Nemtek Communications Task
DESCRIPTION OF THE NEMTEK COMMUNICATIONS TASK
The Nemtek communications task provides a high-level interface between the Integriti controller and the Nemtek Electric Fence Energizers, I/O Cards, and Terminal.
Automation points are used as part of the Nemtek Electric fence integration to map Integriti entities to NEMTEK entities (e.g., Nemtek Energizers).
The NEMTEK communications task scans over the Integriti entities used within the Automation Points for changes and sends data to NEMTEK Electric Fence Energizers.
The NEMTEK communications task also processes incoming messages from NEMTEK and can update the Integriti entities.
The NEMTEK communications task
- Requires a High Security Fence IP HLI license (IR-996025)
- One IR-996025 interface is required for each Nemtek Druid or I/O module being integrated.
- Requires a SMART card to be fitted to the IAC/ISC
Configuring the communications task
To create the Automation communications task, follow the procedure below
- Feu clic a
tabulació seguida de
. - Feu clic
to create a new communications task. - In the window that appears, enter a name for the communications task and enter any necessary notes in the notes field.
- Under Comms Task Setup, drop down the type list box and select NEMTEK.
- Optionally, set an input that will be used to reflect the status of the communications task.

Inputs C01:Z33-Z99 are ideal for this particular application.
This input will go in to alarm if the communications task fails.
For TCP connections to the NEMTEK Automation system - Expand the Configuration Tab.
- Enter the IP address of the NEMTEK Electric Fence Terminal in the IP Address field.
The NEMTEK Communications task can only be configured for a static address. - Enter the port in the TCP Port field.
- Expand Out the Energizers Tab.
- Map each Electric Fence Energizer to a Virtual module.

- Expand the IO Cards Tab.
- Map each IO Card in the system to a Virtual Module.

- Save and close the editor window for the Communications Task.
- Next, Right-click on the Nemtek Comms Task and select

This will automatically set the names of all Inputs and Auxiliaries on the configured virtual modules. Configuring automation points is not required.
Creating Analog Calibrations for Nemtek Inputs/Outputs
Analog Calibrations are used to map NEMTEK Electric Fence Energizers High Voltage and Supply Voltage to Integriti entities.
You will need to create Analog Calibrations for NEMTEK High Voltage and Supply Voltage Auxiliary Entities you want to control or monitor.
To create an Automation Point, follow the procedures below.
Creating Analog Calibrations for Nemtek High Voltage Sortida
- Feu clic a
tabulació seguida de
. - Feu clic
to create a new communications task. - In the window that appears, enter a name for the communications task and enter any necessary notes in the notes field. e.g NEMTEK HV.
- Under Calibration Linear Component, Gain = 125, Shift = 0
- Expand the Display Tab
- Set Format/Scale to “K0F5.0”
- Set Display String to “Volts”.
- Save and close the editor window for the Analog Calibration.
- Navigate to the Auxiliaries of Energizer 1

- Set the Analog Calibration of

a,
- Repeat Steps 9 & 10 for each energizer.
The Zone Output High Voltage Aux value is Bi-directional and can be set using the Integriti software or via the Nemtek Electric Fence Terminal.
Creating Analog Calibrations for Nemtek Supply Voltage Sortida
- Feu clic a
tabulació seguida de
. - Feu clic
to create a new communications task. - In the window that appears, enter a name for the communications task and enter any necessary notes in the notes field. e.g NEMTEK HV.
- Under Calibration Linear Component, Gain = 125, Shift = 0
- Expand the Display Tab
- Set Format/Scale to “K3F2.3”
- Set Display String to “Volts”.
- Save and close the editor window for the Analog Calibration.
- Navigate to the Auxiliaries of Energizer 1.
- Set the Analog Calibration of

a,
- Repeat Steps 9 & 10 for each energizer.

The Analog Aux Supply Voltage value is set by the Nemtek Electric Fence Terminal and is only monitored by the Integriti system.
Seu Global
| Gamma interior Austràlia +61 3 9780 4300 sales.au@innerrange.com |
Gamma interior Estats Units +1 844-588-0874 sales.usa@innerrange.com |
| Gamma interior Regne Unit +44 (0) 845 470 5000 sales.uk@innerrange.com |
Gamma interior Canadà +1 844-588-0874 sales.canada@innerrange.com |
| Gamma interior Orient Mitjà +971 4 8067100 sales.me@innerrange.com |
Interior Range India +91 80 4070 3333 sales.india@innerrange.com |
desembre 2025
Les especificacions i descripcions dels productes i serveis contingudes en aquest document eren correctes en el moment de la publicació.
Inner Range es reserva el dret de canviar les especificacions o retirar productes sense previ avís.
Copyright ©2025 Inner Range Pty. Ltd., Austràlia
INNERRANGE.COM
Copyright © Inner Range PTY LTD December 2025![]()
Documents/Recursos
![]() |
Inner Range Nemtek Communications Task [pdfGuia de l'usuari Nemtek Communications Task, Communications Task, Task |