Fire-Lite ES-50X

Fire-Lite ES-50X Addressable Alarm Control Panel User Manual

Model: ES-50X | Marca: Fire-Lite

1. Introducció

The Fire-Lite ES-50X is an advanced 50-point addressable fire alarm control panel designed for small to medium-sized applications. It features a built-in communicator, supports up to 50 addressable devices, and includes a real-time clock/calendar with four programmable function keys. This manual provides essential information for the proper installation, operation, and maintenance of the ES-50X panel to ensure reliable fire detection and notification.

Fire-Lite ES-50X Addressable Alarm Control Panel, front view

Figura 1: Davant view of the Fire-Lite ES-50X Addressable Alarm Control Panel. The panel is housed in a red enclosure with a central control interface featuring an LCD display, keypad, and function buttons. A key lock is visible on the right side of the enclosure.

2. Informació de seguretat

Important: Read all instructions carefully before installation and operation. Failure to follow these instructions may result in property damage, serious injury, or death. This device must be installed by qualified personnel in accordance with all local and national electrical codes and standards, including NFPA 72.

3. Configuració i instal·lació

3.1 Contingut del paquet

Verifiqueu que tots els components siguin presents abans de començar la instal·lació:

3.2 Muntatge del panell

The ES-50X panel is designed for surface mounting. Choose a secure, dry location that is easily accessible for servicing and visible for status indication.

  1. Mark the desired mounting holes on the wall using the panel's enclosure as a template.
  2. Perforeu els forats pilot adequats per als cargols de muntatge.
  3. Secure the panel to the wall using the provided mounting hardware. Ensure the panel is level and securely fastened.

3.3 Connexions de cablejat

All wiring must comply with NFPA 70 (National Electrical Code) and NFPA 72 (National Fire Alarm and Signaling Code), as well as local codes.

3.4 Engegada inicial

After all wiring is complete and verified:

  1. Ensure all field wiring is correctly terminated and free of shorts or opens.
  2. Connect the standby batteries.
  3. Apply AC power to the panel. The panel will perform a self-test and then display its operational status.
  4. Verify that the panel indicates a "Normal" or "System Healthy" status. Address any trouble conditions immediately.

4. Instruccions de funcionament

4.1 Interfície del tauler de control

The ES-50X features an LCD display, a numeric keypad, and dedicated function buttons for system interaction.

4.2 Resposta a les alarmes

When an alarm occurs, the panel will activate notification appliances and display alarm information.

  1. Agrair: Premeu el botó ACK button to silence the panel's internal buzzer and acknowledge the alarm. The LCD will show the alarm location.
  2. Silenci: After verifying the situation and ensuring safety, press the SILENCI button to silence horns and strobes. Do not silence if there is an active fire or danger.
  3. Investigar: Proceed to the alarm location to investigate the cause.
  4. Restablir: Once the cause of the alarm is resolved and the area is safe, press the RESET button. The panel will attempt to clear the alarm condition and return to normal. If the alarm persists, the condition has not been resolved.

4.3 Viewing System Status and Events

The panel's display provides real-time system status. Use the navigation buttons (up/down arrows) to scroll through event history or system menus.

5. Manteniment

Regular maintenance is crucial for the reliable operation of your fire alarm system. All maintenance should be performed by qualified personnel.

5.1 Routine Checks (Monthly)

5.2 Annual Inspection and Testing

A comprehensive annual inspection and test of the entire fire alarm system should be conducted by a certified fire alarm technician in accordance with NFPA 72.

5.3 Substitució de la bateria

Standby batteries typically have a lifespan of 3-5 years. Replace them proactively or when the panel indicates a low battery trouble condition.

  1. Disconnect AC Power: Turn off the circuit breaker supplying power to the panel.
  2. Disconnect Old Batteries: Carefully disconnect the old batteries, observing polarity.
  3. Instal·leu piles noves: Connect new, fully charged batteries of the correct type and rating.
  4. Restore AC Power: Turn on the circuit breaker. The panel should clear the battery trouble.
  5. Eliminar: Dispose of old batteries responsibly according to local environmental regulations.

