POTTER VSR 4

POTTER VSR-4 - Vane Type Water Flow Alarm Switch

Model: VSR 4 | Brand: POTTER

1. Introducció

The POTTER VSR-4 is a vane type water flow alarm switch designed for use on 4-inch pipes. This device is engineered to detect sustained water flow in sprinkler systems, triggering an alarm signal to indicate activation of the fire suppression system. It is an essential component for fire safety installations, providing reliable flow detection.

POTTER VSR-4 Vane Type Water Flow Alarm Switch

Image 1.1: The POTTER VSR-4 Vane Type Water Flow Alarm Switch. This image shows the red control housing mounted on a grey pipe clamp assembly, with the vane visible within the clamp.

2. Configuració i instal·lació

Proper installation of the VSR-4 switch is crucial for its correct operation and compliance with safety standards. Installation should only be performed by qualified personnel in accordance with all applicable national and local codes and standards, including NFPA 13, 72, and 25.

2.1 Comprovacions prèvies a la instal·lació

2.2 Passos d'instal·lació

  1. Aïllament del sistema: Shut off the water supply and drain the pipe section where the switch will be installed.
  2. Preparació de canonades: Clean the exterior of the pipe at the installation point. The VSR-4 is designed for horizontal or vertical pipe runs.
  3. Muntatge: Position the switch on the pipe, ensuring the vane is correctly oriented with the direction of water flow. The arrow on the switch housing indicates the required flow direction.
  4. Assegurament: Tighten the U-bolt nuts evenly to secure the switch firmly to the pipe. Do not overtighten.
  5. Cablejat: Connect the electrical wiring to the switch terminals according to the wiring diagram provided inside the switch enclosure. Ensure all connections are secure and comply with electrical codes. The VSR-4 is a corded electric device.
  6. Restauració del sistema: Slowly restore water pressure to the system, checking for leaks around the switch.
  7. Prova: Perform initial operational tests as described in the "Operation" section to confirm proper functionality.

3. Funcionament

The POTTER VSR-4 operates by detecting a sustained flow of water through the pipe. When water flows at or above a specified rate, the vane inside the pipe is displaced, activating a set of contacts within the switch enclosure. This activation sends a signal to a connected fire alarm control panel or other monitoring device.

3.1 Activació d'alarma

3.2 Testing the Switch

Regular testing is essential to ensure the VSR-4 is functioning correctly. Refer to NFPA 25 for specific testing frequencies and procedures.

  1. Notify Authorities: Inform the fire department or monitoring station that a test is being conducted to avoid false alarms.
  2. Iniciar el flux: Open the inspector's test connection or a drain valve downstream of the flow switch to create a sustained water flow.
  3. Observe Alarm: Verify that the flow switch activates and sends an alarm signal to the control panel within the specified delay time.
  4. Restore System: Close the test connection or drain valve. The alarm should reset once water flow ceases.
  5. Notify Authorities: Inform the fire department or monitoring station that the test is complete.

4. Manteniment

Routine maintenance helps ensure the long-term reliability of the POTTER VSR-4. All maintenance should be performed by qualified personnel.

Do not attempt to disassemble the switch or repair internal components. If the switch is found to be faulty, it should be replaced by a new unit.

5. Solució De Problemes

This section provides guidance for common issues encountered with the VSR-4 water flow alarm switch. For complex problems, contact a qualified fire protection technician.

ProblemaCausa possibleSolució
Switch does not alarm during flow test.
  • Flux d'aigua insuficient.
  • Cablejat incorrecte.
  • Interruptor defectuós.
  • Vane obstruction.
  • Ensure adequate flow rate is achieved.
  • Verifiqueu el cablejat amb el diagrama.
  • Replace the switch if faulty.
  • Inspect for debris obstructing the vane (requires system isolation).
False alarms or intermittent alarms.
  • Water surges/pressure fluctuations.
  • Improper delay setting.
  • Muntatge fluix.
  • Check for system pressure issues.
  • Adjust delay setting if applicable (refer to manufacturer's instructions).
  • Ensure switch is securely mounted.
No hi ha alimentació a l'interruptor.
  • L’interruptor automàtic s’ha disparat.
  • Connexió elèctrica solta.
  • Comproveu i reinicieu l'interruptor.
  • Inspect and secure power connections.

6. Especificacions

AtributDetall
MarcaCERERAR
Número de modelVSR 4
DescripcióVane Type Water Flow Alarm Switch for 4" Pipe
Tipus de sensorFotoelèctric
Tipus d’alarmaAlarma de cabal d'aigua
Font d'alimentacióElèctric amb cable
Compatibilitat de canonades4-inch (Nominal)
UPC767571885695
FabricantCERERAR

7. Informació de la garantia

Specific warranty terms for the POTTER VSR-4 are provided by the manufacturer. Please refer to the documentation included with your purchase or visit the official POTTER website for detailed warranty coverage, terms, and conditions. Retain your proof of purchase for warranty claims.

8. Atenció al client

For technical assistance, troubleshooting beyond this manual, or inquiries regarding your POTTER VSR-4, please contact the manufacturer's customer support or your authorized distributor. Ensure you have your product model number (VSR 4) and any relevant purchase details ready when contacting support.

You may find contact information on the official POTTER weblloc web o a través del venedor a qui vau comprar el producte.

Documents relacionats - VSR 4

Preview Guia d'instal·lació de l'interruptor d'alarma de flux d'aigua a prova d'explosió Potter VSR-FEX tipus paleta
This document provides detailed installation, operation, testing, and technical specifications for the Potter VSR-FEX Explosion Proof Vane Type Waterflow Alarm Switch, designed for use in hazardous locations and wet sprinkler systems.
Preview Interruptor d'alarma de flux d'aigua tipus paleta Potter VSR amb retard: instal·lació, especificacions i funcionament
Comprehensive guide to the Potter VSR Vane Type Waterflow Alarm Switch with Retard. Covers product specifications, ordering information, installation procedures, testing requirements, and maintenance. Approved by UL, CUL, FM, LPCB, CE, and VdS for wet sprinkler systems.
Preview Interruptor d'alarma de flux d'aigua tipus paleta Potter VSR-ST: instal·lació i especificacions
Guia completa de l'interruptor d'alarma de flux d'aigua tipus paleta Potter VSR-ST, que detalla les seves especificacions, procediments d'instal·lació, requisits de prova, manteniment i desmuntatge per a sistemes d'aspersors d'incendis de canonades petites.
Preview Potter VSR-C Vane Type Waterflow Alarm Switch with Retard for Copper Pipe
Technical specifications, installation, testing, and maintenance guide for the Potter VSR-C vane type waterflow alarm switch designed for copper pipe sprinkler systems. Includes details on service pressure, flow sensitivity, contact ratings, enclosure, and environmental specifications.
Preview Potter VSR-S Vane Type Waterflow Alarm Switch with Retard Installation and Operation Manual
This document provides detailed instructions for the installation, operation, and maintenance of the Potter VSR-S Vane Type Waterflow Alarm Switch with Retard. It covers features, technical specifications, electrical connections, testing procedures, and replacement parts for the VSR-S model.
Preview Potter VSG Low Flow Rate Waterflow Switch with Electronic Retard - Technical Specifications and Installation
Detailed technical specifications, installation guide, and wiring diagrams for the Potter VSG Low Flow Rate Vane Type Waterflow Switch with Electronic Retard, designed for water mist systems.