1. Introducció
This manual provides comprehensive instructions for the safe and effective operation of the Srliya ETCR3200C Double Clamp Ground Meter Test Tool. This device is designed for precise measurement of grounding resistance, soil resistivity, and AC current, utilizing various test methods including the double clamp method, three-wire, four-wire, and two-wire simple tests. Please read this manual thoroughly before use to ensure proper functionality and safety.
2. Informació de seguretat
Always adhere to the following safety precautions to prevent injury and damage to the instrument:
- Ensure the instrument is in good working condition before each use.
- Do not operate the device in wet environments or near flammable gases.
- Verify that all test leads and connections are secure and undamaged.
- Avoid touching live circuits during measurements.
- The device features battery voltage prompt and overload protection. Pay attention to these indicators.
- Only use accessories and replacement parts specified by the manufacturer.
- Keep the instrument away from strong electromagnetic fields.
3. Producte acabatview
3.1 Característiques clau
- Measures grounding resistance, DC resistance, AC current, and soil resistivity.
- Supports accurate test, simple test, selective test, double clamp method, three-wire, four-wire, and two-wire test methods.
- Constructed from high-quality, durable ABS material.
- Automatic shutdown after 10 minutes of inactivity to conserve power.
- Inclou bateria voltage prompt and overload protection for enhanced safety.
- USB interface for data upload, monitoring, saving, and printing.
- Data storage capacity for 300 groups of measurements.
3.2 Contingut del paquet

Figure 1: The ETCR3200C meter, two current clamps, four grounding stakes, test leads (red, black, green, yellow), USB cable, power adapter, and a carrying bag.
El paquet normalment inclou:
- ETCR3200C Double Clamp Ground Meter
- Two Current Clamps
- Four Grounding Stakes
- Set of Test Leads (Red, Black, Green, Yellow)
- Cable de comunicació USB
- Adaptador d'alimentació
- Bossa de transport
- Manual d'usuari (aquest document)
3.3 Disposició de l'instrument

Figure 2: The ETCR3200C meter housed in its protective yellow case, with the lid open revealing connection diagrams for various test methods.

Figure 3: Close-up of the ETCR3200C control panel, featuring the large digital display, rotary function selector, and various control buttons (HOLD, SET, TEST, AL, CLR, READ).
The ETCR3200C features a robust design with a clear digital display, a rotary switch for function selection, and dedicated buttons for operation. The inside of the protective case lid provides quick reference diagrams for different wiring configurations.
- Pantalla de visualització: Shows measurement values, units, and status indicators.
- Funció Interruptor rotatiu: Selects measurement modes (Grounding Resistance, Soil Resistivity, AC Current, etc.).
- Terminals d'entrada: Color-coded terminals for connecting test leads (E, ES, P, C, C1, C2).
- Botons de control:
- PROVA: Inicia una mesura.
- MANTENIR: Congela la lectura actual de la pantalla.
- SET: Accesses settings or parameters.
- AL (alarma): Manages alarm functions.
- CLR (Clear): Clears data or settings.
- LLEGIR: Recalls stored data.
- Port USB: For connecting to a computer for data transfer and monitoring.
- Entrada d'alimentació: Per carregar la bateria interna.
4. Configuració
4.1 Engegada/apagada
- To power on, rotate the function switch from the "OFF" position to any measurement mode.
- To power off, rotate the function switch to the "OFF" position.
- The device will automatically shut down after approximately 10 minutes of inactivity.
4.2 Càrrega de la bateria
Connect the provided power adapter to the instrument's power input port and plug it into a suitable power outlet. The battery indicator on the display will show charging status. Ensure the device is fully charged before extended use.
4.3 Connecting Test Leads and Accessories
Refer to the connection diagrams located on the inside of the instrument's lid (Figure 2) for specific wiring configurations based on the desired measurement method. Ensure all connections are firm and correct before proceeding with any test.