6. Solució De Problemes

Aquesta secció ofereix solucions a problemes comuns. Per a problemes complexos, poseu-vos en contacte amb un tècnic qualificat d'alarmes d'incendis.

ProblemaCausa possibleSolució
Panel displays "System Trouble"Various issues: low battery, AC power loss, ground fault, open circuit on SLC/NAC.Check AC power. Verify battery connections and voltage. Consult the panel display for specific trouble codes and refer to the detailed installation manual for diagnostics.
Notification appliances do not activate during alarmNAC wiring fault, power supply issue, silenced by mistake.Check NAC wiring for opens or shorts. Verify NAC power supply. Ensure the system is not in "Silence" mode.
Panel does not reset after alarmAlarm condition still present, device not cleared.Ensure the initiating device (e.g., smoke detector) has cleared the alarm condition. Check for residual smoke or heat. If a pull station was activated, ensure it is reset.
Device fault on SLC loopDamaged device, incorrect wiring, address conflict.Identify the specific device from the panel display. Check wiring to the device. Verify device address. Replace faulty device if necessary.

7. Especificacions

Key technical specifications for the Fire-Lite ES-50X Addressable Alarm Control Panel:

8. Garantia i assistència

For specific warranty details, please refer to the warranty statement included with your product packaging or contact Fire-Lite directly. Fire-Lite products typically come with a limited warranty covering defects in materials and workmanship.

Suport tècnic

For technical assistance, troubleshooting beyond this manual, or service inquiries, please contact your authorized Fire-Lite distributor or a certified fire alarm technician. Do not attempt to repair the panel yourself, as this may void the warranty and compromise system integrity.

For general information about Fire-Lite products, visit the official Fire-Lite weblloc.

Documents relacionats - ES-50X

Preview Guia d'inici ràpid de CLSS Pathway Pro: Fire-Lite de Honeywell
Guia d'inici ràpid per al Fire-Lite CLSS Pathway Pro, un comunicador i una passarel·la per als panells de control d'alarma d'incendis (FACP) ES-50XP i ES-200XP que es connecten al núvol CLSS de Honeywell a través de xarxes LTE CAT-M1. Proporciona instruccions per a la programació de FACP i CLSS.
Preview Manual d'instal·lació i programació del Fire-Lite MS-9200UDLS / MS-9200UDLSE
Manual complet per als panells de control d'alarma d'incendis (FACP) i els comunicadors/transmissors d'alarma digital (DACT) Fire-Lite MS-9200UDLS i MS-9200UDLSE, que cobreix la instal·lació, la programació i el funcionament dels sistemes de protecció contra incendis.
Preview Fire-Lite PK-9200W Windows-Based Programming Utility Software Manual
This manual details the Fire-Lite PK-9200W Windows-Based Off-Line Programming Utility software, designed for programming and managing the MS-9200 Addressable Fire Alarm Control Panel. It covers installation, system requirements, software features, and operational procedures for configuring fire alarm systems.
Preview Manual de referència tècnica Fire-Lite MS-4812 i MS-4824
Aquest document proporciona una referència tècnica completa per als panells de control d'alarma d'incendis Fire-Lite MS-4812 i MS-4824, i detalla els procediments d'instal·lació, programació i funcionament.
Preview Mòdul fix de l'anunciador Fire-Lite AFM-16AF: manual tècnic
Manual tècnic complet per al mòdul fix d'anunciador Fire-Lite AFM-16AF, que cobreix la instal·lació, el funcionament, les especificacions i la garantia dels panells de control d'alarma d'incendis Sensiscan 2000.
Preview Manual d'instruccions del panell de control d'alarma d'incendis Fire-Lite MINISCAN 112/124
Manual d'instruccions complet per al panell de control d'alarma d'incendis Fire-Lite MINISCAN 112/124. Detalls de la instal·lació, diagrames de cablejat del sistema, controls, indicadors, selecció de bateries i resolució de problemes. Guia essencial per a la configuració i el manteniment del sistema.