REFCO Gobi II

REFCO Gobi II Universal Vol.tagManual d'instruccions de la bomba d'eliminació de condensats

Model: Gobi II

1. Introducció

The REFCO Gobi II is a high-performance condensate removal pump designed for use with air conditioning systems ranging from 6,000 Btu/H (1.75kW) up to 120,000 Btu/H (35 kW). It features a digital water sensor, universal voltage compatibility, and user-configurable flow settings, making it suitable for various HVAC applications.

Important Note: REMOVE ALL OLD WIRING. New power and alarm wires are included with this pump. These new wires MUST be used and properly grounded during installation. Pump wiring has been updated from all previous versions.

REFCO Gobi II Condensate Pump and Accessories

Image 1: REFCO Gobi II Condensate Pump with included power cables and discharge tubing.

2. Configuració i instal·lació

Proper installation is crucial for the safe and efficient operation of the Gobi II pump. Refer to the detailed wiring diagram and follow all local electrical codes.

2.1 Instruccions de cablejat

The Gobi II pump utilizes a new wiring configuration. It is imperative to replace any existing wiring with the new power and alarm wires provided. Ensure all connections are secure and correctly grounded.

Wiring diagram for REFCO Gobi II Condensate Pump showing new power and alarm wire connections

Image 2: Wiring diagram illustrating the new power and alarm wire connections for the Gobi II pump. Old wiring must be removed and replaced with the new, grounded wires.

2.2 Col·locació

The pump is designed for under A/C unit mounting. Consider the maximum suction height of 10 ft (3 m) and maximum head of 65.6 ft (20 m) when determining the pump's location relative to the condensate source and discharge point.

2.3 Discharge Line Connection

Connect the provided 1/4" I.D. (6.25 mm) discharge tube to the pump's outlet. Ensure the tube is routed without kinks or sharp bends to allow for unobstructed condensate flow.

3. Instruccions de funcionament

The Gobi II pump operates automatically based on its digital water sensor. Once properly installed and powered, it will activate to remove condensate when the water level in the reservoir reaches a predetermined point.

  • Funcionament automàtic: The pump's digital sensor detects condensate levels and initiates pumping cycles as needed.
  • User-Configurable Flow: The pump features user-configurable flow settings to optimize performance for various AC unit capacities. Refer to the specific configuration guide for detailed instructions on adjusting flow settings.
  • Funcionament silenciós: The pump is designed for quiet operation, typically producing 20dBA at 3 ft (1 m) distance.

4. Manteniment

Regular maintenance ensures the longevity and optimal performance of your Gobi II condensate pump.

  • Neteja del sensor: Periodically inspect and gently clean the digital water sensor to prevent buildup that could affect its accuracy. Disconnect power before cleaning.
  • Reservoir Inspection: Check the pump's reservoir for any debris or sludge accumulation. Clean as necessary to maintain clear operation.
  • Discharge Line Check: Ensure the discharge line remains clear of obstructions and kinks. Verify that water is flowing freely from the discharge point.

5. Solució De Problemes

If you encounter issues with your Gobi II pump, refer to the following troubleshooting guide:

ProblemaCausa possibleSolució
La bomba no funcionaNo power; Sensor malfunction; Motor failureCheck power supply and connections; Clean sensor; Contact qualified technician if motor is suspected to be faulty.
Pump running continuously or too frequentlySensor dirty or faulty; Air in suction line; Leak in systemClean sensor; Check for air leaks in suction line; Inspect AC unit for excessive condensate production or leaks.
Water overflow from AC unit or pumpDischarge line blocked or kinked; Pump failure; Sensor not activating pumpClear discharge line; Check pump operation; Clean or replace sensor.
Excessive noise or gurglingAir in pump or lines; Improper installation; Debris in pumpBleed air from system; Ensure proper mounting and level installation; Inspect for and remove debris.

6. Especificacions

  • Model: Gobi II
  • Cabal màxim: 11 GPH (42 l/h)
  • Succió màxima: 10 ft (3 m) self-priming
  • Capçalera màxima: 65.6 peus (20 m)
  • Nivell de so: 20dBA at 3 ft (1 m) / 19dBA at 1 EN ISO 3744:2010
  • Voltage: 100 ~ 240 VAC 50/60 Hz (auto sensing universal power input)
  • Consum d'energia: 8 watts (during maximum operation at 110V)
  • Relé d'alarma: 10 Amps NO/NC contacts with integrated replaceable HRC 10A fuse 5 × 20 mm
  • Pes: 1.3 Lbs. (600g)
  • Discharge Tube: 1/4" I.D. (6.25 mm) × 3.3 ft (1 m)
  • Protecció: Class II double insulation, Fully potted, IP-44
  • Temperatura de funcionament: Ambient 37.5°F to 104°F (3°C to 40°C) / Water 41°F to 77°F (5°C to 25°C)
  • Compliment: Conforms to UL:778 and certified to CSA C22.2#68
  • Dimensions del producte: 11.3 cm de llargada x 2.09 cm d'amplada x 2.09 cm d'alçada
  • Material: Plàstic

7. Garantia i Suport

For warranty information and technical support, please refer to the documentation provided with your purchase or contact REFCO directly through their official website or authorized distributors. Keep your proof of purchase for warranty claims.

Documents relacionats - Gobi II

Preview Manual d'instal·lació i funcionament de la bomba de condensats Gobi II
Guia completa per a la bomba de condensats REFCO Gobi II, que cobreix la instal·lació, el funcionament, el manteniment i la resolució de problemes dels sistemes HVAC/R.
Preview Manual d'instal·lació i funcionament de la bomba de condensats REFCO Gobi II
A comprehensive guide to the REFCO Gobi II condensate pump, detailing installation, operation, safety precautions, technical specifications, and troubleshooting. Features include configurable quiet mode, diagnostic LED, USB connectivity, and broad application range.
Preview Bomba de condensats REFCO GOBI II: Guia d'instal·lació ràpida
Guia ràpida oficial per a la bomba de condensats REFCO GOBI II (model 3004145). Proporciona informació essencial sobre la instal·lació, el funcionament, la seguretat i el manteniment per a una eliminació eficient de condensats en sistemes de climatització.
Preview Manual d'instal·lació i tècnic de la bomba de condensats universal combinada REFCO 3004146
Aquest document proporciona informació completa sobre la instal·lació, les especificacions tècniques, les directrius de seguretat i la resolució de problemes de la bomba de condensats universal combinada REFCO (model 3004146).
Preview Refco VAMP-F Manual d'instruccions de la bomba de condensats
Aquest document proporciona instruccions completes per a la instal·lació, el funcionament, el manteniment i la resolució de problemes del Refco V.AMPBomba de condensats -F. Inclou directrius de seguretat, especificacions i informació sobre les peces.
Preview REFCO VAMPManual d'instruccions de la bomba de condensats -X
Aquest manual d'instruccions proporciona informació detallada sobre el REFCO V.AMPBomba de condensats -X, que cobreix les seves especificacions, instal·lació, funcionament, manteniment, directrius de seguretat i resolució de problemes. Disponible en anglès, alemany, francès, italià i castellà.