Figure 4: Essential accessories including grounding stakes, test leads, USB cable, and power adapter, used for various measurement setups.
5. Instruccions de funcionament
The ETCR3200C supports multiple measurement methods. Always select the appropriate method for your application and ensure correct wiring.
5.1 Grounding Resistance Measurement
The instrument offers several methods for grounding resistance measurement:
- Three-Wire/Four-Wire Method: This is the standard and most accurate method.
- Connect the test leads and grounding stakes according to the 3-wire or 4-wire diagram on the case lid.
- Rotate the function switch to the "Grounding Resistance" mode.
- Premeu el botó PROVA botó per iniciar la mesura.
- El resultat es mostrarà a la pantalla.
- Double Clamp Mètode: Used for measuring grounding resistance without disconnecting the ground system.
- Connect the two current clamps to the designated ports on the meter.
- Clamp one clamp around the grounding conductor to be tested and the other around an auxiliary grounding conductor.
- Select the "Double Clamp Method" on the rotary switch.
- Premeu PROVA.
- The grounding resistance will be displayed.
- Two-Wire Simple Test: For quick checks where high accuracy is not critical.
- Connect the test leads as per the 2-wire diagram.
- Select the "2-Wire Test" mode.
- Premeu PROVA.
5.2 Soil Resistivity Measurement (Quadrupole Method)
This method uses four grounding stakes (Winner method) to measure soil resistivity.
- Drive the four grounding stakes into the ground at equal distances in a straight line.
- Connect the test leads to the stakes and the meter's C1, P1, P2, C2 terminals according to the soil resistivity diagram.
- Set the electrode spacing range on the meter (1m to 100m).
- Rotate the function switch to "Soil Resistivity" mode.
- Premeu PROVA.
- The soil resistivity value (in Ωm) will be displayed.
5.3 Mesura de corrent altern
The ETCR3200C can also measure AC current up to 600.0A.
- Rotate the function switch to "AC Current" mode.
- Open the jaws of the current clamp i clamp it around the conductor carrying the AC current.
- The AC current value will be displayed automatically.
5.4 Data Storage and Communication
- The meter can store up to 300 groups of measurement data.
- Utilitza el LLEGIR button to recall stored data.
- Connect the meter to a computer via the USB interface using the provided cable.
- Utilize the monitoring software (if provided by the manufacturer) to upload, save, and print data.
6. Manteniment
- Neteja: Wipe the instrument with a soft, damp tela. No utilitzeu netejadors abrasius ni dissolvents.
- Emmagatzematge: Store the meter and its accessories in the provided carrying bag in a cool, dry place, away from direct sunlight and extreme temperatures.
- Cura de la bateria: Recarrega la bateria regularment, fins i tot si el dispositiu no s'utilitza amb freqüència, per mantenir-ne l'estat.
- Calibració: For continued accuracy, periodic calibration by qualified personnel is recommended.
7. Solució De Problemes
If you encounter issues with your ETCR3200C, consider the following:
- Sense energia: Check battery charge. Ensure the function switch is not in the "OFF" position.
- Lectures inexactes:
- Verify test lead connections are secure and correct for the selected method.
- Ensure grounding stakes are properly inserted into the ground.
- Check for environmental interference or poor contact.
- Consider battery level; low battery can affect accuracy.
- "OL" o Indicació de sobrecàrrega: The measured value exceeds the instrument's range. Check the circuit or select a different range if available.
- Problemes de visualització: If the display is blank or erratic, try restarting the device. If the problem persists, contact support.
For persistent issues not resolved by these steps, contact customer support.
8. Especificacions
| Paràmetre | Especificació |
|---|---|
| Model | ETCR3200C |
| Mètodes de mesura | Grounding Resistance: Rated current pole changing method Soil Resistivity: Quadrupole method (Winner method) AC Current: Clamp mètode |
| Freqüència de prova | 128Hz/111Hz/105Hz/94Hz (AFC) |
| Corrent de prova de curtcircuit | AC 250mA maximum |
| Electrode Spacing Range | Approx. 1m ~ 100m (3.3ft ~ 328.1ft) |
| Grounding Resistance Range | 0.00Ω ~ 30.00kΩ |
| Soil Resistivity Range | 0.00Ωm ~ 9000kΩm |
| Interval de corrent de CA | AC 0mA ~ 600.0A |
| Temps de mesurament | Grounding/Soil Resistivity: Approx. 15 seconds/time |
| Measurement Cycles | > 5000 times (short-circuit test, 30s interval) |
| Interfície de comunicació | USB interface for software monitoring and data transfer |
| Emmagatzematge de dades | 300 groups (MEM storage indication, PULL symbol for full storage) |
| Apagat automàtic | Després de 10 minuts d'inactivitat |
| Font d'alimentació | Bateria interna recarregable |
| Dimensions (paquet) | 13.78 x 11.81 x 11.02 polzades |
| Pes (paquet) | 14.79 lliures |
9. Garantia i Suport
Specific warranty details for the Srliya ETCR3200C are not provided within this document. For warranty information, technical support, or service inquiries, please refer to the product packaging, the manufacturer's official weblloc web o poseu-vos en contacte amb el vostre punt de venda.
Manufacturer: Srliya