Walfront NLQ3-125/2P

WALFRONT NLQ3-125/2P Dual Power Automatic Transfer Switch User Manual

Model: NLQ3-125/2P | Brand: Walfront

1. Producte acabatview

The WALFRONT NLQ3-125/2P Dual Power Automatic Transfer Switch (ATS) is designed to ensure a continuous and reliable power supply by automatically switching between a primary and backup power source. This 2-pole, 100A, AC110V controller provides immediate backup, ensuring continuity and safety when the normal power supply is interrupted. It is suitable for a wide range of applications including homes, shopping malls, factories, laboratories, and farms, offering interference-free technology. Constructed from flame-retardant PC materials and featuring silver contacts, this ATS offers insulation, high temperature resistance, and long-term reliability.

The device supports both automatic and manual operation modes, allowing for flexible control over your power supply system. Its integrated design and 35mm standard rail mounting make it suitable for PZ30 distribution boxes.

WALFRONT NLQ3-125/2P Dual Power Automatic Transfer Switch

Figure 1: WALFRONT NLQ3-125/2P Dual Power Automatic Transfer Switch.

2. Especificacions

EspecificacióValor
Tipus d'elementInterruptor de transferència automàtica de doble potència
Model de producteNLQ3-125/2P
MaterialPC flame retardant + silver alloy
Tipus de canviSecondary power distribution
Corrent nominal100A
Bobina Voltage110 V AC
Aïllament VoltageAC690V AC
VoltageAC400V AC
Freqüència nominal50 Hz/60 Hz
Nivell elèctricPC isolation type
Resistència d'impuls nominal Voltage8KV
Control Circuit Rated Control Voltage NosaltresAC110V 85%-110% Us
Auxiliary Circuit CapacityTwo Relays, Each With Two Sets of AC110V50HZ le=5y
Tipus de muntatgeWall Mount (35mm standard rail mounting)
Dimensions del producte4.72 x 3.93 x 3.54 polzades (109 mm x 97 mm x 69 mm)
Pes de l'article1.33 lliures
Mode d'operacióON-OFF (Automatic/Manual)
Especificació MetISO 9001
Dimensions of the WALFRONT NLQ3-125/2P Automatic Transfer Switch

Figure 2: Product dimensions (109mm/4.3in, 97mm/3.8in, 69mm/2.7in).

3. Safety Information and Environmental Conditions

Before installation and operation, please read and understand all safety warnings and environmental requirements.

3.1 Condicions ambientals

  • La temperatura ambient màxima no ha de superar els 40 ℃.
  • The minimum ambient temperature should not be lower than -5℃.
  • The average temperature within 24 hours should not be higher than 35℃.
  • The altitude of the installation site should not be higher than 2000 meters.
  • When the maximum temperature reaches 40℃, the relative humidity of the installation site should not exceed 50%.
  • When the temperature is at its lowest (-5℃), the relative humidity may be higher. For example, at 25℃, the relative humidity can be 90%. Special measures should be taken to address occasional condensation on product surfaces due to temperature changes.

3.2 Precaucions generals de seguretat

  • Ensure the integrity of the ATS before installation.
  • All electrical work must be performed by qualified personnel in accordance with local electrical codes and regulations.
  • Always disconnect power before performing any installation, maintenance, or inspection.
  • No feu funcionar l'interruptor si sembla que està danyat.
  • Assegureu-vos de posar a terra correctament per evitar descàrregues elèctriques.

4. Configuració i instal·lació

The WALFRONT NLQ3-125/2P ATS is designed for 35mm standard rail mounting, typically within a PZ30 distribution box.

4.1 Comprovació prèvia a la instal·lació

Before installation, carefully inspect the ATS for any signs of damage or defects. Use the operating handle to manually open or close the ATS to check the flexibility of the transmission device. Test the generation and disconnection conditions of the load for each phase of the primary and backup power sources to ensure proper functionality.

4.2 Instruccions de cablejat

Refer to the wiring diagram below for correct connection of the primary (Normal Power A) and backup (Reverse Power B) power sources, as well as the load output and control lines.

Wiring diagram for WALFRONT NLQ3-125/2P Automatic Transfer Switch

Figure 3: Wiring diagram showing connections for Normal Power A, Reverse Power B, Load Output, Common Feed, Common Control Line, and Stand-by Control Line.

  • Normal Power A: Connect your primary power source to the designated terminals.
  • Reverse Power B: Connect your backup power source (e.g., generator, solar inverter) to the designated terminals.
  • Sortida de càrrega: Connect the output terminals to your electrical load.
  • Control Lines: Connect the common feed, common control line, and stand-by control line as indicated in the diagram for automatic operation.
Close-up of input/output terminals on the WALFRONT NLQ3-125/2P ATS

Figura 4: Primer pla view of the input and output terminals for wiring connections.

WALFRONT NLQ3-125/2P ATS installed inside a waterproof plastic box

Figura 5: Example installation of the ATS within a waterproof plastic box for protection.

5. Instruccions de funcionament

The WALFRONT NLQ3-125/2P ATS offers both automatic and manual operation modes.

5.1 Selecció del mode

Locate the mode selection switch on the device. It typically has positions for "Auto" and "Manual".

