BEST BAL700

Manual d'usuari del balast d'il·luminació d'emergència BEST BAL700

Comprehensive instructions for installation, operation, and maintenance of your emergency lighting ballast.

1. Producte acabatview

The BEST BAL700 Emergency Lighting Ballast is designed to convert new or existing fluorescent fixtures into emergency lighting units. This ballast allows fluorescent lighting fixtures to operate for both normal and emergency purposes. In the event of a power outage, it automatically switches to battery power, providing a minimum of 90 minutes of emergency illumination. It is compatible with a wide range of fluorescent lamps and AC ballasts.

BEST BAL700 Emergency Lighting Ballast with wiring

Image 1.1: The BEST BAL700 Emergency Lighting Ballast, showing its compact white housing and multi-colored wiring harness for connection to a fluorescent fixture.

2. Característiques clau

  • Dual Voltage Compatibilitat: Operates on both 120V and 277V AC power supplies.
  • Il·luminació d'emergència: Provides a minimum of 90 minutes of emergency lighting with a maximum initial lumen output of 700 lumens.
  • Transferència automàtica: Features an internal solid-state transfer switch that automatically connects the internal battery to the fluorescent lamp(s) during power interruptions.
  • AC Output Enhancement: Ensures compatibility with newer lamp technologies and contributes to prolonged lamp vida.
  • Bateria recarregable: Equipped with a long-life, maintenance-free, rechargeable sealed NiCd battery.
  • Recàrrega ràpida: Fully automatic solid-state, two-rate charger recharges a discharged battery within 24 hours.
  • Test Switch and Indicator: Includes an LED charge rate/power ON indicator light and a push-to-test switch for mandated code compliance testing.
  • Temps de retard: Incorporates a time delay enhancement to overcome end-of-life circuit protection in fluorescent lamps.
  • Damp Ubicació classificada: UL listed for installation in damp ubicacions.
  • Disseny compacte: Durable painted steel construction in a white finish, designed to fit most fluorescent fixtures.

3. Especificacions tècniques

Atribut Valor
Número de modelBAL700
Lumen Output (Emergency)700 lumens (initial)
Hora d’operació d’emergènciaMínim 90 minuts
Entrada Voltage120/277V AC, 60Hz
Tipus de bateriaSealed NiCd (Nickel Cadmium)
Temps de recàrrega de la bateria24 hores
Dimensions (L x A x A)9.5 x 2.4 x 1.5 polzades
PesAproximadament 0.01 unces (Note: This weight seems incorrect based on typical ballast weights, please verify with manufacturer if critical.)
Material de l'habitatgeAcer pintat
Temperatura de funcionamentLlistat UL per a damp ubicacions
Lamp CompatibilitatMost one, two, three, and four-lamp electronic standard and dimming AC ballasts. Operates one 17W-40W T8 through T12, two 13W-39W, one 13W-42W 4-pin compact or one 18W-40W 4-pin compact fluorescent lamps.
CertificacionsUL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes, UL listed for damp ubicacions.
lateral view of BEST BAL700 Emergency Lighting Ballast

Imatge 3.1: Costat A view of the BEST BAL700 Emergency Lighting Ballast, highlighting its compact form factor suitable for various fixture installations.

4. Instruccions d'instal·lació

4.1. Precaucions de seguretat

  • ADVERTIMENT: Risc de descàrrega elèctrica. Desconnecteu l'alimentació a l'interruptor o a la caixa de fusibles abans de la instal·lació o el manteniment.
  • Installation should be performed by a qualified electrician in accordance with the National Electrical Code (NEC) and local codes.
  • Assegureu-vos que l'entrada voltage (120V or 277V) matches the building's electrical supply.
  • Do not use with dimming ballasts unless specifically rated for such use.
  • No instal·leu a prop d'escalfadors de gas o elèctrics.

4.2. Muntatge

The BAL700 ballast is suitable for installation inside, on top of, or remotely from the fixture. Its compact design allows for versatile placement within most fluorescent fixtures.

  1. Choose a mounting location that allows for proper heat dissipation and access for maintenance.
  2. Secure the ballast using appropriate fasteners (not included) through the mounting tabs.

4.3. Cablatge

Refer to the wiring diagram provided on the ballast label for specific connections. General steps include:

  1. Connect the unswitched AC power supply (120V or 277V) to the ballast's input wires.
  2. Connect the ballast's output wires to the fluorescent lamp(s) and the existing AC ballast as per the diagram.
  3. Assegureu-vos que totes les connexions estiguin segures i aïllades.
  4. Install the LED test switch in an accessible location on the fixture or wall plate.

Nota: The BAL700 can be used in both switched and unswitched fixtures. For switched fixtures, ensure the emergency ballast receives unswitched power to allow for emergency operation regardless of the wall switch position.

