GEYA GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

GEYA GRD9L-R Automatic Reclosing Device User Manual

Model: GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

1. Producte acabatview

The GEYA GRD9L-R Automatic Reclosing Device is an electromagnetic leakage circuit breaker (RCCB) designed to enhance electrical system reliability and reduce manual intervention. It automatically recloses the circuit when a leakage fault causes the RCD to trip unexpectedly, minimizing downtime and maintenance costs.

This device is suitable for various applications, including electrical network terminal lines, meter boxes, new energy circuit management, solar PV control boxes, smart electricity systems, smart homes, and charging stations for new energy vehicles.

Característiques principals:

  • Automatic reclosing function after RCD trip, eliminating the need for manual reset.
  • Integrated 3 reclosing attempts. An auxiliary contact can send an alarm if continuous tripping occurs within 15 minutes.
  • Manual/Automatic selector switch for operational flexibility.
  • Features double mechanical/electronic locking for enhanced safety.
  • Compatible with auxiliary contacts, alarm contacts, shunt releases, and undervoltage releases.
  • Reclosing attempt counter resets if no trip occurs or after a manual reset within 15 minutes of successful reclosure.
GEYA GRD9L-R Automatic Reclosing Device

Figura 1: Frontal view of the GEYA GRD9L-R Automatic Reclosing Device.

2. Informació de seguretat

ADVERTIMENT: Installation and maintenance of this device must be performed by a qualified electrician in accordance with all local and national electrical codes and regulations. Failure to do so may result in electric shock, fire, or other serious injury.

  • Desconnecteu sempre l'alimentació abans d'instal·lar, revisar o desmuntar el dispositiu.
  • Assegureu-vos de la connexió a terra correcta del sistema elèctric.
  • No feu funcionar el dispositiu si sembla que està danyat.
  • Verify correct wiring connections to prevent malfunction or damage.
  • El dispositiu està dissenyat per a un volum específictage and current ratings. Do not exceed these limits.

3. Product Components and Diagrams

3.1 Descripció de la funció

Function Description Diagram

Figure 2: Diagram illustrating the automatic reclosing logic and function description. The device attempts to reclose the circuit up to three times with specific time intervals. If the interval between two successful closings exceeds 15 minutes, the program clears the accumulated closing times.

3.2 Functions Diagram (Auto Mode Logic)

Functions Diagram Auto Mode

Figure 3: Detailed flow chart of the automatic reclosing sequence. After a trip, the device attempts to reclose. If successful, it waits. If it trips again, it attempts a second reclose after 10 seconds. A third attempt follows after 60 seconds if the second fails. If all three attempts fail within 15 minutes, the device locks out and sends an auxiliary alarm. The power delay (Tr) is 2 seconds. Note: Customization of closing times and delay times requires contacting the manufacturer.

3.3 Funció de bloqueig

Locking Function Diagram

Figure 4: Illustration of the locking mechanism. When the locking function is activated (e.g., by inserting a padlock with a diameter less than 3.5 mm), the RCCB cannot be closed, ensuring safety during circuit checks or maintenance. This prevents accidental reclosure.

4. Configuració i instal·lació

The GEYA GRD9L-R device is designed for DIN rail mounting and can be integrated with other electrical components such as an RCCB and auxiliary modules.

4.1 Component Integration

Component Integration Diagram

Figura 5: Example of how the GRD9L-R device can be installed alongside an Auxiliary module and an RCCB on a standard DIN rail. Ensure proper alignment and secure fastening of all components.

4.2 Esquema de cablejat

Diagrama de cablejat Example

Figura 6: Un example application wiring diagram. This diagram shows the connection of the GRD9L-R device with an alarm lamp, an RCCB, and multiple load circuits. Red lines indicate live connections, blue lines indicate neutral connections. The auxiliary contacts (A1, A2, COM, NO) are used for external signaling, such as an alarm lamp. Always consult a qualified electrician for correct wiring specific to your installation.

4.3 Passos d'instal·lació (directrius generals):

  1. Desconnexió d'alimentació: Ensure the main power supply to the circuit is completely disconnected before beginning installation.
  2. Muntatge: Mount the GRD9L-R device, the associated RCCB, and any auxiliary modules onto a standard DIN rail within an appropriate electrical enclosure.
  3. Cablejat: Connect the input and output terminals of the GRD9L-R and RCCB according to the wiring diagram (Figure 6) and local electrical codes. Pay close attention to live (L) and neutral (N) connections.
  4. Connexions auxiliars: If using, connect auxiliary contacts (A1, A2, COM, NO) for remote signaling or control, such as an alarm lamp.
  5. Verificació: Double-check all wiring connections for tightness and correctness.
  6. Restauració d'energia: Un cop finalitzada i verificada la instal·lació, restableix l'alimentació del circuit.

5. Instruccions de funcionament

5.1 Manual/Automatic Selector

The device features a selector switch labeled "AUTO" and "MANU" (Manual). This switch allows you to choose the operating mode:

  • Mode AUTOMÀTIC: In this mode, the device will automatically attempt to reclose the associated RCCB after a trip, following the reclosing logic described in Figure 3. This is the default and recommended mode for continuous operation.
  • MANU Mode: In this mode, the automatic reclosing function is disabled. If the RCCB trips, it must be manually reset. This mode is useful for maintenance or specific operational requirements where automatic reclosure is not desired.