Close-up of the WALFRONT NLQ3-125/2P ATS showing the manual/auto switch

Figure 6: The mode selection switch for automatic or manual operation.

5.2 Funcionament automàtic

Set the mode selection switch to "Auto". In this mode, the ATS will automatically detect the presence and stability of the primary power source (Normal Power A). If the primary power fails or becomes unstable, the switch will automatically transfer the load to the backup power source (Reverse Power B) within milliseconds, ensuring an uninterrupted power supply. When the primary power is restored, the ATS will automatically switch the load back to the primary source.

5.3 Funcionament manual

Set the mode selection switch to "Manual". In this mode, the user can manually switch between the primary and backup power sources using the operating handle. This mode is useful for testing, maintenance, or specific scenarios where manual control is preferred. Always ensure power is disconnected or appropriate safety measures are taken during manual switching.

6. Manteniment

The WALFRONT NLQ3-125/2P ATS is designed for reliable, long-term operation with minimal maintenance. However, periodic inspection is recommended to ensure optimal performance and safety.

  • Inspecció visual: Regularly check the device for any signs of physical damage, loose connections, or overheating.
  • Neteja: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
  • Comprovació del terminal: Periodically verify that all wiring terminals are securely tightened.
  • Prova funcional: If safe to do so, periodically test the automatic transfer function by simulating a primary power failure to ensure the switch operates correctly.

Desconnecteu sempre l'alimentació de la unitat abans de realitzar qualsevol manteniment o inspecció.

7. Solució De Problemes

If the WALFRONT NLQ3-125/2P ATS is not functioning as expected, consider the following basic troubleshooting steps:

  • No Power Transfer:
    • Check if both primary and backup power sources are active and stable.
    • Ensure the mode selection switch is set to "Auto" for automatic transfer.
    • Verifiqueu que totes les connexions de cablejat siguin segures i correctes segons el diagrama de cablejat.
  • Funcionament intermitent:
    • Comproveu si hi ha connexions de cablejat soltes als terminals.
    • Ensure environmental conditions (temperature, humidity) are within specified limits.
  • El dispositiu no respon:
    • Confirm that the control circuit is receiving the correct voltage (AC110V).
    • If the device is completely unresponsive, consult a qualified electrician.

For complex issues or if troubleshooting steps do not resolve the problem, it is recommended to contact a qualified electrician or the product manufacturer for assistance.

8. Àrea d'aplicació

The WALFRONT NLQ3-125/2P Dual Power Automatic Transfer Switch is versatile and designed for various environments where continuous power supply is critical. Its robust design ensures reliable operation in diverse settings.

  • Residencial: Ensuring uninterrupted power for homes, especially during outages.
  • Comercial: Maintaining power in shopping malls, offices, and other commercial establishments.
  • Industrial: Critical for factories and industrial facilities to prevent production downtime.
  • Agricultural: Providing reliable power for farms and nurseries.
  • Laboratoris: Essential for maintaining power to sensitive equipment.
Application areas for the WALFRONT ATS including household, shopping malls, company power, and factory power

Figura 7: Examples of application areas: household electricity, shopping malls, company power consumption, and factory power.

Aplicació addicional examples for the WALFRONT ATS in factories, shopping malls, and nurseries

Figure 8: Additional application examples: factories, shopping malls, and nurseries, highlighting its wide usability.

Documents relacionats - NLQ3-125/2P

Preview EARU ELECTRIC EAATS-A Series Din Rail ATS Instruction Manual
Instruction manual for the EARU ELECTRIC EAATS-A Series Din Rail Automatic Transfer Switch (ATS). Covers safety, product description, and technical specifications for reliable dual-power supply systems.
Preview Catàleg de commutadors de transferència automàtica de doble font de la sèrie MATSN d'Eaton
Catàleg complet que detalla els interruptors de transferència automàtica de doble font de la sèrie MATSN d'Eaton, amb especificacions del producte, guies de selecció, dades tècniques i informació de cablejat per a una gestió d'energia fiable.
Preview EARU EAATS-A Series ATS Dual Power Switch - English Manual
Comprehensive English manual for the EARU EAATS-A Series Dual Power Automatic Transfer Switch. Covers general information, installation conditions, technical parameters, wiring diagrams, maintenance, and safety precautions for reliable power supply switching.
Preview Eaton MATSN Series Dual Source Automatic Transfer Switch | Product Catalog & Specifications
Explore the Eaton MATSN Series Dual Source Automatic Transfer Switch. This document details features, technical specifications, controller functions, wiring diagrams, dimensions, and a comprehensive selection guide for reliable power transfer solutions.
Preview EARU Automatic Transfer Switch (ATS) Operating Instruction and Technical Specifications
Comprehensive operating instructions and technical specifications for the EARU Automatic Transfer Switch (ATS) model EAATS-F-CG-80. Covers product overview, working conditions, model breakdown, detailed technical parameters, installation guidelines, maintenance procedures, and wiring diagrams.
Preview ECOFLOW Automatic Transfer Switch User Manual V1.0
Comprehensive user manual for the ECOFLOW Automatic Transfer Switch (ATS) V1.0, detailing its features, installation, technical specifications, wiring, and frequently asked questions for reliable power backup solutions.