Diversitech CP-22LPT

Asurity by Diversitech CP-22LPT Low Profile Manual d'usuari de la bomba de condensats

Model: CP-22LPT

Introducció

This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Asurity by Diversitech CP-22LPT Low Profile Condensate Pump. This pump is designed to automatically evacuate condensate or water discharge from HVACR equipment, offering a vertical lift capability of up to 22 feet. Its low-profile design makes it suitable for installations in tight spaces.

Informació de seguretat

Llegiu atentament totes les instruccions abans de la instal·lació i el funcionament. Si no seguiu aquestes instruccions, podeu patir danys materials, lesions personals o la mort.

  • Risc elèctric: Disconnect power before servicing. This unit operates on 110 Volts. Ensure all electrical connections comply with local codes.
  • Perill d'aigua: This pump handles water. Ensure proper drainage and prevent water damage.
  • Instal·lació: Install the pump in a location where it is accessible for maintenance and inspection.
  • Ús previst: Use this pump only for its intended purpose of evacuating condensate from HVACR equipment.
  • Llistat UL: This product is UL listed, meeting electrical and mechanical safety standards for water pumps.

Contingut del paquet

Verifiqueu que hi hagi tots els elements abans de començar la instal·lació:

  • Asurity by Diversitech CP-22LPT Condensate Pump
  • 20 ft Clear Vinyl Tubing
  • 4 ft Safety Switch Wire (pigtail)

Producte acabatview

The Asurity CP-22LPT condensate pump features a compact design with advanced functionalities for reliable condensate removal.

Asurity CP-22LPT Condensate Pump with Clear Tubing

Imatge 1: The Asurity CP-22LPT low profile condensate pump shown with the included clear vinyl tubing. The pump features a red base and a black motor housing with ventilation slots and an outlet port.

Asurity CP-22LPT Condensate Pump with Tubing and Safety Switch Wire

Imatge 2: Un de dalt a baix view of the Asurity CP-22LPT condensate pump, accompanied by the coiled clear vinyl tubing and the yellow safety switch wire. This image highlights all primary components included with the unit.

lateral View of Asurity CP-22LPT Condensate Pump

Imatge 3: A side perspective of the Asurity CP-22LPT condensate pump, illustrating its low-profile design. This view emphasizes the compact dimensions suitable for installation in confined spaces.

Característiques principals:

  • LED Status Indicator Lights (Power, Run, Alarm)
  • Vibració Dampening System for quiet operation
  • Integrated Safety Switch with 4 feet of wire for air-handler shutdown
  • Pro baixfile design for tight installations
  • Metal mounting tabs for secure installation
  • Four inlet holes (with 3 poly covers for unused ports)
  • Float switch and duckbill-style check valve

Configuració i instal·lació

Proper installation is crucial for the pump's performance and longevity. Ensure all local electrical and plumbing codes are followed.

  1. Col·locació: Position the pump on a level surface near the HVACR unit. The low-profile design is ideal for tight spaces. Utilize the vibration dampening feet and metal mounting tabs for secure placement.
  2. Condensate Inlet Connection: Connect the condensate drain line from the HVACR unit to one of the pump's inlet holes. The pump has four inlet holes; seal any unused inlets with the provided poly covers.
  3. Connexió de la línia de descàrrega: Connect the 20 ft clear vinyl tubing to the pump's discharge outlet. Route the tubing upwards, ensuring it does not exceed the pump's 22 ft vertical lift capability, and then to a suitable drain point. Avoid kinks or sharp bends in the tubing. The integrated duckbill-style check valve prevents backflow.
  4. Connexió elèctrica: Connect the pump to a dedicated 110V power supply. Ensure the power source is off before making connections.
  5. Safety Switch Connection: Connect the 4 ft safety switch wire (pigtail) to the air-handler's shutdown circuit. This feature is designed to shut down the HVACR unit if the pump fails or the water level rises too high, preventing overflow. Refer to your HVACR unit's manual for specific wiring instructions for the safety switch.
  6. Prova: After installation, manually pour water into the pump's reservoir to verify proper operation. The pump should activate, discharge the water, and then shut off. Check for any leaks.

Instruccions de funcionament

The Asurity CP-22LPT condensate pump operates automatically once properly installed and powered.