5. Instruccions de funcionament

5.1. Funcionament normal

When AC power is present, the BAL700 ballast charges its internal battery. The connected fluorescent lamp(s) will operate normally via the existing AC ballast. The LED indicator light on the test switch will illuminate, indicating that the battery is charging and the unit is ready for emergency operation.

5.2. Emergency Operation

Upon interruption of normal AC power, the BAL700 automatically switches to emergency mode. The internal solid-state transfer switch activates, powering one fluorescent lamp from the internal NiCd battery for a minimum of 90 minutes. When AC power is restored, the unit automatically returns to normal operation and begins recharging the battery.

5.3. Testing the Unit

Regular testing is required to ensure proper emergency function and compliance with safety codes.

  1. Prova mensual: Press and hold the push-to-test switch for at least 30 seconds. The emergency lamp should illuminate. Release the switch; the lamp should extinguish (if AC power is present).
  2. Prova anual: Conduct a full 90-minute discharge test. Interrupt AC power to the fixture for 90 minutes. The emergency lamp should remain illuminated for the entire duration. After the test, restore AC power and allow the battery to recharge for 24 hours.

Nota: Keep records of all tests for inspection purposes.

6. Manteniment

The BEST BAL700 Emergency Lighting Ballast is designed for low maintenance. The NiCd battery is sealed and maintenance-free. However, regular checks are recommended:

  • Inspecció visual: Periodically inspect the unit for any visible damage, loose connections, or signs of overheating.
  • Recàrrega de la bateria: After any emergency discharge or test, ensure the unit has at least 24 hours of uninterrupted AC power to fully recharge the battery.
  • Neteja: If necessary, gently wipe the exterior of the ballast with a dry, soft cloth. Do not use abrasive cleaners or solvents.
  • Substitució de la bateria: While designed for long life, NiCd batteries have a finite lifespan. If the unit fails to provide 90 minutes of emergency illumination during an annual test, the battery may need replacement. Contact qualified service personnel for battery replacement.

7. Solució De Problemes

Problema Causa possible Solució
Emergència lamp does not illuminate during test or power outage.
  • No AC power to the ballast.
  • La bateria no està completament carregada.
  • Defectuós lamp.
  • Cablejat incorrecte.
  • Battery at end of life.
  • Internal ballast fault.
  • Comproveu l'interruptor/fusible.
  • Allow 24 hours for battery recharge.
  • Replace fluorescent lamp.
  • Verifiqueu el cablejat amb el diagrama.
  • Replace battery (contact service).
  • Contact manufacturer support.
LED indicator light is off.
  • No AC power to the ballast.
  • Faulty LED or wiring to LED.
  • Comproveu la font d'alimentació de CA.
  • Verify wiring to test switch/LED.
Emergència lamp illuminates for less than 90 minutes.
  • La bateria no està completament carregada.
  • Battery at end of life.
  • Allow 24 hours for battery recharge.
  • Replace battery (contact service).

Si els passos de resolució de problemes no resolen el problema, poseu-vos en contacte amb l'atenció al client.

8. Informació de la garantia

The BEST BAL700 Emergency Lighting Ballast comes with a Cinc anys de garantia against defects in material and workmanship. This warranty excludes lamps. For warranty claims or detailed terms and conditions, please refer to the original purchase documentation or contact BEST customer support.

9. Atenció al client

For technical assistance, installation questions, or warranty inquiries, please contact BEST customer support:

  • Weblloc: Visit the official BEST Lighting Products weblloc web amb preguntes freqüents i informació de contacte.
  • Telèfon: Consulteu l'embalatge del producte o el del fabricant weblloc web per obtenir el número de telèfon d'atenció al client més actualitzat.
  • Correu electrònic: General inquiries can often be sent via email forms available on the manufacturer's weblloc.

When contacting support, please have your product model number (BAL700) and purchase date available.

Documents relacionats - BAL700

Preview Llista de preus de les MILLORS frontisses i accessoris per a portes PL77 | Agost 2025 | dormakaba
The official BEST Hinges & Door Accessories Price List PL77, effective August 2025, featuring a comprehensive catalog of hinges, door accessories, specifications, finishes, and terms of sale from BEST, a dormakaba Group company.
Preview BEST Exit Alarm Systems: ALK, ALW, WALW - Technical Specifications
Detailed specifications for BEST Exit Alarm systems (ALK, ALW, WALW) and kits, including features, wiring, weatherization, and ordering information for Precision Series devices.
Preview BEST Hinges and Door Accessories Canada Price List | August 2025
Comprehensive price list for BEST Hinges and Door Accessories in Canada, featuring detailed product specifications, options, finishes, and pricing for various hinge types. Includes PL77 catalog information for August 2025.