Watts LF009M3-QT

Watts 3/4" Reduced Pressure Zone Backflow Preventer (Model LF009M3-QT) Instruction Manual

Guia completa per a la instal·lació, el funcionament i el manteniment.

1. Producte acabatview

The Watts 3/4 inch Lead Free Reduced Pressure Zone (RPZ) Assembly is engineered to safeguard potable water supplies from contamination due to backsiphonage or backpressure. This device complies with national plumbing codes and water authority requirements, making it suitable for continuous pressure piping applications and cross-connections identified as health hazards.

Watts 3/4 inch Reduced Pressure Zone Backflow Preventer

Image 1.1: The Watts 3/4 inch Reduced Pressure Zone Backflow Preventer assembly.

Watts backflow preventer with text 'Protect Potable Water Supplies'

Image 1.2: Visual representation emphasizing the backflow preventer's role in protecting potable water supplies.

Característiques principals:

2. Informació de seguretat

Always adhere to local plumbing codes and regulations during installation and maintenance. This device must be installed by a qualified professional. Failure to follow instructions may result in property damage or injury.

Diagram showing backflow preventer installation warning

Image 2.1: Important note regarding installation of backflow preventers in pits. Always consult local codes.

3. Instruccions d'instal·lació

Proper installation is crucial for the effective operation of the backflow preventer. This device should be installed in a location that allows for easy access for testing and maintenance.

3.1 Comprovacions prèvies a la instal·lació

  1. Verify that the assembly size (3/4 inch) matches the pipe size.
  2. Inspect the unit for any visible damage that may have occurred during shipping.
  3. Ensure all necessary tools and materials are available, including pipe sealant or thread tape.

3.2 Passos d'instal·lació

  1. Preparació de les canonades: Ensure the piping is clean and free of debris. The assembly must be installed horizontally, with the relief valve pointing downwards.
  2. Orient the Valve: Observe the flow arrow cast into the valve body to ensure correct orientation with the direction of water flow.
  3. Close-up of the Watts backflow preventer body showing flow arrow

    Imatge 3.1: Primer pla view of the valve body, highlighting the flow direction arrow for proper installation.

  4. Connect to Piping: Apply appropriate pipe sealant or thread tape to the NPT connections. Carefully thread the assembly onto the pipes, ensuring a tight, leak-free seal. Avoid overtightening.
  5. Hands installing the Watts backflow preventer onto plumbing pipes

    Image 3.2: A technician connecting the backflow preventer to the plumbing system.

  6. Support the Assembly: Provide adequate support for the assembly to prevent stress on the piping connections.
  7. Open Shutoff Valves: Slowly open the inlet and outlet shutoff valves to allow water to fill the assembly. Bleed any trapped air from the system.
  8. Comproveu si hi ha fuites: After installation and pressurization, thoroughly inspect all connections for leaks.
Watts backflow preventer installed in a plumbing system

Image 3.3: The Watts backflow preventer fully installed within a plumbing system, ready for operation.

4. Instruccions de funcionament

The Watts Reduced Pressure Zone Assembly operates automatically to prevent backflow. No manual intervention is required during normal operation.

4.1 Funcionament normal

4.2 Shutoff Valves

The integrated quarter-turn ball valve shutoffs are for isolating the unit for maintenance or testing. Ensure they are fully open during normal operation to allow unrestricted flow.

5. Manteniment

Regular maintenance and testing are essential to ensure the continued proper function of the backflow preventer. Local codes typically require annual testing by a certified backflow prevention device tester.

5.1 Routine Testing

5.2 Internal Component Access

The single access cover and modular check construction allow for easy inspection and replacement of internal components if necessary.

  1. Isolate the unit by closing both inlet and outlet shutoff valves.
  2. Depressurize the assembly by opening the test cocks.
  3. Remove the bolts securing the access cover.
  4. Carefully lift the cover to access the check valve assemblies and relief valve.
  5. Interna view of the Watts backflow preventer with cover removed

    Imatge 5.1: View of the internal components after removing the access cover, showing the check valve assemblies.

  6. Inspect components for wear, damage, or debris. Replace any worn or damaged parts with genuine Watts replacement parts.
  7. Reassemble in reverse order, ensuring proper seating of all components and tightening bolts evenly.
  8. Slowly repressurize the system and check for leaks.

6. Solució De Problemes

This section addresses common issues that may arise with the backflow preventer. For complex problems, contact a certified professional.

