YORK 3 Ton, 1/8 Inch El, R-410A

York Thermal Expansion Valve User Manual

Model: 3 Ton, 1/8 Inch El, R-410A

1. Introducció

This manual provides essential information for the proper installation, operation, and maintenance of the York Thermal Expansion Valve (TXV). This genuine OEM part is designed to ensure optimal performance and reliability in compatible R-410A refrigerant systems. Please read this manual thoroughly before proceeding with any procedures.

2. Producte acabatview

The York Thermal Expansion Valve is a critical component in refrigeration and air conditioning systems. Its primary function is to regulate the flow of liquid refrigerant into the evaporator while maintaining a constant superheat at the evaporator outlet. This specific model is rated for 3-ton capacity and features a 1/8 inch equalizer line connection, designed for use with R-410A refrigerant.

York Thermal Expansion Valve with copper tubing and mounting bracket

An image showing the York Thermal Expansion Valve, featuring its brass body, coiled copper sensing bulb capillary tube, and a metal mounting bracket with a screw. The valve is designed for R-410A refrigerant systems.

3. Informació de seguretat

4. Configuració i instal·lació

Proper installation is crucial for the efficient operation of the TXV. This procedure should only be carried out by a certified HVAC professional.

  1. Despressurització del sistema: Ensure the refrigeration system is completely depressurized and evacuated before beginning installation.
  2. Col·locació de la vàlvula: Install the TXV in the liquid line just upstream of the evaporator. Ensure the flow direction arrow on the valve body matches the refrigerant flow.
  3. Brazing Connections: Use appropriate brazing techniques and materials for R-410A systems. Protect the valve body from excessive heat during brazing to prevent internal damage.
  4. Equalizer Line Connection: Connect the 1/8 inch equalizer line from the TXV to the suction line, typically downstream of the evaporator and sensing bulb.
  5. Instal·lació de la bombeta sensora: Securely attach the sensing bulb to the suction line at the evaporator outlet. Ensure good thermal contact by cleaning the pipe surface and using a clamp. Insulate the bulb to prevent ambient temperature interference.
  6. Prova de fuites: After installation, perform a thorough leak test on all connections using an appropriate leak detector.
  7. Evacuació i càrrega: Evacuate the system to a deep vacuum and then charge with the correct amount of R-410A refrigerant according to the system manufacturer's specifications.

5. Principis de funcionament

The Thermal Expansion Valve operates by balancing forces to control refrigerant flow. The primary forces are:

When the superheat at the evaporator outlet increases, the sensing bulb temperature rises, increasing its internal pressure. This pressure overcomes the combined evaporator and spring pressures, opening the valve further to allow more refrigerant into the evaporator. Conversely, if superheat decreases, the bulb pressure drops, causing the valve to close slightly, reducing refrigerant flow. This continuous modulation ensures efficient heat transfer and protects the compressor from liquid slugging.

6. Manteniment

The York TXV is designed for long-term reliability. Regular system maintenance by a qualified technician is recommended to ensure its continued optimal performance.

7. Solució De Problemes

If the refrigeration system is not performing as expected, the TXV may be a contributing factor. Troubleshooting should be performed by a qualified technician.

SímptomaCausa possibleAcció
High Superheat, Low Suction PressureTXV stuck closed or restricted; low refrigerant charge; dirty evaporator coil.Check refrigerant charge; clean evaporator; inspect TXV for blockage or failure.
Low Superheat, High Suction Pressure (Liquid Slugging)TXV stuck open; sensing bulb loose or uninsulated; oversized TXV.Re-secure/insulate sensing bulb; inspect TXV for failure; verify correct TXV sizing.
Fluctuating Superheat/Suction PressureMoisture in system; non-condensables; improper sensing bulb contact.Evacuate and recharge system; check sensing bulb installation.
External Refrigerant LeakLoose connections; damaged valve body or capillary tube.Locate and repair leak; replace TXV if damaged.

Always consult with a professional HVAC technician for accurate diagnosis and repair of TXV-related issues.

8. Especificacions

9. Informació de la garantia

This York Thermal Expansion Valve is a genuine OEM part. Warranty coverage for this product is typically provided by the manufacturer, York, against defects in materials and workmanship. Specific warranty terms, duration, and conditions may vary. Please retain your proof of purchase and contact your seller or the official York customer support for detailed warranty information and claims procedures.

10. Informació de suport

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact:

Documents relacionats - 3 Ton, 1/8 Inch El, R-410A

Preview YORK Sun Premier Rooftop Units 25-50 Ton Installation and Maintenance Manual
Detailed installation and maintenance guide for YORK Sun Premier 25-50 Ton Rooftop Units (RTUs). Covers unit specifications, installation procedures, electrical requirements, safety protocols, and routine maintenance for optimal performance.
Preview YORK 50-65 Ton Single Package Rooftop Units Engineering Guide
Explore the YORK 50-65 Ton Single Package Rooftop Units (YPAL series) with this comprehensive engineering guide. Discover features, specifications, and application details for efficient cooling and heating solutions, including R-410A refrigerant compatibility.
Preview YORK Sun Choice HV13 to HV25 Technical Guide
Comprehensive technical guide for YORK Sun Choice HV13 to HV25 HVAC units, detailing specifications, features, options, performance data, and electrical information for commercial applications.
Preview YORK YLAA Air-Cooled Scroll Chiller Style B: Pack Sheet and Safety Information
This pack sheet for the YORK YLAA Air-Cooled Scroll Chiller Style B provides essential legal, warranty, safety, and installation information for units using R-410A and R-454B refrigerants.
Preview YORK 15-25 Ton Single Package Air Conditioner Gas/Electric & Electric/Electric Service Manual
Comprehensive user, maintenance, and service information manual for YORK 15-25 Ton Single Package Air Conditioner units (Gas/Electric & Electric/Electric). Covers safety, system operation, maintenance procedures, troubleshooting, and owner information.
Preview YORK Altair High Wall Inverter R-410A 60Hz 16SEER User Manual
User manual for the YORK Altair High Wall Inverter air conditioner (R-410A, 60Hz, 16 SEER), covering installation, operation, maintenance, safety precautions, and troubleshooting.