1. Introducció
The ABB THQLSURGE2 is a Type 1 Surge Protective Device (SPD) engineered to safeguard your entire electrical system and connected electronics from damaging power surges. This device offers comprehensive protection for both residential and commercial applications, enhancing the longevity and reliability of your valuable equipment by diverting excess voltage away from sensitive circuits.
2. Informació important de seguretat
ADVERTIMENT: Installation of this device involves working with high voltage electricity. To prevent electric shock, fire, or other hazards, installation must only be performed by a qualified and licensed electrician in accordance with all national and local electrical codes.
Per a la vostra seguretat, és crucial comprar només productes elèctrics originals fabricats per ABB (inclosos els de la marca GE o GE by ABB i els que ara són fabricats per ABB). Els productes falsificats i no autèntics poden no complir els estàndards de seguretat, cosa que us pot posar en risc. Per assegurar-vos que rebeu productes segurs i fiables, comproveu la descripció i les fotos del producte i verifiqueu que el producte es descriu com a producte ABB, GE o GE by ABB i que té etiquetes amb el logotip d'ABB, GE o GE by ABB. Consulteu també la descripció del producte per veure si ha estat certificat per organismes de certificació externs com ara UL, IC i/o Intertek.
3. Configuració i instal·lació
The THQLSURGE2 is designed for plug-on installation, making it suitable for service entrances, subpanel locations, or directly within compatible PowerMark™ load centers. This device requires two full panel spaces for proper installation.
Installation Steps (to be performed by a qualified electrician):
- Ensure all power to the electrical panel is turned off at the main breaker before beginning installation.
- Identify two adjacent, vacant breaker slots within the compatible load center.
- Carefully insert the THQLSURGE2 into the designated slots, ensuring a secure connection.
- Connect the pigtail wiring according to the wiring diagram provided with the product and local electrical codes. Typically, the white wire connects to the neutral bus bar and the bare copper wire connects to the ground bus bar.
- Comproveu que totes les connexions siguin estancades i segures.
- Restore power to the electrical panel.
- Confirm the green LED indicator on the front of the device is illuminated, indicating proper operation.

This image displays the front of the ABB THQLSURGE2 surge protector, highlighting its compact design and the visible status indicator. The label clearly states 'Type 1 Surge Protective Device', 'THQLSURGE2', 'UL 1449 5th Edition', and '120/240VAC'. It also indicates 'Green = PROTECTED' and 'No light = REPLACE UNIT', which are crucial for operational status checks.
4. Instruccions de funcionament
The ABB THQLSURGE2 operates automatically to protect your electrical system from surges. Once installed and powered, it continuously monitors the incoming power lines.
- Indicador LED verd: A continuously illuminated green LED on the front of the device signifies that the surge protector is active and providing protection.
- No LED Light: If the green LED is off, it indicates that the surge protective device has absorbed a significant power surge and is no longer functional. In this state, the unit requires replacement to restore surge protection.
5. Manteniment
The ABB THQLSURGE2 is a maintenance-free device in terms of internal components. The primary maintenance task is to regularly check its operational status.
- Inspecció mensual: It is recommended to visually inspect the green LED indicator on the front of the device at least once a month.
- Substitució: If the green LED is off, the device has reached its end-of-life and must be replaced by a qualified electrician to ensure continued surge protection for your home or office.
6. Solució De Problemes
Most issues related to the THQLSURGE2 can be identified by observing the LED indicator.
| Símptoma | Causa possible | Acció |
|---|---|---|
| Green LED is off | Device has absorbed a significant surge and is no longer functional. | The unit requires replacement. Contact a qualified electrician. |
| Green LED is off immediately after installation | Improper installation or no power to the device. | Verify proper installation and ensure power is supplied to the panel. If issues persist, contact a qualified electrician. |
7. Especificacions
Key technical specifications for the ABB THQLSURGE2 Surge Protective Device:
- Marca: FIG
- Número de model: THQLSURGE2
- Tipus: Dispositiu de protecció contra sobretensions tipus 1 (SPD)
- Volum nominaltage: 120/240 VCA, 50/60 Hz
- Valoració actual: 20 Amps
- Tipus d'interruptor: Estàndard
- Tipus de muntatge: Muntatge endollable
- Nombre de pols: 2
- Nominal Discharge Current (In): 10 kA
- Maximum Discharge Current (Imàx): 25 kA
- Volum de funcionament continu màximtage (MCOV): L-N 150V, L-L 300V
- Voltage Classificació de protecció (VPR): 1kV, 3kA: 600V (L-N), 1000V (L-L)
- Compliment: UL 1449 5th Edition, NEC 2023 Article 230.67
- Pes de l'article: 7 unces
- Dimensions del paquet: 6.69 x 5.35 x 2.28 polzades
- Color: Blanc
- UPC: 783164678246

Aquesta imatge ofereix un costat view of the THQLSURGE2, revealing additional technical specifications printed on the casing. Details include Nominal Voltage (120/240VAC 50/60Hz), In (10kA), Imàx (25kA), MCOV (MAC) values for L-N and L-L, and VPR (1kV, 3kA) values. The attached wiring pigtail is also visible, indicating its connection method.

Un angle view of the ABB THQLSURGE2, illustrating its physical dimensions and how the wiring pigtail extends from the bottom. This perspective helps in understanding the device's footprint for installation within an electrical panel.
8. Informació de la garantia
For detailed warranty information regarding your ABB THQLSURGE2 Surge Protective Device, please contact ABB customer service directly. Warranty details, terms, and conditions may also be available on the official ABB weblloc.
9. Suport i contacte
For technical assistance, product inquiries, or further support, please visit the official ABB website or contact their customer support department. Ensure you have your product model number (THQLSURGE2) available when seeking support.