ProblemaCausa possibleSolució
Water leaking from relief valve
  • Fouled or damaged first check valve.
  • Fouled or damaged second check valve.
  • Debris in relief valve seat.
  • Low inlet pressure.
  • Clean or replace first check valve components.
  • Clean or replace second check valve components.
  • Clean relief valve seat.
  • Verify adequate system pressure.
Reducció del cabal d'aigua
  • Partially closed shutoff valves.
  • Debris lodged in the assembly.
  • Damaged check valve components.
  • Assegureu-vos que les vàlvules de tancament estiguin completament obertes.
  • Isolate and inspect the assembly for obstructions.
  • Inspect and replace damaged check valve components.
External leaks from body or connections
  • Improperly tightened connections.
  • Damaged O-rings or gaskets.
  • Cracked body (rare).
  • Estrenyeu les connexions (no les estrenyeu massa).
  • Replace O-rings or gaskets.
  • Contact Watts support for body damage.

7. Especificacions

AtributValor
Número de modelLF009M3-QT
Mida3/4 polzada
MaterialLead-Free Bronze
Mida de la connexió d'entrada0.75 polzades
Tipus de connexió d'entradaNational Pipe Tapered (NPT)
Mida de connexió de presa3/4 polzades
Tipus de connexió de presaNPT
Pressió màxima de funcionament175 PSI (lliura per polzada quadrada)
Nombre de Ports3
Dimensions (L x A x A)Aproximadament 4 x 4 x 6 polzades
Pes de l'article5.48 lliures
UPC098268705553

8. Informació de la garantia

Watts products are manufactured to high standards and are typically covered by a limited warranty. For specific warranty terms and conditions applicable to your Watts LF009M3-QT Reduced Pressure Zone Assembly, please refer to the warranty documentation included with your product or visit the official Watts website. Warranty claims usually require proof of purchase and adherence to installation and maintenance guidelines.

9. Atenció al client

For technical assistance, replacement parts, or further information regarding your Watts 3/4" Reduced Pressure Zone Backflow Preventer, please contact Watts customer support.

Documents relacionats - LF009M3-QT

Preview Conjunts de zona de pressió reduïda Watts Sèrie LF909: especificacions tècniques
Especificacions tècniques detallades per als conjunts de zona de pressió reduïda Watts sèrie LF909, incloent-hi característiques, funcionament, dimensions, pesos i capacitat. Dissenyat per al control de connexions creuades d'aigua potable.
Preview Especificació d'enginyeria del muntatge de zona de pressió reduïda de la sèrie Watts LF909
Especificació d'enginyeria completa per al conjunt de zona de pressió reduïda Watts sèrie LF909 (21⁄2" - 10"). Detalla les característiques, el funcionament, els materials, les dimensions i la capacitat d'aquest dispositiu de prevenció de reflux sense plom amb sensor d'inundació integrat.
Preview Muntatge de zona de pressió reduïda Watts Sèrie LF919: Manual d'instal·lació, manteniment i reparació
Guia completa per a la instal·lació, el manteniment i la reparació del conjunt de zona de pressió reduïda Watts Series LF919 (1/2" - 2"). Inclou avisos de seguretat, procediments d'instal·lació, instruccions de manteniment i resolució de problemes.
Preview Kit GBS de vàlvula antiretorn doble d'acer inoxidable Watts (007-SS-GBS) - Dades tècniques
Especificacions tècniques, codis de producte, dimensions i característiques de la vàlvula antiretorn doble d'acer inoxidable Watts 007-SS-GBS amb vàlvula de papallona amb engranatges i filtre. Dissenyada per a la prevenció del reflux en instal·lacions de risc mitjà i baix.
Preview Watts Sèrie 009, LF009, LFU009, SS009, U009: Manual d'instal·lació, manteniment i reparació
Aquest manual complet de Watts proporciona una guia essencial per a la instal·lació, el manteniment i la reparació dels conjunts de zona de pressió reduïda de les sèries 009, LF009, LFU009, SS009 i U009. Detalla els avisos de seguretat, els procediments d'instal·lació, la inspecció, el manteniment, la resolució de problemes i la informació sobre la garantia d'aquests dispositius crítics de prevenció del reflux.
Preview Conjunts de zona de pressió reduïda Watts sèrie LF909: Manual d'instal·lació, manteniment i reparació
Guia completa per als conjunts de zona de pressió reduïda de la sèrie Watts LF909, que cobreix la instal·lació, el manteniment, els procediments de prova, la resolució de problemes i la revisió. Essencial per garantir el funcionament correcte i la longevitat.