  • When condensate water enters the pump's reservoir and reaches a predetermined level, the internal float switch activates the pump.
  • The pump will then discharge the water through the connected vinyl tubing to the designated drain.
  • Once the water level drops, the float switch deactivates the pump.
  • Indicadors LED:
    • Pwr (Power): Illuminates when the pump is receiving electrical power.
    • Executar: Illuminates when the pump motor is actively discharging water.
    • Alrm (Alarm): Illuminates if the water level rises to the high-level alarm switch, indicating a potential issue and activating the safety shutdown circuit.

Manteniment

Un manteniment regular garanteix un rendiment òptim i allarga la vida útil de la bomba de condensats.

  • Inspecció mensual: Check the pump reservoir for sludge, mold, or debris. Clean as necessary.
  • Neteja: Disconnect power before cleaning. Remove the pump cover and clean the reservoir with a mild detergent and water. Ensure the float switch moves freely.
  • Línia de descàrrega: Inspect the vinyl tubing for blockages, kinks, or leaks. Clear any obstructions.
  • Inlet Ports: Ensure inlet ports are clear of debris.

Resolució de problemes

Consulteu la taula següent per veure els problemes habituals i les seves solucions.

Problema Causa possible Solució
La bomba no funciona No power; Clogged inlet/outlet; Stuck float switch; Motor failure Check power supply; Clear blockages; Inspect/clean float switch; Contact support if motor fails
La bomba funciona contínuament Stuck float switch; Leak in discharge line; Pump undersized for flow rate Inspect/clean float switch; Check for leaks; Verify pump capacity meets demand
Water overflow / Alarm LED on Pump failure; Clogged discharge line; Safety switch activated Check pump operation; Clear discharge line; Investigate cause of high water level
Excés de soroll/vibració Debris in pump; Improper mounting; Worn motor bearings Clean pump; Ensure secure mounting; Contact support for motor issues

Especificacions

Característica Detall
Marca Diversitech (Asurity)
Número de model CP-22LPT
Voltage 110 Volts
Font d'alimentació Elèctric amb cable
Ascensor màxim 22 peus
Caudal màxim 1.6 galons per minut
Dimensions del producte 12 cm de llargada x 6.75 cm d'amplada x 6 cm d'alçada
Pes de l'article 5.41 lliures
Material Plàstic
Color Vermell Negre
Components inclosos Condensate Pump, 20ft clear vinyl tubing, 4ft safety switch wire (pigtail)
Certificacions Llistat UL

Garantia i Suport

For warranty information or technical support, please contact Diversitech customer service. Keep your purchase receipt for warranty claims.

Fabricant: Diversitech

Weblloc: www.diversitech.com

Contacte: Consulteu el fabricant weblloc web per obtenir informació de contacte actualitzada.

Documents relacionats - CP-22LPT

Preview DiversiTech Condensate Pump Installation and Operation Manual
Comprehensive guide for installing and operating DiversiTech condensate pumps (CP-22, CP-22LP, CP-22T series). Includes safety instructions, specifications, installation steps, operation details, troubleshooting, and warranty information.
Preview DiversiTech Condensate Pump Installation and Operation Guide
This guide provides detailed instructions for installing, operating, and maintaining DiversiTech condensate pumps (CP-22 series). It covers safety precautions, specifications, package contents, step-by-step installation, troubleshooting, and warranty information.
Preview DiversiTech Plenum-Rated Condensate Pump Installation Guide
Comprehensive installation, operation, and maintenance guide for the DiversiTech CP-22LP-P and CP-22LP-230-P Plenum-Rated Condensate Pumps. Includes safety warnings, specifications, step-by-step installation instructions, troubleshooting tips, and warranty information.
Preview DiversiTech REDBOX MINI TUBE Mini Condensate Pump - Instruction Manual
Comprehensive instruction manual for the DiversiTech REDBOX MINI TUBE mini condensate pump, covering installation, specifications, component identification, service, maintenance, troubleshooting, and warranty for air conditioning systems up to 7kW.
Preview Hef-T-Bracket Installation Guide - 230-B2L
Installation instructions and specifications for the DiversiTech Hef-T-Bracket 230-B2L, a wall bracket for air conditioner condenser units.
Preview Diversitech HW-600 Wall Bracket Installation Guide for Mini Split Systems
Comprehensive installation guide for the Diversitech HW-600 wall bracket, designed for mounting mini split air conditioner outdoor units. Includes parts list, assembly instructions, and important safety information.