1. Introducció
The Metrel MI 3102 BT EurotestXE is a versatile, multifunctional measuring instrument designed to perform a comprehensive set of installation safety tests in accordance with IEC/EN 61557 standards. This device supports automated testing sequences for TN, TT, and IT earthing systems, and is capable of performing ISFL measurements and IMD tests. It also offers online voltage monitoring, phase sequence testing, earth resistance measurement, illuminance measurement, and TRMS current measurement.
The EurotestXE features integrated characteristics of fuses and RCDs, enabling immediate PASS/FAIL evaluation of test results. All measurement data can be saved directly on the instrument and later transferred to a computer via EuroLink PRO software for detailed analysis and report generation.
Característiques principals:
- Insulation resistance testing with DC voltage de 50 V a 1000 V.
- Continuity of PE conductors with 200 mA DC test current (polarity change) and 7 mA test current (without RCD tripping).
- Line/Loop impedance and Loop impedance with Trip Lock RCD function.
- TRMS voltage and frequency measurement, and phase sequence testing.
- RCD testing for general and selective types (AC, A, F, B, B+).
- Earth resistance measurement using 3-wire and 2-clamps methods.
- First fault leakage current (ISFL) and Insulation Monitoring Devices (IMDs) testing.
- Automated test sequences for various earthing systems (Auto TT, Auto TN/RCD, Auto TN, Auto IT).
- Power measurements and harmonics analysis.
Equipament inclòs:
- Metrel MI 3102 BT EurotestXE Instrument
- Endoll comandant, 1.5 m
- Cable de prova, 3 x 1.5 m
- Earth test set, 3-wire, 20 m (includes test lead, 4 m; 2 x test lead, 20 m; 2 x test rod)
- Adaptador d'alimentació + 6 piles recarregables NiMH, mida AA
- Programari per a PC EuroLink PRO
- Sonda de prova, 3 peces (blau, negre, verd)
- Clip de cocodril, 3 peces (blau, negre, verd)
- RS232 - PS/2 cable
- cable USB
- Cinturó de transport suau al coll
- Bossa de transport suau
- Breu manual d'instruccions
- Manual d'instruccions en CD
- Manual en CD
- Certificat de calibratge

Figure 1: The Metrel MI 3102 BT EurotestXE instrument along with its comprehensive set of included accessories, including test leads, probes, earth test rods, cables, and carrying bags.
2. Configuració
2.1 Instal·lació de la bateria
The MI 3102 BT EurotestXE requires 6 AA NiMH rechargeable batteries, which are included with the instrument. Before first use, ensure the batteries are fully charged using the provided power supply adapter.
- Locate the battery compartment on the rear of the instrument.
- Obriu la tapa del compartiment de la bateria.
- Insert the 6 AA NiMH rechargeable batteries, observing the correct polarity as indicated inside the compartment.
- Tanqueu bé la tapa del compartiment de la bateria.
- Connect the power supply adapter to the instrument and a suitable power outlet to charge the batteries. The charging indicator will illuminate.
2.2 Connecting Test Leads and Accessories
Proper connection of test leads and accessories is crucial for accurate and safe operation. Refer to the specific test function in the detailed instruction manual for precise connection diagrams.
- Cables de prova: Connect the 3 x 1.5 m test leads to the corresponding input terminals on the instrument. Ensure a firm connection.
- Test Probes and Crocodile Clips: Attach the test probes or crocodile clips to the ends of the test leads as required for the measurement.
- Plug Commander: For certain tests, the 1.5 m plug commander can be used for quick and convenient connections to mains sockets.
- Earth Test Set: For earth resistance measurements, connect the 3-wire earth test set, including the 20 m test leads and test rods, to the designated terminals.

Figura 2: Un primer pla view of the Metrel plug commander, showing its control buttons for test initiation and memory functions.
3. Instruccions de funcionament
The MI 3102 BT EurotestXE features an intuitive interface with a clear display and navigation buttons. For detailed operational procedures for each measurement function, refer to the comprehensive instruction manual provided on CD and the short instruction manual.

