1. Introducció
The APC AP7723 Automatic Transfer Switch (ATS) is a rack-mountable device designed to provide redundant power to connected equipment. It automatically transfers power from a primary source to a secondary source when the primary source becomes unavailable, ensuring continuous operation of critical loads. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your AP7723 ATS.
2. Informació de seguretat
Please read and understand all safety instructions before installing or operating the AP7723 ATS. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- Assegureu-vos que la unitat estigui correctament connectada a terra.
- Do not operate the unit in wet or excessively humid environments.
- Disconnect all power sources before performing any maintenance or installation procedures.
- Només personal qualificat ha d'instal·lar i mantenir aquest equip.
- Comproveu que l'entrada voltage and current ratings of the ATS match the power sources and connected equipment.
3. Configuració i instal·lació
3.1 Contingut del paquet
Verifiqueu que tots els components siguin presents:
- APC AP7723 Automatic Transfer Switch unit
- Maquinari de muntatge en bastidor
- Documentació (aquest manual)
3.2 Physical Installation (Rack-Mounting)
The AP7723 is designed for installation in a standard 19-inch equipment rack, occupying 1U of rack space.
- Secure the rack-mounting brackets to the sides of the ATS unit using the provided screws.
- Mount the ATS into the desired 1U space in your equipment rack using the appropriate rack screws. Ensure it is securely fastened.
3.3 Connecting Power Sources
The AP7723 features two independent AC power inputs (Source A and Source B) and multiple output connectors.

Figure 1: Rear panel of the AP7723 ATS, illustrating the dual power inputs (Source A and Source B) and the nine output connectors. This view helps in identifying where to connect primary and secondary power, as well as the devices to be powered.
- Connect the primary power source cable to the "Source A" input on the rear panel of the ATS.
- Connect the secondary power source cable to the "Source B" input on the rear panel of the ATS.
- Ensure both power sources are active and stable.
3.4 Connexió de dispositius de sortida
The AP7723 provides 9 output connectors to power your equipment.
- Connect your critical equipment power cords to the available output connectors on the rear panel of the ATS.
- Ensure that the total load of the connected equipment does not exceed the maximum current rating of the ATS.
3.5 Network and Serial Connection
The AP7723 supports Ethernet 10/100 and RS-232 for remote management and monitoring.
- Ethernet: Connect a standard Ethernet cable from the ATS's Ethernet port to your network switch or router for network-based management.
- EL-232: Connect a serial cable from the ATS's RS-232 port to a computer or console server for local management.
4. Funcionament
4.1 Tauler frontal sobreview

Figure 2: Front panel of the AP7723 ATS, displaying the Input A/B indicators, Output indicator, Preference A/B buttons, Amps display, and Status LEDs. This panel allows for monitoring power status and setting power source preference.
- Input A/B LEDs: Indicate which input source is active and available.
- LED de sortida: Indicates that power is being supplied to the connected equipment.
- Preference A/B Buttons: Allow manual selection of the preferred input source.
- Amps Visualització: Shows the total current draw of the connected equipment.
- LED d'estat: Provide information on the unit's operational status and any potential issues.
4.2 Automatic Transfer Logic
The AP7723 continuously monitors both input power sources. Under normal conditions, it will draw power from the preferred source (default or user-selected). If the preferred source fails or deviates from acceptable voltage/frequency parameters, the ATS will automatically transfer the load to the alternate source within milliseconds, ensuring uninterrupted power to connected devices.
4.3 Setting Power Source Preference
You can set a preferred input source using the front panel buttons or through the network management interface.
- Press the "Preference A" button to set Source A as the preferred input.
- Press the "Preference B" button to set Source B as the preferred input.
- The ATS will attempt to draw power from the preferred source whenever both sources are available and within acceptable limits.
5. Manteniment
The APC AP7723 ATS is designed for reliable operation with minimal maintenance. However, periodic checks are recommended.
- Neteja: Keep the unit free from dust and debris. Use a dry cloth to wipe the exterior. Do not use liquid cleaners.
- Inspecció del cable: Periodically inspect all power and network cables for signs of wear or damage. Replace any damaged cables immediately.
- Actualitzacions de firmware: Check the APC website for available firmware updates to ensure optimal performance and access to new features. Follow the provided instructions for updating firmware.
6. Solució De Problemes
This section provides solutions to common issues you might encounter with your AP7723 ATS.
| Problema | Causa possible | Solució |
|---|---|---|
| No power to output devices | Input power sources are off or disconnected. ATS is overloaded. | Verify both Source A and Source B are connected and active. Check the Amps display for overload. Reduce load if necessary. |
| ATS not transferring power | Both sources are available and stable. Transfer threshold settings. | The ATS will only transfer if the preferred source fails. Check status LEDs. Consult the network management interface for detailed event logs and threshold settings. |
| Network management inaccessible | Ethernet cable disconnected. Incorrect network settings. | Ensure Ethernet cable is securely connected. Verify IP address and network settings via serial console or front panel (if supported). |
If the problem persists after attempting these solutions, contact APC technical support.
7. Especificacions
| Característica | Detall |
|---|---|
| Número de model | AP7723 |
| Marca | APC |
| Entrada Voltage | CA 230 V |
| Connectors de sortida | 9 |
| Factor de forma | Muntatge en bastidor (1U) |
| Connectivitat | Ethernet 10/100, RS-232 |
| Color | Negre |
| Pes de l'article | 11.43 lliures (5.18 kg) |
| UPC | 022091929893 |
8. Garantia i Suport
For information regarding product warranty, technical support, or service, please refer to the official APC website or contact your local APC representative. Keep your purchase receipt for warranty claims.
Recursos en línia: www.apc.com/support