5.2 Reclosing Logic (Auto Mode)

When in AUTO mode, the device follows a specific sequence of reclosing attempts:

  1. 1st Trip: If the RCD trips, the device waits for 10 seconds, then attempts to reclose.
  2. 2nd Trip: If the RCD trips again within 15 minutes of the first reclosure, the device waits for 60 seconds, then attempts a second reclosure.
  3. 3rd Trip: If the RCD trips a third time within 15 minutes of the second reclosure, the device waits for 300 seconds (5 minutes), then attempts a third reclosure.
  4. Bloqueig: If the RCD trips a fourth time within 15 minutes, or if any of the three reclosing attempts fail, the device enters a lockout state. It will not attempt further reclosures automatically and will activate the auxiliary alarm contact (if connected). Manual intervention is required to reset the device.
  5. Resetting Closing Times: If no trip occurs for 15 minutes after a successful reclosure, or if the device is manually reset, the reclosing attempt counter is cleared.

5.3 Botó de prova

The associated RCCB typically has a test button. Pressing this button simulates a leakage fault and should cause the RCCB to trip. This is used to verify the proper functioning of the RCCB and, in AUTO mode, the reclosing device.

6. Manteniment

The GEYA GRD9L-R Automatic Reclosing Device is designed for minimal maintenance. However, regular checks are recommended to ensure optimal performance and safety.

  • Inspecció visual: Inspeccioneu periòdicament el dispositiu per detectar qualsevol signe de danys físics, decoloració o connexions soltes.
  • Prova de funcionalitat: Regularly test the associated RCCB using its test button. Observe if the GRD9L-R device initiates its reclosing sequence in AUTO mode.
  • Neteja: Ensure the device is kept clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Inspecció professional: It is recommended to have the electrical system, including this device, inspected by a qualified electrician at least once a year.

7. Solució De Problemes

If the GEYA GRD9L-R device is not functioning as expected, consider the following:

ProblemaCausa possibleSolució
Device does not reclose automatically.
  • Device is in MANU mode.
  • Device is in lockout state after multiple failed reclosures.
  • Persistent fault in the circuit.
  • Locking function is activated.
  • Canvia al mode AUTO.
  • Manually reset the device and investigate the cause of repeated trips.
  • Identify and rectify the electrical fault.
  • Ensure no padlock is inserted in the locking mechanism.
Alarm contact is continuously active.
  • Device is in lockout state.
  • Auxiliary contact wiring issue.
  • Investigate and clear the fault, then manually reset the device.
  • Check wiring of auxiliary contacts.
RCCB trips immediately after reclosure.
  • Persistent or severe electrical fault (e.g., short circuit, ground fault).
  • Immediately disconnect power and have a qualified electrician diagnose and repair the fault. Do not attempt further reclosures until the fault is resolved.

If the problem persists after attempting these solutions, contact a qualified electrician or GEYA customer support.

8. Especificacions

CaracterísticaDetall
Número de modelGRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA
MarcaGEYA
Voltage220 volts de corrent altern
Corrent nominal63 A (as per model number)
Nombre de pols2
Tipus d'interruptorRCD (dispositiu de corrent residual)
Tipus de muntatgeWall Mount, Flush Mount (DIN Rail compatible)
Dimensions del paquet12 x 11.6 x 9.1 cm
Pes de l'article350 grams
FabricantZHEJIANG GEYA ELECTRICAL CO.,LTD

9. Garantia i Suport

Specific warranty information for the GEYA GRD9L-R Automatic Reclosing Device is not available in the provided product details. Please refer to the product packaging or contact GEYA customer support for detailed warranty terms and conditions.

For technical support, inquiries, or assistance with installation and troubleshooting, please contact GEYA directly through their official channels or the retailer from whom the product was purchased.

Documents relacionats - GRD9L-R-AC220V+A-SI RCCB 2P-63A-30mA

Preview Catàleg d'equips elèctrics GEYA: interruptors, contactors i més
Catàleg complet de productes elèctrics GEYA, incloent-hi interruptors automàtics en miniatura, contactors, interruptors de transferència i altres equips de seguretat, amb especificacions, aplicacions i estàndards de compliment.
Preview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Comprehensive instruction manual and technical guide for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications, features, technical specifications, installation, networking, troubleshooting, and dimension details for intelligent electrical systems.
Preview GEYA GRD9L-W WiFi Controlled MCB/RCCB/RCBO: Instruction Manual & Technical Guide
Detailed instruction manual for the GEYA GRD9L-W WiFi-controlled MCB/RCCB/RCBO. Covers applications in intelligent household electricity management and photovoltaic systems, function features, technical parameters, panel and wiring diagrams, installation, networking setup with Tuya Smart app, common faults, and dimensions. Essential guide for safe and efficient electrical control.
Preview GEYA Miniature Circuit Breakers, Contactors, and Transfer Switches Catalog | Technical Specifications
Comprehensive catalog from GEYA detailing Miniature Circuit Breakers (MCB), Residual Current Circuit Breakers (RCCB), Residual Current Circuit Breakers with Overcurrent Protection (RCBO), Molded Case Circuit Breakers (MCCB), AC Contactors, Automatic Transfer Switches, and Intelligent Circuit Breakers. Includes technical specifications, scope of application, product features, and compliance information for various models, serving industrial, commercial, and residential applications.
Preview Interruptor miniatura intel·ligent de la sèrie GEYA WiFi: instruccions d'ús
Instruccions d'ús detallades i preguntes freqüents per a l'interruptor miniatura intel·ligent de la sèrie GEYA WiFi (sèrie ZJSB9). Apreneu sobre la instal·lació, la configuració, la resolució de problemes, la seguretat i l'aplicació per a la protecció elèctrica de la llar intel·ligent.
Preview GEYA GPS8-10 Voltage/Current Protector Instruction Manual
Instruction manual for the GEYA GPS8-10 Voltage/Current Protector, detailing its applications, features, technical parameters, wiring, panel diagram, parameter settings, factory settings, and functional diagrams.