring it is secure and accessible for wiring and observation.
  3. Current Transformer (CT) Installation:
    • The included split core CTs are designed for easy installation without requiring disconnection of existing wire terminations, making them ideal for retrofitting.
    • Open each split core CT and carefully place it around the appropriate phase conductor. Ensure the CT closes securely.
    • Observe the correct line/load orientation as indicated on the CTs. For 100 and 200 Amp solid core CTs (if used), color-coded labels assist in identifying the correct orientation.
    • Connect the CT leads to the designated terminals on the Leviton Series 2000 meter according to the wiring diagram.
  4. Voltage Connexió: Connecteu el voltage leads from the electrical system to the appropriate terminals on the meter. Ensure correct phase sequencing and voltage levels (480V 3P4W).
  5. Connexions de comunicació: If integrating with AMR or BAS systems, connect the Isolated Pulse Output and/or RS-485 Serial Port (Modbus Native) to the respective communication devices.
  6. Initial Power-Up and Diagnostics: Restore power to the system. Observe the meter's diagnostic indicators:
    • A red reverse phase indicator will illuminate if the meter is improperly installed (e.g., incorrect CT orientation or wiring). Correct any issues before proceeding.
    • A green duty cycle light should illuminate, indicating that the meter is collecting electrical consumption data at the appropriate rate.

5. Funcionament del comptador

The Leviton Series 2000 meter operates automatically once properly installed and powered. It continuously measures and records electrical consumption data.

6. Manteniment

The Leviton Series 2000 meter is designed for long-term, reliable operation with minimal maintenance.

7. Solució De Problemes

If you encounter issues with your Leviton Series 2000 meter, refer to the following table:

ProblemaCausa possibleSolució
Red reverse phase indicator is illuminated.Improper installation, incorrect CT orientation, or wiring error.Immediately disconnect power. Re-check all wiring connections and CT orientations against the installation diagram. Ensure CTs are securely closed.
Green duty cycle light is not illuminated.Meter is not receiving power or not collecting data.Verify that power is supplied to the meter. Check all power and CT connections. If issues persist, contact technical support.
No readings or incorrect data.Wiring error, CT malfunction, communication issue, or meter fault.Ensure all wiring is correct and secure. Check CTs for proper installation and function. Verify communication settings if connected to an external system. If problem persists, contact technical support.

8. Especificacions

Key technical specifications for the Leviton Series 2000 2K480-2D meter:

9. Garantia i Suport

This Leviton product is covered by a manufacturer's warranty. For specific warranty terms, duration, and conditions, please refer to the warranty information included with your product packaging or visit the official Leviton weblloc.

For technical assistance, troubleshooting beyond this manual, or to inquire about replacement parts, please contact Leviton customer support:

Documents relacionats - 2K480-2D

Preview Leviton VerifEye Advanced Multi-Circuit Meter Quick Install Guide
Quick installation guide for Leviton VerifEye Advanced Multi-Circuit Meters (Cat. Nos. 71D12, 71D48, 70D12, 70D48, 70N12, 70N48), covering warnings, cautions, installation steps, communication verification, and technical specifications.
Preview Manual d'instal·lació del mesurador de panell multifunció Leviton Sèrie 6000
Guia d'instal·lació detallada del mesurador de panell multifunció Leviton Sèrie 6000, que cobreix les seves funcions de mesura, monitorització i elaboració d'informes elèctrics, juntament amb instruccions de comunicació i configuració.
Preview Leviton Series 8000 Multi-Point High Density Meter: Installation and User's Manual
Comprehensive installation and user guide for the Leviton Series 8000 Multi-Point High Density Meter, covering system specifications, safety precautions, installation procedures, configuration, and regulatory compliance.
Preview Mesurador multicircuit avançat Leviton VerifEye: instal·lació i especificacions (72D48, 72N48, 73D48)
Guia d'instal·lació completa i especificacions tècniques per als mesuradors multicircuit VerifEye Advanced de Leviton (models 72D48, 72N48, 73D48). Inclou diagrames de cablejat, configuració de la comunicació, entrades d'impulsos i precaucions de seguretat.
Preview Leviton 0.5% Mini Meter Installation Guide: Flush Mount Enclosure with Wireless AMR
This installation guide provides detailed instructions for setting up and installing the Leviton 0.5% Mini Meter in a flush mount enclosure, including features like wireless AMR capabilities.
Preview Guia de l'aplicació My Leviton: controla els teus dispositius domèstics intel·ligents
Exploreu la Guia de l'aplicació My Leviton per inscriure, integrar i personalitzar fàcilment els vostres dispositius Decora Smart Wi-Fi i el centre de càrrega Leviton amb interruptors intel·ligents per a un control de la llar intel·ligent sense problemes.