Figure 3: The display screen of the Metrel MI 3102 BT EurotestXE, showing the model name and software version upon startup.
3.1 Engegada/apagada
- To power on the instrument, press and hold the power button until the display illuminates.
- To power off, press and hold the power button again until the display shuts down.
3.2 Navegació pels menús
Use the arrow buttons to navigate through the measurement functions and settings menus. The 'OK' or 'Enter' button confirms selections, and the 'Back' or 'Escape' button returns to the previous screen.
3.3 Realització de mesures
Select the desired measurement function from the main menu. Follow the on-screen prompts for connecting test leads and initiating the test. The instrument will display the results and provide a PASS/FAIL indication based on pre-set limits or user-defined parameters.
- Resistència d'aïllament: Select the insulation test, choose the desired test voltage (50V to 1000V), connect leads, and initiate the test.
- Continuïtat: Select the continuity test, connect leads to the PE conductor, and perform the measurement.
- Prova RCD: Select the RCD test function, choose RCD type and current, connect leads, and initiate the test.
- Auto Sequence Tests: Utilize the AUTO SEQUENCE feature for streamlined testing of TN, TT, and IT systems.
4. Manteniment
4.1 Cures i neteja generals
To ensure the longevity and accuracy of your Metrel MI 3102 BT EurotestXE, follow these general care guidelines:
- Keep the instrument clean and free from dust and debris. Use a soft, dry cloth for cleaning the casing. For stubborn dirt, a slightly damp cloth with mild detergent can be used, ensuring no liquid enters the instrument.
- Avoid exposing the instrument to extreme temperatures, high humidity, or direct sunlight for prolonged periods.
- Store the instrument and its accessories in the provided soft carrying bag when not in use to protect them from physical damage.
- Regularly inspect test leads, probes, and other accessories for signs of wear, damage, or frayed insulation. Replace any damaged components immediately to ensure safety and accurate measurements.
4.2 Manteniment de la bateria
The instrument uses NiMH rechargeable batteries. To maximize battery life:
- Recharge batteries fully after each use, especially if the instrument will be stored for an extended period.
- If the instrument will not be used for a long time, it is advisable to remove the batteries to prevent leakage.
- Use only the specified type of rechargeable batteries and the original power supply adapter for charging.
4.3 Calibració
A calibration certificate is included with your EurotestXE. To maintain measurement accuracy and comply with regulatory requirements, it is recommended to have the instrument professionally calibrated at regular intervals, typically annually. Refer to the calibration certificate for recommended re-calibration dates or contact Metrel authorized service centers for calibration services.
5. Solució De Problemes
This section provides general guidance for common issues. For detailed troubleshooting steps, consult the full instruction manual on CD.
| Problema | Causa possible | Solució |
|---|---|---|
| L'instrument no s'encén. | Low or depleted batteries; Incorrect battery installation; Instrument fault. | Ensure batteries are fully charged and correctly inserted. Try replacing batteries. If issue persists, contact support. |
| Inaccurate measurement readings. | Damaged or faulty test leads/probes; Incorrect test setup; Instrument out of calibration. | Check all connections and inspect leads for damage. Verify test setup against manual. Consider professional calibration. |
| Software connection issues (EuroLink PRO). | Incorrect cable (USB/RS232) connection; Driver issues; Software version incompatibility. | Ensure correct USB/RS232 cable is used and securely connected. Install/update necessary drivers. Verify software compatibility with your operating system. |
| "PASS/FAIL" indication is incorrect. | Incorrect test limits set; Device under test does not meet standards. | Review the configured test limits in the instrument settings. Re-evaluate the installation or device being tested against relevant standards. |
6. Especificacions
| Atribut | Detall |
|---|---|
| Marca | Metrel |
| Model | MI 3102 BT EurotestXE |
| Tipus de mesura | Multímetre |
| Min. Vol. Operatiutage | 50 volts (CC) |
| Font d'alimentació | Funciona amb bateria |
| Bateries | Necessites 6 piles AA (incloses) |
| Especificació Met | IEC / EN 61557 |
| ASIN | B07T4D7GYN |
| Data de primera disponibilitat | 24 d'agost de 2020 |
7. Garantia i Suport
7.1 Garantia del producte
The Metrel MI 3102 BT EurotestXE comes with a two-year (24-month) warranty del fabricant. Aquesta garantia cobreix els defectes de materials i de fabricació en condicions d'ús normal. Conserveu el comprovant de compra per a reclamacions de garantia.
The warranty does not cover damage caused by misuse, unauthorized modifications, accidents, or failure to follow the instructions in this manual. For specific warranty terms and conditions, refer to the documentation included with your product or contact Metrel customer service.
7.2 Atenció al client
For technical assistance, troubleshooting beyond this manual, or warranty service, please contact Metrel customer support. Contact information can typically be found on the manufacturer's official website or in the documentation provided with your instrument.
When contacting support, please have your product model number (MI 3102 BT EurotestXE) and serial number (if applicable) ready to expedite the service process.