Sure-Lites EBP500

Sure-Lites EBP500 1-Lamp Emergency Battery Pack Instruction Manual

Model: EBP500

1. Introducció

This manual provides detailed instructions for the installation, operation, and maintenance of the Sure-Lites EBP500 1-Lamp Emergency Battery Pack. This unit is designed to provide emergency power to fluorescent lamps in the event of a power failure, ensuring illumination for safety and egress.

Si us plau, llegiu aquest manual detingudament abans de la instal·lació i l'ús per garantir el funcionament correcte i la seguretat.

2. Instruccions de seguretat importants

Quan utilitzeu equips elèctrics, sempre s'han de seguir les precaucions bàsiques de seguretat, incloses les següents:

3. Components del producte

The Sure-Lites EBP500 Emergency Battery Pack is a compact unit designed for integration into fluorescent lighting fixtures. Below is an image illustrating the key features of the device.

Sure-Lites EBP500 Emergency Battery Pack with wiring terminals and labels

Figura 1: Sure-Lites EBP500 Emergency Battery Pack. This image shows the elongated, rectangular battery pack with a metal casing. Visible labels include "EBP500 EMERGENCY BATTERY PACK", "120/240/277 VAC", "60Hz", "34W", "260mA", and a "UL LISTED" certification mark. Wiring terminals with color-coded connections (yellow, blue, red, black, white) are clearly visible at one end, along with a small connector for the test switch/indicator light.

Els components clau inclouen:

4. Configuració i instal·lació

Installation should only be performed by a qualified electrician in accordance with the National Electrical Code and local regulations.

4.1 Comprovacions prèvies a la instal·lació

4.2 Instruccions de cablejat

Refer to the wiring diagram provided with your fixture and the EBP500 unit for specific connections. General steps include:

  1. Mount the EBP500 unit securely within the fixture or in an adjacent accessible location.
  2. Disconnect the normal AC ballast from the lamp(s) as per the wiring diagram.
  3. Connect the EBP500's input wires to the unswitched AC power source (Line and Neutral).
  4. Connect the EBP500's output wires to the lamp(s) according to the diagram, ensuring proper polarity.
  5. Connect the remote test switch and indicator light to the designated connector on the EBP500. Mount the test switch/indicator light in an accessible location on the fixture.
  6. Once all wiring is complete, connect the battery connector to the EBP500 unit.

4.3 Càrrega inicial

After installation, restore AC power to the fixture. The EBP500 requires a minimum of 24 hours of continuous AC power to fully charge the battery before it can provide its rated emergency duration.

5. Instruccions de funcionament

5.1 Funcionament normal

When AC power is present, the EBP500 unit is in standby mode, continuously charging its battery. The indicator light (if installed) will be illuminated, signifying that the battery is charging and ready for emergency operation.

5.2 Funcionament d'emergència

Upon interruption of normal AC power, the EBP500 automatically switches to emergency mode, providing power to the connected fluorescent lamp(s) for a minimum of 90 minutes. The indicator light will turn off during emergency operation.

5.3 Testing the Unit

To test the emergency function, press and hold the test switch. The connected lamp(s) should illuminate, and the indicator light should turn off. Release the test switch to return to normal operation. Regular testing is recommended as per local codes (e.g., monthly 30-second tests, annual 90-minute tests).

6. Manteniment

The EBP500 requires minimal maintenance. However, periodic checks are essential to ensure proper operation.

7. Solució De Problemes

ProblemaCausa possibleSolució
Emergència lamp does not illuminate during test or power failure.
  • No AC power to the unit.
  • La bateria no està completament carregada.
  • Defectuós lamp.
  • Cablejat incorrecte.
  • Battery pack failure.
  • Comproveu el disjuntor i les connexions del cablejat.
  • Allow 24 hours for initial charge.
  • Substitueix lamp.
  • Verifiqueu el cablejat amb el diagrama.
  • Replace the entire EBP500 unit.
Indicator light is off during normal AC power.
  • No AC power to the unit.
  • Indicator light or wiring faulty.
  • Battery pack failure.
  • Check AC power supply.
  • Check indicator light connections.
  • Replace the entire EBP500 unit.
Emergència lamp duration is less than 90 minutes.
  • La bateria no està completament carregada.
  • Battery pack nearing end of life.
  • Ensure 24-hour charge time.
  • Replace the entire EBP500 unit.

Si els passos de resolució de problemes no resolen el problema, poseu-vos en contacte amb el personal de servei qualificat.

8. Especificacions

9. Garantia i Suport

For warranty information or technical support, please contact Sure-Lites customer service. Refer to the product packaging or the Sure-Lites official website for contact details. Please have your model number (EBP500) and purchase date available when contacting support.

This product is designed for long-term reliability when installed and maintained correctly. Adherence to the instructions in this manual will help ensure optimal performance.

Documents relacionats - EBP500

Preview Controlador LED d'emergència Sure-Lites EBPLEDL6SF: especificacions i dades del producte
Especificacions detallades, característiques i dades d'instal·lació per al controlador LED d'emergència Sure-Lites EBPLEDL6SF de Cooper Lighting Solutions. Inclou el producteview, dades tècniques, certificacions i dibuixos dimensionals.
Preview Manual d'instal·lació del balast d'emergència Sure-Lites EBP1400NCX/NCF
Guia completa d'instal·lació, funcionament i manteniment dels balasts d'emergència Sure-Lites EBP1400NCX i EBP1400NCF, que detalla les precaucions de seguretat, els diagrames de cablejat i la informació.amp compatibilitat.
Preview Sure-Lites EBPLED Emergency Battery Packs: 7W & 14W LED Emergency Lighting
Datasheet for Sure-Lites EBPLED series LED emergency battery packs. Features 90-minute run time, constant wattage output, LiFePO4 battery, and UL 924 compliance for 7W and 14W models, suitable for various commercial applications.
Preview Llum d'emergència de la sèrie APEL de Sure-Lites
Exploreu la llum d'emergència Sure-Lites de la sèrie APEL, que inclou la certificació UL 924, 90 minuts de funcionament, capçals LED ajustables i una bateria de níquel-cadmi resistent. Ideal per a una sortida d'emergència fiable amb opcions de capacitat remota.
Preview Sure-Lites EBPLEDL6SF Emergency LED Driver - Technical Specifications and Features
Detailed technical specifications, features, and application information for the Sure-Lites EBPLEDL6SF Emergency LED Driver by Cooper Lighting Solutions. Includes product overview, certifications, dimensions, and warranty.
Preview Sistema d'il·luminació d'emergència connectat Sure-Lites FirstLink | Cooper Lighting Solutions
Exploreu el sistema d'il·luminació d'emergència connectat Sure-Lites FirstLink de Cooper Lighting Solutions. Aquest fullet detalla les característiques del sistema, el maquinari, el control d'aplicacions i els plans de servei dissenyats per a la seguretat dels edificis i el compliment de la normativa.